Laserfiche WebLink
f <br /> WATER SUPPLY DATA <br /> Ili <br /> SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D <br /> NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. <br /> TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) <br /> SRC 73.0 59.0 2000.0 61.8 1773.2 57.5 <br /> Available pressure is 4 .3 psi (7%) greater than required pressure. <br /> AGGREGATE FLOW ANALYSIS: <br /> TOTAL FLOW AT SOURCE 1773.2 GPM <br /> TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM <br /> OTHER HOSE STREAM ALLOWANCES 250.0 GPM <br /> TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 1523.2 GPM <br /> NODE ANALYSIS DATA <br /> NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE <br /> (FT) (PSI) (GPM) <br /> S1 34 . 9 K=25.20 25.0 126.1 <br /> S2 34 . 9 K=25.20 25.0 126.0 <br /> S3 34 . 9 K=25.20 25.1 126.14110 <br /> S4 34 . 9 K=25.20 25.4 127.0 <br /> S5 34 .9 K=25.20 25.5 127.2 <br /> S6 34 .9 K=25.20 25.4 127.0 <br /> S7 34 .9 K=25.20 25.4 127.1 <br /> S8 34 . 9 K=25.20 25.7 127.8 <br /> S9 34 . 9 K=25.20 25.4 127.1 <br /> S10 34 . 9 K=25.20 25.4 127.0 <br /> S11 34 . 9 K=25.20 25.4 127.1 <br /> S12 34 . 9 K=25.20 25.7 127.8 <br /> UG1 18.0 - - - - 68.9 - - - <br /> UG2 -5.0 - - - - 78.2 - <br /> UG3 -5.0 - - - - 75. 9 - - - <br /> UG4 -5.0 - - - - 74.2 - - - <br /> UG5 -8.0 HOSE STREAM 72.0 250.0 <br /> FLG 0.5 - - - - 66.7 - - - <br /> DC1 2.0 - - - - 65.8 - - - <br /> DC2 2.0 - - - - 58.3 - - - <br /> BR 2.0 - - - - 58.2 - - - <br /> TR 32.0 - - - - 42.9 - - - <br /> 100 33.5 - - - - 38.0 - - - <br /> 101 33.5 - - - - 37.9 - - - <br /> 102 33.5 - - - - 37.4 - - - <br /> 103 33.5 - - - - 36.9 - - - <br /> 104 33.5 - - - - 36.5 - - - <br /> 105 33.5 - - - - 36.24111 <br /> - - - <br /> 106 33.5 - - - - 35.9 - - <br />