DEC'Pm <br /> ECIEVE <br /> 2013 <br /> Catch Design Studio CITY OF EVERETT <br /> 9031 21st Ave SW Permit Services <br /> Seattle,WA 98106 <br /> P#206-322-4323 <br /> MOCHINUT EVERETT <br /> November 20th, 2023 <br /> 8417 Evergreen Way, Everett, WA 98208 <br /> Plumbing PERMIt O. B2309-071 <br /> Response Letter#1 : <br /> 1. It appears that on sheet Al the occupancy load table is not accurately depicting <br /> the space shown on the floor plan. IBC 1004.5 <br /> a. The floor areas for the dining area-table and chairs (380 sq. ft.) appears <br /> to be less than the floor plan would indicate. <br /> • Revised the dining area calculations. See page Al. <br /> b. The floor area- long bench has an occupant load of 1 person per 18 <br /> inches,where does this occupant load come from? <br /> • Provided the long bench calculation. Total length of the bench is <br /> 150 inch and divide by 18,Then the occupancy load of long bench <br /> is 8. See page Al. <br /> c. The accessory use room name has no occupant load and is not depicted <br /> on the floor plan. This is the largest area in the table but would indicate <br /> that it has no occupancy. <br /> • Recalculated the accessory use on the occupancy load table. See <br /> page Al. <br /> if/9 <br />