Technical Data TD450157EN
<br />EffectiveApril 2021
<br />Eluxa horns, horn strobes & strobes
<br />Table 5. Specifications
<br />Physical
<br />Material Red or white textured UV stabilized, colored impregnated engineered plastic. Exceeds 94V-0 UL flammability rating
<br />Weight Wall: 0.35 Ibs; Ceiling: 0.55 Ibs
<br />Lens Light Emitting Diode (LED) in a rugged Lexan lens
<br />Dimensions Wall: 4.79"H x 2.76" W x 1.18" D, Trimplate: 5.25" H x 4.58" W x 0.32" D; Ceiling: 6.27" Diameter x 1.69" 0
<br />Operating Temperature Indoor: 32°F to 122°F WC to 50°C) and maximum humidity of 93%
<br />Mounting & Wire Connections
<br />Mounting (indoor only) Mounting plate included with all models. ELHS and ELST are for wall -mount applications only. ELHN can be used for
<br />wall and ceiling -mount applications. Wall mounting: Single -gang, ELSBB backboxes or to 4" square with adapter kit.
<br />ELHN can be used for wall and ceiling -mount applications. ELHSC and ELSTC are for ceiling mount applications only.
<br />The ELHNC can also be used for wall -mount applications. Ceiling mounting: LSPKBB-C backboxes or to 4" square, 1
<br />1/2" or 2 1/8"and Octagonal, 1 %z" or 2 1/8"deep
<br />Wire Connections #12 through #18 AWG
<br />Power & General
<br />Operating voltage 12 VDC/VFWR: 8 - 17.5 VDC/VFWR; 24 VDCNFWR: 16 - 33 VDCNFWR (12 VDC ELHN/ELHNC models only)
<br />Strobe Output Rating UL 1971, UL 1638, ULC S526: Selectable 15, 30, 75, 110, 135, 185 candela output for wall models; Selectable 15, 30, 75,
<br />110, 150, 177 candela output for ceiling models
<br />Synchronization Models Strobes can be synchronized with Wheelock's DSM Sync Modules, PS Power Supplies or SAFEPATH products, using
<br />Wheelock patented sync protocol
<br />Architects and Engineers Specifications
<br />The LED notification appliances shall be Wheelock® ELHS audible
<br />visual strobe appliances, ELST visual strobe appliances and ELHN
<br />audible appliances for wall and ceiling -mount applications with a low -
<br />profile design or approved equals. Special lettering, including AGENT,
<br />ALERT, EVACUATE, and no lettering, shall be available. The ELHS
<br />and ELST strobes shall be listed for UL Standard 1971 (Emergency
<br />Devices for the Hearing -Impaired) for Indoor Fire Protection Service
<br />and UL 1638 (Visible Signaling Devices. The ELHS and ELHN
<br />Audibles shall be UL Listed under Standard 464 (Fire Protective
<br />Signaling). All models shall meet the requirements of FCC Part 15
<br />and ICES-003. All inputs shall be compatible with standard reverse
<br />polarity supervision of circuit wiring by a Fire Alarm Control Panel
<br />(FACP) with the ability to operate from 16 to 33 VDCNFWR.
<br />The ELHS audible strobe and ELST strobe appliances shall produce
<br />a flash rate of one (1) flash per second over the Regulated Voltage
<br />Range and shall incorporate a Light Emitting Diode (LED) as the
<br />light source with a rugged Lexan® lens. The appliances shall be of
<br />low current design. The LED strobe flash duration shall be 20 ms.
<br />Where Multi -Candela appliances are specified, the strobe intensity
<br />shall have 6 field selectable settings at 15, 30, 75, 110, 135 and 185
<br />candela for wall mount applications and 15, 30, 75, 110, 150 and 177
<br />for ceiling applications. The selector switch for selecting the candela
<br />shall be tamper resistant. Appliances with candela settings shall
<br />show the candela selection in a visible location at all times when
<br />installed.
<br />The audible shall have a choice of three (3) horn patterns (high & low
<br />WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
<br />3 YEAR WARRANTY
<br />Eaton
<br />1000 Eaton Boulevard
<br />Cleveland, OH 44122
<br />United States
<br />Eaton.com
<br />Life safety & mass notification solutions
<br />273 Branchport Ave.
<br />-��
<br />Long Branch, NJ 07740
<br />Powering Business Worldwide
<br />Eaton.com/Lifesafetynotification
<br />output): Continuous, T3, and T3/T4 for fire (T3) and CO (T4) signaling
<br />The ELHS audible strobe, ELST strobe, and ELHN audible shall
<br />include a hinged mounting plate. Mounting options shall include
<br />LED backboxes, single -gang backbox and to 4" square with adapter
<br />kit for wall -mount models and LED Ceiling backboxes, 4" square, 1
<br />1/2" or 2 1/8"deep and 4" Octagonal, 1 1/2" or 2 1/8"deep for ceiling
<br />models. Two wire appliance wiring shall be capable of directly
<br />connecting to the mounting base. Removal of an appliance shall
<br />result in a supervision fault condition by the Fire Alarm Control Panel
<br />(FRCP). All notification appliances shall be backwards compatible.
<br />The ELHS, ELHN and ELST wall models shall have a low profile
<br />measuring 4.79"H x 2.76"W x 1.18"D. The ELHSC, ELHNC and
<br />ELSTC ceiling models shall have a low profile measuring 6.27"
<br />Diameter with 1.69"D.
<br />When synchronization is required, the appliance shall be compatible
<br />with Wheelock®'s DSM Sync Modules, PS Power Supplies,
<br />SAFEPATH products or other manufacturer's panels with built-in
<br />Wheelock® Patented Sync Protocol. The strobes shall not drift out
<br />of synchronization at any time during operation. If the sync protocol
<br />fails to operate, the strobe shall revert to a non -synchronized flash -
<br />rate and still maintain (1) flash per second over its Regulated Voltage
<br />Range. The appliance shall also be designed so that the audible
<br />signal may be silenced while maintaining strobe activation when
<br />used with Wheelock® patented sync protocol.
<br />NFPA 72 2016, UL 1971, UL, 1638, UL 464 ULC-S525-16, ULC-S526-
<br />16, CSFM, FCC, RoHS, ICES
<br />© 2021 Eaton
<br />All Rights Reserved
<br />Printed in USA
<br />Publication No. TD450157EN
<br />April 2021
<br />Eaton is a registered trademark.
<br />All other trademarks are property
<br />of their respective owners.
<br />
|