Laserfiche WebLink
PROGRAMMING AND SOFTWARE <br />• Autoprogramming (learn mode) reduces installation time <br />• Custom English labels (per point) may be manually entered or <br />selected from an internal library file <br />• Two programmable Form-C relay outputs <br />• 99 software zones <br />• Continuous fire protection during online programming <br />• Program Check automatically catches common errors not linked <br />to any zone or input point <br />• OFFLINE PROGRAMMING: Create the entire program in your <br />office using FS-Tools, a Windows® -based software package, and <br />upload/download system programming locally. Offline program- <br />ming requires an ethernet connection. FS-Tools is available on <br />www.firelite.com. <br />User interface <br />LED INDICATORS <br />• Fire Alarm (red) <br />• CO Alarm (red) <br />• AC Power (green) <br />• Supervisory (yellow) <br />• Trouble (yellow) <br />• Ground fault (yellow) <br />• Battery fault (yellow) <br />• Disabled (yellow) <br />• Maintenance (yellow) <br />• Communication (yellow) <br />• Alarm Silenced (yellow) <br />• F1-F4 Programmable Function Keys (yellow) <br />KEYPAD <br />• 16 key alpha -numeric pad <br />• Acknowledge <br />• Alarm Silence <br />• Drill (Manual Evacuate) <br />• Four (4) programmable function keys <br />• Reset (lamp test) <br />PRODUCT LINE INFORMATION <br />ES-20OX: Addressable Fire Alarm Control Panel with one SLC loop. <br />Includes main circuit board with display, pre -installed communicator, <br />chassis with transformer, backbox with door, plastic bag containing <br />screws, cables, key, etc. (For ES-200XC, refer to DF-60958.) <br />FS-Tools: Programming software for Windows® -based PC com- <br />puter. Available for download at www.firelite.com. <br />CELL-CAB-FL/CELL-MOD: Optional GSM communicators. <br />IPOTS-COM: Dual technology (POTS and IP) communicator. <br />(replacement board) <br />DP-ES-R: Optional dress panel for the ES-200X. <br />TR-CE: Optional trim ring for semi -flush mounting. <br />BB-2F: Optional cabinet for one or two modules. <br />BB-6F: Optional cabinet for up to six modules mounted on CHS-6 <br />chassis. <br />BB-26: Battery backbox, holds up to two 25 AH batteries and CHG- <br />75. <br />BB-55F: Battery box, houses two 55 AH batteries <br />CHS-6: Chassis, mounts up to six multi -modules in a BB-6F cabinet. <br />CHG-75: Battery charger for lead -acid batteries with a rating of 25 to <br />75 AH. <br />CHG-120F: Remote battery charging system for lead -acid batteries <br />with a rating of 55 to 120 AH. Requires additional BB-55F for mount- <br />ing. <br />BAT Series: Batteries, see data sheet DF-52397. <br />PRN Series: UL listed compatible event printer. Uses tractor -fed <br />paper. <br />OPTIONAL MODULES <br />4XTMF Reverse Polarity Transmitter Module: Provides a super- <br />vised output for local energy municipal box transmitter, alarm and <br />trouble. Includes a disable switch and disable trouble LED. <br />PWRMOD24 Power Expander Module: Optional power module. <br />Increases alarm power output to 6 amps. <br />COMPATIBLE ANNUNCIATORS <br />ANN-80: Remote LCD annunciator mimics the information dis- <br />played on the FACP LCD display. Recommended wire type is un- <br />shielded. <br />ANN-100: Remote LCD annunciator mimics the information dis- <br />played on the FACP LCD display. Recommended wire type is un- <br />shielded. For use in FM applications only. <br />ANN-110: LED Driver Module provides connections to a user sup- <br />plied graphic annunciator. (See DF-52430.) <br />ANN-LED: Annunciator Module provides three LEDs for each zone: <br />Alarm, Trouble, and Supervisory. Ships with red enclosure. (See DF- <br />60241.) <br />ANN-RLED: Provides alarm (red) indicators for up to 30 input zones <br />or addressable points. (See DF-60241.) <br />ANN-RLY: Relay Module provides 10 programmable Form-C relays. <br />Can be mounted inside the cabinet. (See DF-52431.) <br />ANN-S/PG: Serial/Parallel Printer Gateway module provides a con- <br />nection for a serial or parallel printer. (See DF-52429.) <br />ADDRESSABLE DEVICES <br />All feature a polling LED and rotary switches for addressing. <br />SD365: Addressable low -profile photoelectric smoke detector. Lite- <br />Speed only. <br />SD365-IV: Addressable low -profile photoelectric smoke detector. <br />Ivory. LiteSpeed and CLIP mode. <br />SD365T: Addressable low -profile photoelectric smoke detector with <br />thermal sensor. LiteSpeed only. <br />SD365T-IV: Addressable low -profile photoelectric smoke detector <br />with thermal sensor. Ivory. LiteSpeed and CLIP mode. <br />SD365R: Remote test capable addressable photoelectric smoke <br />detector for use with DNR(W) duct detector housing. LiteSpeed only. <br />SD365R-IV: Remote test capable addressable photoelectric smoke <br />detector for use with DNR(W) duct detector housing. Ivory. Lite- <br />Speed and CLIP mode. <br />H365: Low -profile 135°F fixed thermal sensor. LiteSpeed only. <br />H365-IV: Low -profile 135°F fixed thermal sensor. Ivory. LiteSpeed <br />and CLIP mode. <br />H365R: Low -profile, intelligent, rate -of -rise thermal sensor. Lite- <br />Speed only. <br />H365R-IV: Low -profile, intelligent, rate -of -rise thermal sensor. Ivory. <br />LiteSpeed and CLIP mode. <br />H365HT: Low -profile intelligent 190°F/88°C fixed thermal sensor. <br />LiteSpeed only. <br />H365HT-IV: Low -profile intelligent 190°F/88°C fixed thermal sensor. <br />Ivory. LiteSpeed and CLIP mode. <br />Leqacy Devices <br />CP355: Addressable low -profile ionization smoke detector. <br />SD355: Addressable low -profile photoelectric smoke detector. <br />SD355T: Addressable low -profile photoelectric smoke detector with <br />thermal sensor. <br />SD355R: Remote test capable addressable photoelectric smoke <br />detector for use with DNR(W) duct detector housing. <br />SD355CO: Addressable, low -profile device that provides fire, heat, <br />and carbon monoxide (CO) detection. <br />H355: Fast -response, low -profile heat detector. <br />Page 2 of 4 — DF-60957:C • 7/16/2018 <br />