PLUMBING SPECIFICATIONS <br />PLUMBING WORK, GENERAL <br />A. GENERAL REQUIREMENTS <br />1. CONTRACT REQUIREMENTS: COMPLY WITH BIDDING AND CONTRACT REQUIREMENTS AS OUTLINED BY THE <br />OWNER AND ARCHITECT. <br />2. WORK INCLUDED: THIS SECTION APPLIES TO ALL MECHANICAL WORK NORMALLY SPECIFIED UNDER <br />DIVISIONS 22 AND 23. PROVIDE ALL MATERIALS, LABOR, EQUIPMENT, TOOLS, FIELD DESIGN, SHOP <br />DRAWINGS, HOISTING, SCAFFOLDING, SUPERVISION AND OVERHEAD FOR THE CONSTRUCTION, INSTALLATION, <br />CONNECTION, TESTING AND OPERATION OF ALL MECHANICAL WORK AS SHOWN AND SPECIFIED. THE WORD <br />"PROVIDE" USED HEREINAFTER MEANS TO FURNISH AND INSTALL. ALL WORK AND MATERIALS REQUIRED <br />FOR COMPLETE FUNCTIONING SYSTEMS ARE NOT OUTLINED HERE, BUT SHALL BE PROVIDED AS PART OF <br />THIS WORK. <br />3. CODES: COMPLY WITH ALL APPLICABLE CODES AND ORDINANCES OF THE LOCAL AND STATE CODE <br />ENFORCING AGENCIES. OBTAIN PERMITS, APPROVALS, AND INSPECTIONS, AND PAY ALL COSTS AND FEES <br />FOR PERMITS, REVIEWS, AND INSPECTIONS. <br />4. ABBREVIATIONS: WHERE ABBREVIATIONS ARE USED IN THE SPECIFICATIONS AND ON THE DRAWINGS, THE <br />COMMON INDUSTRY DEFINITION SHALL APPLY UNLESS INDICATED OTHERWISE. THE TERM A/E SHALL <br />REFER TO THE PROJECT ARCHITECT AND MECHANICAL CONSULTING ENGINEER AS IF ONE ORGANIZATION. <br />5. SUBMITTALS: SUBMIT PRODUCT DATA AND SHOP DRAWINGS FOR ALL SIGNIFICANT MATERIALS, EQUIPMENT, <br />AND FIXTURES TO THE A/E FOR REVIEW. ALLOW REASONABLE TIME FOR REVIEW AND RETURN PRIOR TO <br />ORDERING. PDF (ELECTRONIC) SUBMITTALS AREA ACCEPTABLE, IF PAPER COPIES ARE SUBMITTED ASSUME <br />OWNER AND A/E WILL RETAIN A TOTAL OF THREE COPIES OF SUBMITTALS. <br />6. SAFETY MEASURES: PROVIDE A SAFE ENVIRONMENT TO PROTECT EMPLOYEES AND ALL OTHERS FROM <br />INJURY. COMPLY WITH LOCAL, STATE AND FEDERAL SAFETY AND HEALTH REGULATIONS FOR <br />CONSTRUCTION. <br />B. PERFORMANCE OF WORK <br />1. COORDINATION: COORDINATE MECHANICAL WORK WITH ALL OTHER TRADES AND TAKE ALL MEASUREMENTS <br />NECESSARY TO ENSURE PROPER INSTALLATION OF MECHANICAL WORK PRIOR TO START OF FABRICATION. <br />THIS CONTRACTOR SHALL CREATE BUILDING INFORMATION MODELS (BIM) AND/OR LARGE-SCALE DETAIL <br />DRAWINGS WHERE NECESSARY TO COORDINATE WORK IN TIGHT AREAS. THE CONTRACT DRAWINGS DO NOT <br />ATTEMPT TO SHOW EXACT LOCATIONS OF DUCTWORK, PIPING, FIXTURES, AND EQUIPMENT, OR ALL <br />TRANSITIONS AND OFFSETS THAT WILL BE NECESSARY FOR INSTALLATION. ALL NECESSARY TRANSITIONS <br />AND OFFSETS SHALL BE PROVIDED AS PART OF THIS WORK WITHOUT ADDED COMPENSATION. <br />2. CONTINUITY OF SERVICE: ANY SYSTEMS OR SERVICES WITHIN EXISTING OCCUPIED BUILDINGS SHALL BE <br />MAINTAINED WITH MINIMUM INTERRUPTION. COORDINATE ANY NEEDED INTERRUPTIONS WITH THE OWNER. <br />ANY OVERTIME WORK REQUIRED BY THIS PROJECT TO MAINTAIN EXISTING BUILDINGS IN CONTINUOUS <br />SERVICE, WITHOUT REDUCING THEIR EFFICIENCY, SHALL BE INCLUDED AS A PART OF THIS CONTRACT. <br />3. DEMOLITION: PROVIDE MECHANICAL SYSTEM DEMOLITION IN AREAS OF EXISTING BUILDINGS TO <br />ACCOMMODATE INSTALLATION OF NEW