Laserfiche WebLink
Bulletin 036 January 2023 <br /> Reilabli ® Model KFR56 Series Sprinklers <br /> Quick-response, Standard Spray Fusible Link Sprinklers <br /> K5.6(80 metric)' <br /> cULus Listed, FM Approved,VdS Approved,CE CertifiedIF 1101.1111MIL. <br /> Product Description <br /> Model KFR56 series sprinklers are standard spray,quick-response :': <br /> sprinklers with a fusible link operating element. The sprinklers are ► 1111 <br /> cULus Listed, FM Approved, VdS Approved, and CE Certified. <br /> See Table C for available finishes. All KFR56 sprinklers have a +$ 1 <br /> nominal K-factor of 5.6(80 metric). • — <br /> -114 <br /> Model KFR56 series sprinklers are available in Ordinary (165°F <br /> [74°C])or Intermediate(212°F[100°C])temperature classification. Model KFR56 Pendent Model KFR56 Upright <br /> Model KFR56 Pendent sprinklers are available with Model F1, <br /> Model F2,or Model FP recessed escutcheons. <br /> Application_ <br /> Model KFR56 series sprinklers are listed and approved for '",.. 011111 <br /> installation in accordance with NFPA 13 and FM Loss Prevention Data Sheets. Follow requirements of NFPA 13 for Quick-response <br /> Standard Spray Sprinklers when installing Model KFR56 series <br /> sprinklers. FM Approvals classifies Model KFR56 sprinklers as <br /> K5.6 QR Non-storage and K5.6 QR In-rack Storage sprinklers. Model CCP Model KFR56 HSW <br /> Installation <br /> Model KFR56 series sprinklers must be installed in accordance <br /> with the requirements of NFPA 13 or FM Property Loss Prevention Exceeding the maximum recommended torque may cause leakage • <br /> Data Sheets. The Model F1, F2, and FP escutcheons are the or impairment of the sprinklers. <br /> only recessed escutcheons listed and approved for use with <br /> Model KFR56 Pendent sprinklers. The use of any other recessed Listings & Approvals <br /> escutcheon will void all approvals and warranties. Do not install <br /> Model FP escutcheons in ceilings that are positively pressurized Listed by Underwriters Laboratories, Inc. and UL Certified for <br /> with respect to the occupied space below. Canada (cULus) <br /> • <br /> Use only the Model W2 sprinkler wrench for installing Model Sprinklers,Automatic and Open (VNIV) <br /> KFR56 series pendent, upright, and horizontal sidewall sprinklers, FM Approved(FM) <br /> and use the Model W1 or W4 wrench for installing Model KFR56 • K5.6 QR Non-storage <br /> series recessed pendent, conical concealed pendent(CCP), and • K5.6 QR In-rack Storage <br /> recessed horizontal sidewall sprinklers.The use of wrenches other <br /> than those specified may damage these sprinklers. VdS Approved and CE Certified to EN12259 <br /> Recommended installation torque is 14-20 ft-lbs (19 — 27 N.m). UKCA:0832-UKCA-CPR-S5073, -5074,-5075 <br /> Do not tighten sprinklers over the maximum recommended torque. <br /> Model KFR Series Sprinkler Summary Table A <br /> Max.Working Sprinkler <br /> Sprinkler Model Orientation Listing or Approval Pressure Identification <br /> psi(bar) Number(SIN) <br /> cULus 250(17.2) <br /> KFR56 Pendent Pendent RA3614 <br /> FM,VdS,CE, UKCA 175(12) <br /> KFR56 Upright cULus 250(17.2) <br /> KFR56 Upright Intermediate Upright FM,VdS,CE, UKCA 175(12) RA3624 <br /> 11111 <br /> cULus 250(17.2) <br /> KFR56 HSW HSW RA3634 <br /> FM,VdS, CE, UKCA 175(12) <br /> www.reliablesprinkler.com <br />