Mechanical Specifications <br /> General Condenser Coil— Single Source Power Entry —This ac- <br /> The units shall be horizontal airflow as The Spine Fin TMcondenser coil shall be cessory when used with electric heat <br /> shipped and convertible to downflow. All continuously wrapped, corrosion resis- accessory shall allow single source power <br /> units shall be factory assembled, piped, tant all aluminum with minimum brazed connection to unit and heater combina- <br /> internally wired and fully charged with joints.This coil is 3/8 inch O.D.seamless tion. Single source power entry kits shall <br /> refrigerant. All units shall be factory run aluminum tubing glued to a continuous have specific matching heater(s). Kit <br /> tested to check cooling operation,fan and aluminum fin.Coils are lab tested to shall include high voltage terminal blocks, <br /> blower rotation and control or TXV se- withstand 2,000 pounds of pressure per fuse blocks and fuses, cut-to-length in- <br /> quence.Units shall be designed to operate square inch.The outdoor coil provides terconnecting wiring, and junction box (if <br /> at ambient temperatures between 115°F low airflow resistance and efficient heat required) to provide power sources with <br /> and 55°F in cooling as manufactured. transfer.The coil is protected on all four fuse protection as required for both the <br /> Cooling performance shall be rated in ac- sides by louvered panels. unit and accessory heater. Kit compo- <br /> cordance with A.H.R.I.standards. Indoor Air Fan—Direct-drive,forward- nents shall install within the unit cabinet in <br /> Unit Casing curved,centrifugal wheel in a Composite the heater access section. Single source <br /> All components shall be mounted in a Vortica® Blower housing.Motor shall branch power circuit shall be protected and <br /> weather-resistant steel cabinet with an have thermal overload protection. wired in accordance with local codes. <br /> enamel finish.Access panels shall be pro- Permanently lubricated motor bearings. Fully Modulating Economizer — This <br /> vided for unit controls and indoor coil and Motor/blower assembly isolated from unit accessory shall be field installed and be <br /> fans. Indoor air section compartment shall with rubber mounts. composed of the following items: 0-100% <br /> be completely insulated with fireproof, Condenser Fan—Direct-drive, draw fresh air damper,damper drive motor,fixed <br /> permanent, odorless glass fiber material. dry bulb enthalpy control, and low voltage <br /> Knockouts shall be provided for utility and perthru propeller type.Weather-proofed <br /> split capacitor fan motor shall wiring plug for electrical connections.Solid <br /> control connections. Drain connections per state enthalpy or differential enthalpy con- <br /> shall be provided to accommodate indoor have built-in thermal overload and per- trol is optional. Economizer operations <br /> water runoff. manently lubricated motor bearings. shall be controlled by the preset position <br /> Compressor System Controls of the enthalpy control. A barometic relief <br /> The compressor shall be hermetically System controls include condenser fan, damper shall be standard with the econo- <br /> sealed, high efficiency Climatuff° com- evaporator fan and compressor contac- mizer and provide a pressure operated <br /> pressors. Internal overcurrent and over tors. damper that shall be gravity closing and <br /> temperature protection, internal pressure Accessories prohibit entrance of outside air on equip- <br /> relief shall be standard. Roof Curb—The roof curb shall be de- ment "off' cycle. Economizer requires <br /> Refrigeration System signed to mate with the unit and provide BAYRLAY004A relay kit to interface the <br /> All units shall have TXV in cooling and TXV support and complete weathertight instal- economizer to the heat pump. <br /> in heating.Service pressure tap ports,and lation when properly installed. Adhesive Manual Outside Air Dampers — Rain <br /> a refrigerant line filter dryer shall be Stan- back polyurethane sealing strips shall be hood and screen shall be field installed. <br /> dard. provided to ensure an airtight seal be- Suitable for up to 25%outside air. <br /> Indoor Coil tween supply and return openings of the Start Kit— Extra compressor starting ca- <br /> Coils shall be internally finned or smooth curb and unit.The roof curb design allows pacity for single phase equipment. <br /> field fabricated ductwork to be connected <br /> bore 3/8" copper tubes mechanically directly to the curb. Curb ships knocked Control Options <br /> bonded to configured aluminum plate down for field assembly, and includes Standard Indoor Thermostats — Two <br /> fin as standard. Evaporator coil leak and factory-installed wood nailer strips. stage heating/cooling or one stage heat- <br /> pressure tested to 200 psig; condenser ing/cooling thermostats shall be available <br /> coil tested to 450 psig. Electric Heaters—Each heater assem- in either manual or automatic changeover. <br /> bly shall include power supply fusing if <br /> over 48 amps, automatic resetting limit Programmable Electronic Night Set- <br /> switches and heat limiters for thermal back Thermostat — Programmable <br /> protection.Heaters shall be provided with electronic thermostat shall provide heat- <br /> polarized plugs for quick connection to ing setback and cooling setup with 7-day, <br /> unit low voltage wiring.Electric heat mod- programming capability. 1 H/1 C or 2H/2C <br /> ules shall be UL listed. models available. <br /> Unitary Small AHRI Standard 4 <br /> C US <br /> • 1 / USTEO <br /> ntertek <br /> Trane The manufacturer has a policy of continuous product and product data improvement and it reserves the right <br /> 6200 Troup Highway to change design and specifications without notice <br /> Tyler, TX 75707-9010 <br />