WORK. EXISTING PIPING, VALVES, AND DUCTWORK, WHERE INDICATED <br />ON THE DRAWINGS, MAY BE REUSED IN THEIR ORIGINAL LOCATION. DO NOT REUSE EXISTING PIPING, <br />VALVES, OR DUCTWORK ONCE THEY ARE REMOVED, UNLESS WRITTEN PERMISSION IS OBTAINED FROM <br />OWNER. REMOVE ALL UNUSED PIPING AND DUCTWORK LOCATED IN REMODEL AREAS OF EXISTING <br />BUILDINGS. <br />4. CUTTING AND PATCHING: PROVIDE ALL CUTTING OF BUILDING CONSTRUCTION, AS REQUIRED FOR THIS <br />WORK. KEEP CUTTING TO A MINIMUM, AND USE SAW CUTTING TO MAINTAIN NEAT, EVEN OPENINGS. <br />UNLESS PATCHING IS INCLUDED UNDER OTHER DIVISIONS OF THIS SPECIFICATION, PROVIDE PATCHING AT <br />ALL CUTTING LOCATIONS. All PATCHING SHALL CONFORM TO SPECIFICATIONS FOR THE NEW GENERAL <br />CONSTRUCTION WORK. FINISH TO MATCH EXISTING WORK. <br />C. PROJECT COMPLETION <br />1. RECORD DRAWINGS (AS-BUILTS): CORRECTIONS AND CHANGES MADE DURING THE PROGRESS OF THE <br />WORK SHALL BE NEATLY RECORDED AS ACTUALLY INSTALLED FOR AS -BUILT RECORDS. FURNISH ONE <br />CLEAN SET TO THE A/E UPON COMPLETION OF THE PROJECT. <br />2. OPERATION AND MAINTENANCE MANUALS: PROVIDE (3) FINISHED COPIES OF MECHANICAL OPERATION AND <br />MAINTENANCE MANUALS, FOR WORK UNDER THIS PROJECT. ARRANGE INFORMATION CONTAINED IN THE <br />MANUALS IN AN ORDERLY ARRANGEMENT (BY SPECIFICATION SECTION), SEPARATED BY TABS. PROVIDE <br />EQUIPMENT MANUFACTURER, MODEL NUMBER, SIZE, CAPACITY, PERFORMANCE DATA, SCHEDULE OF ROUTINE <br />MAINTENANCE, SUPPLIERS LISTS, UST OF REPLACEMENT PARTS, AND INCLUDE ANY SHOP DRAWINGS. <br />3. OWNER INSTRUCTION: CONTRACTOR SHALL INSTRUCT THE OWNER IN THE USE AND OPERATION OF ALL <br />SYSTEMS INSTALLED UNDER THIS CONTRACT. OBTAIN OWNER'S WRITTEN ACCEPTANCE THAT THEY HAVE <br />BEEN ADEQUATELY TRAINED. <br />4. GUARANTEE: GUARANTEE MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR AFTER THE DATE <br />OF SUBSTANTIAL COMPLETION. REFER TO ADDITIONAL REQUIREMENTS OUTLINED BY ARCHITECT AND <br />OWNER. BASIC MATERIALS AND METHODS (APPLIES TO ALL WORK) <br />1.1. WORK INCLUDED: THIS SECTION APPLIES TO ALL MECHANICAL WORK NORMALLY SPECIFIED UNDER <br />DIVISIONS 21, 22 AND 23, AND REPRESENTS REQUIREMENTS IN ADDITION TO THE REQUIREMENTS <br />STATED IN OTHER SECTIONS. THESE SPECIFICATIONS DO NOT COVER ALL ITEMS THAT WILL BE <br />REQUIRED FOR COMPLETE AND WORKING SYSTEMS. WHERE MATERIALS OR EQUIPMENT NEEDED FOR <br />THIS PROJECT ARE NOT COVERED IN THESE SPECIFICATIONS, PROVIDE THE MATERIALS AND EQUIPMENT <br />OF A QUALITY EQUAL TO OR BETTER THAN THAT GENERALLY UTILIZED BY THE INDUSTRY FOR SIMILAR <br />PROJECTS IN THE SAME GEOGRAPHIC AREA <br />D. SUPPORT AND HANGERS <br />1. SUPPORT OF MECHANICAL SYSTEMS: EACH PIECE OF EQUIPMENT SHALL BE SUPPORTED (FROM ABOVE <br />OR BELOW) IN NOT LESS THAN FOUR CORNERS FROM THE BUILDING STRUCTURE. PIPING AND DUCTWORK <br />SHALL BE SUPPORTED AT INTERVALS SPECIFIED, WITH EACH SYSTEM SUPPORTED INDEPENDENTLY FROM <br />THE BUILDING STRUCTURE. <br />2. SEISMIC BRACING: PROVIDE COMPLETE SEISMIC BRACING FOR ALL NEW PIPING, DUCTWORK, TERMINAL <br />UNITS AND EQUIPMENT AS REQUIRED BY THE CURRENT IBC WITH ALL LOCAL AMENDMENTS AND ASCE/SCI <br />7-10 (THE CURRENT CODE). BRACING MAY BE PER GUIDELINES ESTABLISHED BY RESTRAINT <br />MANUFACTURERS SUCH AS; MASON INDUSTRIES AND I.SAT PROVIDED THEY MEET THE CURRENT CODE. <br />ALL BRACING SHALL BE DESIGNED AND MANUFACTURED BY MASON, I.SAT, OR PRIOR -APPROVED <br />ALTERNATE. 