Laserfiche WebLink
TOLBraceTM Seismic Calculations <br /> BP Everett 500'B' Job#112357 T <br /> 5900 36TH AVE WEST F,�,i�*N <br /> Powering Business 1AieridWide <br /> Brace Identification SB-101110 <br /> Brace Type(Per NFPA#13) NFPA Type F <br /> Braced Pipe(ft) 4"Sch.10 Steel Pipe <br /> Spacing of Brace 60'0"(18.29 m) <br /> Orientation of Brace Longitudinal <br /> Bracing Material 1"Sch.40 <br /> Maximum Brace Length 7'0"(2.13 m) <br /> Slenderness Ratio used for Load Calculation 200 <br /> True Angle of Brace for Calculation 60° <br /> Type of Fastener Fig.828 Across 1/2"-7/8" Thick Flange Beam <br /> Length of Fastener N/A <br /> Summary of Pipe within Zone of Influence <br /> 4"Sch.10 Steel Pipe(101.6 mm) 160 ft(18.3 m) <br /> • <br /> G-Factor Used 0.6452 <br /> Allowance for Heads and Fittings 15% <br /> Conclusions <br /> Total Adjusted Load of Pipe in Zone of Influence 524 lbs(238 kg) <br /> Material Capacity 1604 lbs(728 kg) <br /> Fastener Capacity 1186 lbs(538 kg) <br /> Fig.4L Clamp 1732 lbs(785 kg) <br /> Fig.980- 1/2" Universal Swivel 1818 lbs(825 kg) <br /> Structural Member W <br /> Calculations prepared by Ethan Nelson <br /> *The description of the Structural Member is for informational purposes only. <br /> TOLBrace'"'software calculates the brace assembly only,not the structure it is attached to. <br /> Calculated with TOLBrace"'8 <br /> Visit us at www.tolco.com <br /> • <br />