Laserfiche WebLink
Calculation: Strut Grid Design {1-31 <br />Vert. strut to existing struss attachment: <br />Vert. load: 499.06 lb <br />Angle clip: (2) B-line B115 clips with 1/2" dia. Thru bolts with strut nuts <br />Brace Bracket Design: <br />Try: (1) B Line B 115 Bracket <br />T.: 249.5 lb (ASD) <br />Angle thickness: 0.25 in. <br />Load ecc, e: 1.875 in. <br />Ind. Mom: 0.47 k-in. <br />Angle width: 1.625 in. <br />Sy: 0.017 in3 <br />Zy: 0.025 in3 <br />Allow mom: 0.50 k-in. <br />Unity: 0.933 OK <br />Try: (2) B441-22A beam clamp <br />Tm : 499.06 lb (ASD) <br />Allow load: 1850 lb (ASD) <br />Unity check: 0.27 OK <br />13115it <br />Four Hale Corner Angle <br />Standard finishes: ZN, GRN, HDG, <br />SS4, AL <br />• Wt.JC 76 Lbs. (34_5 kg) <br />PA GRN ['� 33/4' <br />(95.2) <br />4 L1C1t3.ti9 <br />PA Pre -assembled fitting <br />B441-22A <br />Beam Clamp <br />• Design Load 1650 Lbs_ W.23 kN) <br />when used in pairs <br />• Safety Factor of 5 <br />• 1-i* (19.0) Max. flange thickness <br />• For use with 1rlh.141.3) to 31/4' 482.5; <br />high channel <br />« Recommended Torque: 150 in-lbs. <br />(16.9 Nem) <br />• Sold in pieces <br />• Other flange thickness variations are <br />available, contact us for sizes <br />• Standard finishes: ZN, HDG, SS4 <br />• Wt./C 93 Lbs. I42.2 kg) <br />3' <br />1 "/," <br />(76 2) <br />(47.61 <br />i <br />6 <br />(25.4) <br />(127.0) <br />(6.3) <br />28 134th St. SW, Ste 200, Everett, WA 98204 1 (425) 741-3800 <br />roject: Boeing Bldg 40-56 Pg. No: H - 3 <br />address: 3003 W Casino Rd, Everett, WA 98204 Date: 2/6/24 <br />'lient: Sazan Group Job No.: 262024.011 <br />a <br />Paae 11 of 11 <br />