3. CONNECTIONS TO THE BUILDING STRUCTURE: PROVIDE ALL NECESSARY CONNECTIONS <br />TO THE BUILDING STRUCTURE FOR SEISMIC RESTRAINTS AND SUPPORTS. WHERE CONCRETE STRUCTURE <br />IS PRESENT, REVIEW THE USE OF CONCRETE ANCHORS WITH THE ARCHITECT, OWNER, AND GENERAL <br />CONTRACTOR, AND VERIFY THAT THERE ARE NO POST -TENSIONED SLABS OR OTHER CONDITIONS THAT <br />NEED TO BE TAKEN INTO ACCOUNT IN SETTING OF ANCHORS. UTLZE MCCULLOUGH "KWIK-BOLT", <br />PHILLIPS SELF -DRILLING ANCHORS, GREGORY 'BULLDOG," OMARK "DRILL ANCHORS', OR OTHER APPROVED <br />ANCHOR TO ATTACH TO CONCRETE STRUCTURES. WHERE BUILDING STRUCTURE IS WOOD OR STEEL, <br />OBTAIN ARCHITECT APPROVAL OF HARDWARE AND METHODS TO BE UTILIZED FOR ATTACHMENT TO THE <br />STRUCTURE. <br />4. ADDITIONAL FRAMING: PROVIDE STEEL FRAMING MEMBERS TO TRANSFER LOAD FROM SUPPORT POINTS AT <br />HANGERS TO LOCATIONS WHERE CONNECTIONS CAN BE MADE TO THE BUILDING STRUCTURE. FRAMING <br />MEMBERS SHALL BE 12-GAUGE MINIMUM, 1-3/8" X 1-5/8" MINIMUM CROSS-SECTION SIZE; UNISTRUT, <br />POWERSTRUT, OR OTHER APPROVED. SELECT MEMBER SIZE AND TYPE, AS APPROPRIATE FOR LOAD PER <br />MANUFACTURER GUIDELINES. <br />5. PIPE HANGERS: CLEAS OR RING HANGERS WITH STEEL RODS. HANGERS FOR INSULATED PIPING SHALL <br />BE SIZED FOR OUTSIDE INSULATION AND 6" SHIELDS SHALL BE PROVIDED AT ALL HANGERS TO PROTECT <br />INSULATION. PIPE SUPPORT SPACING PER IMC. PROVIDE PLASTIC SEPARATION BETWEEN CLAMPS AND <br />COPPER PIPE. <br />6. HANGER RODS: HOT ROLLED STEEL ROD, ASTM A 36; SIZE TO 'CODE FOR PRESSURE PIPING', ANSI B <br />31.1, WITH SAFETY FACTOR OF 5. MINIMUM ROD SIZE; 1" PIPE AND SMALLER (240 POUNDS) = 1/4" <br />ROD, 1-1/4" TO 2" PIPE (TO 610 POUNDS) = 3/8" ROD, 2-1/2" TO 4" PIPE (TO 1,130 POUNDS) _ <br />1/2' ROD, 5' TO 8' PIPE (TO 1,810 POUNDS) = 5/8' ROD. <br />7. INSTALL HIGH DENSITY PRE -MOLDED PIPE INSULATION 180 DEGREES (HALF -SHELLS) ON BOTTOM HALF OF <br />PIPE AT SUPPORTS FOR PIPING GREATER THAN 1" IN DIAMETER, 6" LONG FOR PIPING 6" IN SIZE OR <br />SMALLER. FOR COLD PIPE SUPPORTS USE 3.0 PCF DENSITY POLYISOCYANURATE INSULATION. HOT PIPE <br />SUPPORTS SHALL BE HIGH DENSITY POLYISOCYANURATE FOR FLUIDS UP TO 300 F, OR CALCIUM SILICATE. <br />INSULATION AT SUPPORTS SHALL HAVE SAME THICKNESS AS ADJACENT INSULATION. <br />8. VIBRATION ISOLATION: VIBRATION ISOLATORS FOR HANGING EQUIPMENT SHALL BE EQUAL TO MASON <br />INDUSTRIES MODEL 30N, COMBINATION SPRING AND DOUBLE DEFLECTION NEOPRENE HANGER, DEFLECTION <br />AS RECOMMENDED BY MANUFACTURER. VIBRATION ISOLATORS FOR BASE MOUNTED EQUIPMENT SHALL BE <br />EQUAL TO MASON INDUSTRIES MODEL SLF, DEFLECTION AS RECOMMENDED BY MANUFACTURER. <br />C. EQUIPMENT AND PIPING IDENTIFICATION <br />1. NAMEPLATES: PROVIDE