Laserfiche WebLink
WATER SUPPLY DATA <br /> SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D <br /> NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. <br /> TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) <br /> SRC 73.0 59.0 2000.0 61.9 1765.3 56.3 <br /> Available pressure is 5. 6 psi (9%) greater than required pressure. <br /> AGGREGATE FLOW ANALYSIS: <br /> TOTAL FLOW AT SOURCE 1765.3 GPM j <br /> TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM <br /> OTHER HOSE STREAM ALLOWANCES 250.0 GPM <br /> TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 1515.3 GPM <br /> NODE ANALYSIS DATA <br /> NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE <br /> (FT) (PSI) (GPM) <br /> Si 32.2 K=25.20 25.2 126.6 <br /> S2 32.2 K=25.20 25.1 126.2 <br /> S3 32.2 K=25.20 25.1 126.2ill <br /> S4 32.2 K=25.20 25.2 126. 6 <br /> S5 32.2 K=25.20 25.2 126.4 <br /> S6 32.2 K=25.20 25.0 126.0 <br /> S7 32.2 K=25.20 25.0 126.0 <br /> S8 32.2 K=25.20 25.2 126.4 <br /> S9 32.2 K=25.20 25.1 126.4 <br /> S10 32.2 K=25.20 25.0 126.0 <br /> Sli 32.2 K=25.20 25.0 126.0 <br /> S12 32.2 K=25.20 25.1 126.4 <br /> UG1 18.0 - - - - 67.8 - - - <br /> UG2 -5.0 - - - - 77.0 - - - <br /> UG3 -5.0 - - - - 74 .8 - - - <br /> UG4 -5.0 - - - - 73.0 - - - <br /> UG5 -8.0 HOSE STREAM 70.9 250.0 <br /> FLG 0.5 - - - - 65.6 - - - <br /> DC1 2.0 - - - - 64 .7 - - - <br /> DC2 2.0 - - - - 57 .2 - - - <br /> BR 2.0 - - - - 57.1 - - - <br /> TR 32 .0 - - - - 41.8 - - - <br /> 99 33.5 - - - - 40.0 - - - <br /> 100 33.5 - - - - 39.2 - - - <br /> 101 33.5 - - - - 40.0 - - - <br /> 102 33.5 - - - - 39.3 - - - <br /> 103 33.5 - - - - 39.2 - - - <br /> 104 33.5 - - - - 38.8 - - - <br /> 105 33.5 - - - - 38.5 - - - <br />