Laserfiche WebLink
FIRE DEPARTMENT <br /> r <br /> TO: Teresa Weldon, Planning <br /> FROM: Jim Venturo, Assistant Fire Marshal <br /> DATE: 12/7/17 <br /> SUBJECT: SEPA #17-020 <br /> 909 N Broadway <br /> 1. Flammable Finishes & Spraying - Provide a portable fire extinguisher with a minimum U.L. <br /> rating of 4-A:40-B:C within 30 feet or 4-A:80-B:C within 50 feet of the spray area. 2015 IFC, <br /> Table 906.3(2). <br /> Note: Paint booth suppression shall be sprinklers. Existing building's sprinkler system <br /> can be used to protect spray booth. <br /> A separate flow and tamper shutoff is required on spray booth. <br /> Flow and tamper switch shall be wired into building's fire alarm system as its own zone. <br /> EVERETT FIRE DEPARTMENT•2930 Wetmore Avenue Ste 7A• Everett WA 98201-4067• (425)257-8100• Fax(425)257-8139 <br />