NAMEPLATE FOR EACH PIECE OF EQUIPMENT, INCLUDING EQUIPMENT NUMBER AND <br />ANY SPECIAL INSTRUCTION FOR ITS USE; LAMINATED BLACK AND WHITE PLASTIC WITH LETTERING CUT <br />THROUGH TO WHITE BACKGROUND. MINIMUM SIZE 3" X 1'. <br />2. PIPE IDENTIFICATION: ALL PIPING IN SERVICEABLE LOCATIONS (INCLUDING ABOVE LAY -IN CEILINGS) SHALL <br />BE IDENTIFIED WITH SEMI -RIGID PLASTIC OR ADHESIVE IDENTIFICATION MARKERS. MARKERS SHALL <br />CONFORM TO ANSI A13.1, 'SCHEME FOR THE IDENTIFICATION OF PIPING SYSTEMS'. LOCATE MARKERS <br />ADJACENT TO EACH VALVE, AT MINIMUM 30' CENTERS WITH AT LEAST ONE MARKER BETWEEN ANY TWO <br />PARTITIONS. PROVIDE DIRECTION OF FLOW ARROWS AT MARKERS. <br />D. MISCELLANEOUS MATERIALS AND ACCESSORIES <br />1. DIELECTRIC UNIONS: PROVIDE AT EACH PIPE CONNECTION BETWEEN DISSIMILAR METALS. 2 INCHES AND <br />SMALLER, 250 PSIG AT 180 DEG. F., ANSI B16.39. OVER 2" USE FLANGE FTTINGS, ANSI 816.42 (IRON) <br />OR ANSI B16.24 (BRONZE), WATTS 3000 SERIES, EPCO OR EQUIVALENT. <br />2. FIRE SEALING AT RATED WALLS AND FLOORS: PROVIDE UL LISTED FIRE RATED PUTTY AT ALL PIPE <br />PENETRATIONS OF RATED WALLS AND FLOORS. PUTTY SHALL BE INSTALLED STRICTLY PER MANUFACTURER <br />INSTRUCTIONS WITH SLEEVES WHERE REQUIRED. OVERALL INSTALLATION SHALL MEET CODE <br />REQUIREMENTS. PIPE INSULATION SHALL NOT BE CONTINUOUS THROUGH FIRE RATED WALLS OR FLOORS. <br />3. MOTORS: UNLESS OTHERWISE SPECIFIED, ALL ELECTRIC MOTORS FURNISHED SHALL CONFORM WITH THE <br />REQUIREMENTS OF NEMA MG1 "MOTORS AND GENERATORS." PROVIDE MINIMUM MOTOR EFFICIENCIES AS <br />REQUIRED BY THE ENERGY CODE. <br />4. INTERCONNECTING WIRING: PROVIDE ANY NECESSARY INTERCONNECTING WIRING BETWEEN INDIVIDUAL <br />COMPONENTS AND ACCESSORIES FURNISHED WITH MECHANICAL EQUIPMENT PACKAGES (UNLESS THAT <br />WIRING IS SPECIFICALLY CALLED FOR ON THE ELECTRICAL DRAWINGS). WIRING AND WIRING ACCESSORIES <br />SHALL BE IN ACCORDANCE WITH DIVISION 26 SPECIFICATIONS (AND/OR THE SPECIFICATIONS ON THE <br />ELECTRICAL DRAWINGS) AND LOCAL ELECTRICAL CODE. WIRING SHALL BE IN CONDUIT OR RACEWAY. <br />WIRING SHALL BE PROVIDED AT THE EXPENSES OF THE SUBCONTRACTOR FURNISHING THE EQUIPMENT <br />PACKAGE. <br />E. EXECUTION OF WORK <br />1. INSTALLATION, GENERAL: FOLLOW MANUFACTURER'S INSTRUCTIONS AND UTILIZE GOOD INDUSTRY PRACTICE <br />WHEN INSTALLING ALL WORK. USE ONLY SKILLED TRADESPEOPLE WITH QUALIFIED SUPERVISION. ALL <br />WORK SHALL BE LEFT NEAT AND CLEAN. <br />2. CONCEALMENT: PIPING AND DUCTWORK SHALL BE CONCEALED WITHIN BUILDING CONSTRUCTION, UNLESS <br />SPECIFICALLY INDICATED OTHERWISE WHERE PIPING IS INDICATED TO BE EXPOSED TO VIEW IN FINISHED <br />SPACES OR CABINETS, PROVIDE CHROME ESCUTCHEONS WHERE THE PIPING PENETRATES THE WALL, FLOOR <br />OR CEILING CONSTRUCTION <br />3. WATER SEALING AT FLOORS: PROVIDE WATER TIGHT SEALING AT EACH FLOOR PENETRATION INCLUDING <br />PIPING WITHIN WALL CAVITIES. PROVIDE WATER SLEEVES SEALED TO THE FLOOR CONSTRUCTION AND <br />PROJECTING NOT LESS THAN 1.5" ABOVE FLOOR WHERE INSULATED PIPING PENETRATES THE FLOOR. THE <br />INTENT IS TO MINIMIZE