Laserfiche WebLink
6of34 <br /> 1■■i11`TI <br /> Hilti PROFIS Engineering 3.0.75 <br /> www.hilti.com <br /> Company: Otak,Inc. Page: 6 <br /> Address: Specifier: <br /> Phone I Fax: I E-Mail: <br /> Design: BRT Shelter Windscreen Retrofit-Long Direction Date: 2/3/2022 <br /> Fastening point: <br /> 4 Shear load <br /> Load V.[Ib] Capacity$ V„[Ib] Utilization Pv=Vua/4) Va Status <br /> Steel Strength* 78 3,211 3 OK <br /> Steel failure(with lever arm)* N/A N/A N/A N/A <br /> Pryout Strength(Bond Strength controls)** 314 18,204 2 OK <br /> Concrete edge failure in direction** N/A N/A N/A N/A <br /> *highest loaded anchor **anchor group(relevant anchors) <br /> 4.1 Steel Strength <br /> Vsa =ESR value refer to ICC-ES ESR-3187 <br /> Vsteel >Vua ACI 318-14 Table 17.3.1.1 <br /> Variables <br /> Ase,v[in.2] fut.[Psi] <br /> 0.14 58,000 <br /> Calculations <br /> Vsa[Ib] <br /> 4,940 <br /> Results <br /> Vsa[Ib] steel Vsa[Ib] Vua[Ib] <br /> 4,940 0.650 3,211 78 <br /> Input data and results must be checked for conformity with the existing conditions and for plausibility! <br /> PROFIS Engineering(c)2003-2022 Hilti AG,FL-9494 Schaan Hilti is a registered Trademark of Hilti AG,Schaan <br /> 6 <br />