PASSAGE OF WATER DURING A SIGNIFICANT WATER LEAKAGE EVENT. SEALING IS <br />REQUIRED FOR CONCRETE FLOORS, BUT NOT REQUIRED FOR OTHER FLOOR SYSTEMS WHERE THE <br />CONSTRUCTION ITSELF, AT THE PIPE PENETRATION, ALLOWS SIGNIFICANT WATER SEEPAGE (PLANKED WOOD <br />FLOOR FOR EXAMPLE). <br />4. COORDINATION WITH OTHER TRADES: COMPLETE DRAWINGS AND SPECIFICATIONS OF All TRADES WILL <br />BE FURNISHED OR WILL BE AVAILABLE FOR INSPECTION IN THE CONSTRUCTION OFFICE AT THE <br />JOBSITE. CAREFULLY CHECK THESE DRAWINGS AND SPECIFICATIONS BEFORE INSTALLING ANY WORK. <br />IN ALL CASES, CONSIDER THE WORK OF ALL OTHER TRADES AND COORDINATE WORK WITH THAT OF <br />THE SHEET METAL, PIPING, PLUMBING, ELECTRICAL, AND SITE -WORK SUBCONTRACTORS, SO THAT THE <br />BEST ARRANGEMENT OF ALL EQUIPMENT, PIPING, CONDUIT, DUCTS, AND OTHER RELATED ITEMS CAN BE <br />OBTAINED. <br />PLUMBING INSULATION <br />A GENERAL <br />1. MANUFACTURERS: MANVILLE, OWENS-CORNING, CERTAINTEED, OR KNAUF. INSTALL IN ACCORDANCE <br />WITH MANUFACTURER'S INSTRUCTIONS. <br />2. INSULATION THICKNESS: REFER TO INSULATION REQUIREMENTS ON THE DRAWINGS FOR SYSTEMS TO <br />BE INSULATED AND THICKNESS OF INSULATION. <br />B. INSULATION MATERIALS <br />1. INDOOR PIPE INSULATION: FIBERGLASS PIPE INSULATION WITH ALL -SERVICE (VAPOR BARRIER) JACKET <br />SHALL BE PROVIDED FOR ALL PIPING SYSTEMS, EXCEPT REFRIGERANT PIPING. FITTINGS SHALL BE <br />MITERED SECTIONS OF INSULATION WITH THE SAME THICKNESS AS ADJACENT PIPE INSULATION WITH <br />FACTORY-PREMOLDED, ONE-PIECE, UL LISTED (25/50) PVC FITTING COVERS. INSTALLATION MUST <br />REFLECT CAREFUL WORKMANSHIP, AND BE NEAT IN APPEARANCE. VAPOR BARRIER SHALL BE SEALED <br />AT ALL JOINTS ON COLD PIPING. <br />2. OUTDOOR PIPE INSULATION: INSULATION AND FITTINGS SAME AS SPECIFIED FOR INDOOR PIPE <br />INSULATION. PROVIDE METAL JACKErs OF 0.016" ALUMINUM WITH INTEGRAL VAPOR RETARDER, <br />SELF-SEALING, WATERTIGHT METAL BANDS FOR BUR JOINTS. SEAL JOINTS WITH ALUMINUM PIGMENTED <br />VAPOR RETARDER MASTIC, FOSTER 60-65, OR APPROVED EQUIVALENT. <br />3. ROOF DRAIN BODY INSULATION: FLEXIBLE FIBERGLASS BLANKET CONFORMING TO ASTM C 553, TYPE I, <br />AND NOMINAL DENSITY NOT LESS THAN 1 LB. PER CUBIC FOOT, COVERED WITH 8-OUNCE CANVAS <br />AND VAPOR RETARDER CEMENT. <br />FIRE PROTECTION <br />A GENERAL <br />1. WORK INCLUDED: DESIGN AND PROVIDE ALTERATIONS TO, AND EXTENSION OF, THE EXISTING FIRE <br />PROTECTION SYSTEM, TO ACCOMMODATE THE NEW SPACE LAYOUT AND INSTALL ALL WORK IN <br />ACCORDANCE NFPA 13, ALL OTHER APPLICABLE CODES, STANDARDS, AND REGULATIONS, AND AS <br />REQUIRED BY THE AUTHORITY HAVING JURISDICTION. WORK SHALL INCLUDE ALTERATIONS TO THE <br />EXISTING FIRE SPRINKLER PIPING AS NEEDED TO MAKE REASONABLE CLEARANCE FOR NEW WORK BY <br />OTHER TRADES. <br />2. SYSTEM TYPE: PROVIDE WET -PIPE SPRINKLER PROTECTION FOR ALL HEATED AREAS. WHERE <br />SPRINKLER COVERAGE OF UNHEATED AREAS IN AND AROUND THE BUILDING IS REQUIRED, PROVIDE <br />EITHER A DRY -PIPE SYSTEM OR DRY -SPRINKLER COVERAGE FROM THE NET SYSTEM. IF A DRY -PIPE <br />FIRE SPRINKLER SYSTEM IS PROVIDED, REVIEW THE ELECTRICAL DRAWINGS TO DETERMINE EXTENT OF <br />ADDITIONAL POWER AND ALARM SERVICES REQUIRED, AND PAY ELECTRICAL COSTS ASSOCIATED WITH <br />THESE SERVICES. <br />3. AUTHORITIES: COMPLY WITH ALL REQUIREMENTS OF THE AUTHORITIES, WHICH SHALL INCLUDE THE <br />STATE FIRE MARSHAL, LOCAL BUILDING AND FIRE DEPARTMENTS, AND OWNER'S INSURANCE <br />ORGANIZATION. <br />4. LICENSE THE FIRE SPRINKLER CONTRACTOR SHALL BE STATE -LICENSED AND REGULARLY ENGAGED IN <br />THE DESIGN AND INSTALLATION OF AUTOMATIC SPRINKLER SYSTEMS AND, WHERE APPLICABLE, <br />UNDERGROUND FIRE MAINS. SHOP DRAWINGS SHALL BE STAMPED BY A STATE-UCENSED FIRE <br />PROTECTION ENGINEER OR DESIGNER WITH A NICET LEVEL III CERTIFICATION. <br />5. DESIGN DRAWINGS: COORDINATE LOCATIONS OF SPRINKLER HEADS, VALVES, AND OTHER EXPOSED <br />ITEMS WITH ARCHITECT, THEN PREPARE COMPLETE DESIGN DRAWINGS AND SUBMIT TO THE AUTHORITIES <br />FOR APPROVAL ALSO SUBMIT AUTHORITY -APPROVED DRAWINGS TO THE A/E FOR REVIEW PRIOR TO <br />START OF WORK. <br />6. COORDINATION WITH OTHER TRADES: DURING PREPARATION OF SHOP DRAWINGS, CALL TO THE <br />ATTENTION OF THE GENERAL CONTRACTOR ANY POINTS OF CONFLICT BETWEEN NEW OR EXISTING FIRE <br />SPRINKLER WORK AND THAT OF THE OTHER TRADES, SO THAT THE CONFLICT MAY BE PROPERLY <br />RESOLVED. WORK WHICH UNREASONABLY INTERFERES WITH THE WORK OF OTHER TRADES SHALL BE <br />REMOVED AND RE -INSTALLED AT THIS SUBCONTRACTOR'S EXPENSE. IT SHALL BE UNDERSTOOD THAT <br />NO EXTRAS TO THE CONTRACT WILL BE PERMITTED TO ACCOMPLISH THE ABOVE RESULTS. <br />B. FIRE SPRINKLER SYSTEM MATERIALS <br />1. APPROVED MANUFACTURERS: VIKING CORP., STAR SPRINKLER CORP., RELIABLE AUTOMATIC SPRINKLER <br />CO., GRINNELL FIRE PROTECTION SYSTEMS CO., 'AUTOMATIC" SPRINKLER CORP. OF AMERICA, CENTRAL <br />SPRINKLER CORP., GLOBE FIRE EQUIPMENT CO., MICHIGAN. <br />2. GENERAL COMPONENTS: ALL REQUIRED COMPONENTS, INCLUDING VALVES, FLOW SWITCHES, TAMPER <br />SWITCHES, HANGERS, FITTINGS, AND OTHER ACCESSORIES, SHALL MEET NFPA STANDARDS, AND SHALL <br />HAVE UL AND FM LISTING WHERE SUCH LISTING IS AVAILABLE. <br />3. PIPE ASTM-135 OR ASTM A-53, STAMPED ON PIPE. SCHEDULE 40 BLACK STEEL, WITH THREADED <br />OR GROOVED FITTINGS; SCHEDULE 10 ACCEPTABLE FOR ROLL -GROOVED ONLY. THREADED FITTINGS <br />THROUGH 2", ANSI B16.4 BLACK. OVER 2' GROOVE FITTINGS, ANSI / ASTM A47, MCTAUUC STYLE 75, <br />750, 77, OR FM APPROVED EQUAL FITTINGS. <br />4. SPRINKLER HEADS: WHERE INSTALLED IN SUSPENDED CEILINGS, SPRINKLER HEADS SHALL BE CHROME <br />PLATED RECESSED PENDANT TYPE WITH CHROME ESCUTCHEONS. TEMPERATURE RATINGS AND <br />RESPONSE TIME AS REQUIRED BY AUTHORITIES. HEADS SHALL MATCH EXISTING HEADS IN THE <br />BUILDING, TO THE EXTENT POSSIBLE. PROVIDE SPARE HEADS, NOT LESS THAN TWO OF EACH TYPE, <br />OR MORE AS REQUIRED BY NFPA. <br />DOMESTIC WATER AND DRAINAGE <br />A PIPING SYSTEMS <br />1. DOMESTIC WATER PIPING: TYPE L COPPER WATER TUBE, HARD DRAWN, ASTM B 88. WROUGHT <br />COPPER SOLDER FITTINGS AND SCREWED ADAPTERS, ANSI B16.22.J. SOLDER; 95 PERCENT TIN, 5 <br />PERCENT ANTIMONY SOLDER, ASTM B 32, 95TA <br />2. DOMESTIC PIPING INSULATION: PREFORMED GLASS FIBER WITH VAPOR BARRIER JACKET AND A FLAME <br />SPREAD INDEX OF 25 AND A MAXIMUM SMOKE -DEVELOPED INDEX OF 50, THICKNESS PER THE <br />CURRENT ENERGY CODE. EXTERIOR EXPOSED PIPING SHALL BE COVERED WITH .015 IN THICK <br />ALUMINUM JACKET WITH TWO-INCH LAPS AND BANDED WITH 3/8" STAINLESS STEEL BANDS AT 9" ON <br />CENTER. SEAL LAPS WITH SILICONE SEALANT. <br />3. CONDENSATE DRAIN PIPING AND FITTINGS: SEAMLESS TYPE L COPPER WITH 95-5 SOLDER. INSULATE <br />CONDENSATE DRAIN PIPING WITH 1/2" INCH THICK ARMSTRONG 'ARMAFLEX' OR EQUAL <br />4. SMALL VALVES (2" AND SMALLER): BALL VALVES FED. SPEC. WW-V-35, 250-PSIG BRONZE OR <br />BRASS BODY, BALL AND STEM, SOLDER ENDS OR SCREWED, TEFLON SEAT AND SEAL. CHECK VALVES <br />AND OTHER VALVES SHALL BE OF EQUAL QUALITY AND SAME MANUFACTURER OF BALL VALVES AND <br />SHALL HAVE NOT LESS THAN 125-PSIG RATING. GATE VALVES (ALLOWED ONLY WHERE INDICATED) MSS <br />SP80, 125-PSIG BRONZE, SCREWED OR SOLDER END, UNION BONNET, RISING STEM, SOLID BRONZE <br />DISC. PROVIDE SHUT-OFF VALVES AT ALL EQUIPMENT CONNECTIONS. <br />5. ROOF DRAIN, WASTE AND VENT PIPING: ASTM A74 STANDARD WEIGHT HUBLESS CAST IRON PIPE, CISPI <br />301. COUPLINGS; NEOPRENE SLEEVE GASKET, STAINLESS STEEL SHIELD AND BANDS. FITTINGS SHALL <br />BE STANDARD WEIGHT CAST IRON SOIL PIPE FITTINGS, ANSI A112.5.1 AND ASTM A74. HUBLESS CAST <br />IRON FITTINGS, CISPI 301. <br />B. PLUMBING ACCESSORIES AND EQUIPMENT: <br />1. REDUCED PRESSURE BACKFLOW PREVENTER ASSEMBLIES: REDUCED PRESSURE TYPE BACK -FLOW <br />PREVENTER; 3/4" TO 2" SIZE; BRONZE CONSTRUCTION WITH ISOLATING BALL VALVES, STRAINER AND <br />AIR GAP DRAIN FETING. HERSEY MODEL FRPII, WATTS 909 SERIES OR APPROVED EQUIVALENT. <br />PROVIDE CERTIFICATION OF BACKFLOW PREVENTER BY STATE CERTIFIED SPECIALIST, INCLUDE WITH <br />MAINTENANCE MANUALS. <br />2. PRESSURE REDUCING VALVES: 2 INCH AND SMALLER, COMPLETE WITH INTEGRAL STRAINER, PRESSURE <br />GAUGE, AND INTEGRAL THERMAL EXPANSION BY-PASS, BRONZE CONSTRUCTION WITH STAINLESS STEEL <br />STRAINER. WATTS NO. U5B OR EQUIVALENT. <br />3. STRAINERS: 2-1/2 INCHES AND SMALLER, BRONZE, Y-PATTERN, THREADED ENDS, 20-MESH <br />STAINLESS STEEL SCREEN; 250 PSI AT 210 F. <br />4. FLOOR DRAINS: SMITH 2O05, DOUBLE DRAINAGE, ADJUSTABLE STRAINER HEAD FLOOR DRAIN, DUCO <br />COATED CAST IRON BODY, FLASHING COLLAR, NICKEL BRONZE STRAINER WITH 1/4' HOLES. PROVIDE <br />SQUARE STRAINER IN AREAS WITH TILE FLOORS AND ROUND STRAINERS IN OTHER LOCATIONS. WHERE <br />FUNNEL DRAINS ARE INDICATED, ADD SMITH 3590 ROUGH BRONZE FUNNEL REMOVE STRAINER WITHIN <br />FUNNEL, AS REQUIRED, TO ELIMINATE SPLASHING. <br />5. EQUIPMENT, GENERAL: PROVIDE ALL EQUIPMENT CONSISTENT WITH THE CAPACITY, MANUFACTURER, <br />MODEL NUMBER, AND ACCESSORIES AS SPECIFIED OR INDICATED ON THE DRAWING SCHEDULES AND <br />NOTES. EQUIPMENT SUPPLIERS SHALL VERIFY THAT MODEL NUMBERS ARE CONSISTENT WITH CAPACITY, <br />FEATURES, AND ACCESSORIES CALLED FOR AND IDENTIFY ANY CONFLICTS PRIOR TO SUBMITTING <br />QUOTATIONS TO CONTRACTORS. ALL EQUIPMENT WITH ELECTRICAL COMPONENTS SHALL HAVE UL <br />LISTING AS REQUIRED BY THE ELECTRICAL INSPECTOR. ALTERNATE MANUFACTURERS WILL BE <br />CONSIDERED; HOWEVER, A/E FINAL APPROVAL OF EQUALITY OF ALTERNATE MANUFACTURER MODELS IS <br />REQUIRED. ACCEPTABLE ALTERNATE MANUFACTURERS INCLUDE BELL AND GOSSErf, AMTROL, TACO, AO <br />SMITH, STATE, OR AS INDICATED OR PRIOR -APPROVED OTHERWISE. ALTERNATE MANUFACTURERS WITH <br />PRIOR APPROVAL ARE SILL RESPONSIBLE FOR MEETING OR EXCEEDING THE QUALITY AND FEATURES <br />OF THE SPECIFIED ITEMS. <br />PLUMBING FIXTURES <br />A. PLUMBING FIXTURE ACCESSORIES <br />1. FIXTURE CARRIERS: PROVIDE CAST IRON OR STEEL CARRIERS FOR ALL WALL -HUNG FIXTURES WITH <br />CONCEALED FIXTURE CARRIERS CONSTRUCTED FOR THE PARTICULAR FIXTURE, HEAVY DUTY <br />CONSTRUCTION WITH SECURE ANCHORING TO CONCRETE FLOOR. SMITH, WADE, ZURN, OR APPROVED. <br />BACK LUG OF WATER CLOSET CARRIERS SHALL BE ANCHORED TO FLOOR. <br />2. DRAINS AND TRAPS: PROVIDE GRID STRAINER DRAINS FOR ALL LAVATORIES UNLESS INDICATED <br />OTHERWISE. PROVIDE BASKET STRAINER DRAINS FOR ALL SINKS UNLESS INDICATED OTHERWISE. <br />PROVIDE TRAPS AND TAILPIECES AT ALL FIXTURES UNLESS TRAP IS INTEGRAL WITH FIXTURE. <br />3. STOPS: PROVIDE CHROME STOPS AT EACH WATER CONNECTION TO EACH FIXTURE, EXCEPT WHERE A <br />FAUCET OR CONTROL HAS INTEGRAL STOPS. STOPS SHALL BE A LOOSE KEY PATTERN WITH SHIELD; <br />CHICAGO, BRIDGEPORT BRASS, BRASS CRAFT (SPEEDWAY), TELEDYNE, OR EQUIVALENT. <br />4. CAULKING: PROVIDE SILICONE SEALER BETWEEN THE TOP AND THE SIDES OF PLUMBING FIXTURES <br />AND ADJACENT WALL SURFACES; GENERAL ELECTRIC NO. SCS/202. APPLY PER MANUFACTURER'S <br />RECOMMENDATIONS TO FORM A SMOOTH, UNOBTRUSIVE JOINT. <br />5. EXPOSED PLUMBING: IN GENERAL, ALL PIPING SHALL BE CONCEALED UNLESS INDICATED OTHERWISE. <br />ANY PIPING THAT MUST BE EXPOSED WITHIN CABINETS OR OTHERWISE, DUE TO CONNECTIONS <br />REQUIRED FOR FIXTURES AND EQUIPMENT, SHALL BE PAINTED SILVER. ALL EXPOSED ITEMS, <br />INCLUDING STOPS, TRAPS, ETC., SHALL BE CHROME PLATED. <br />B. PLUMBING FIXTURES <br />1. GENERAL: PROVIDE THE PLUMBING FIXTURES AS ON THE DRAWINGS . PROVIDE THE <br />MANUFACTURER AND MODEL NUMBERS AS INDICATED; HOWEVER, CONTRACTOR SHALL VERIFY MODEL <br />NUMBERS OF FIXTURES, FLUSH VALVES, FAUCETS, ETC., FT TOGETHER PROPERLY. ALTERNATE <br />MANUFACTURERS WILL BE CONSIDERED; HOWEVER, A/E FINAL APPROVAL OF EQUALITY OF ALTERNATE <br />MANUFACTURER MODELS IS REQUIRED. ACCEPTABLE ALTERNATE FIXTURE MANUFACTURERS INCLUDE <br />KOHLER, AMERICAN STANDARD, EWER, ELKAY, JUST, OR AS INDICATED OR PRIOR APPROVED <br />OTHERWISE. ALTERNATE MANUFACTURERS WITH PRIOR APPROVAL ARE STILL RESPONSIBLE FOR <br />MEETING OR EXCEEDING THE QUALITY AND FEATURES OF THE SPECIFIED ITEMS. <br />0 <br />2 <br />O � <br />Z <br />y <br />t V <br />U N <br />N <br />O i <br />m a <br />Z. <br />-cw <br />06 <br />Z <br />uLL1�a <br />;.; <br />g=l <br />� <br />2727 Oakes Ave. <br />Suite 100 <br />Everett, WA 98201 <br />REVISIONS <br />A DOH REVISION 12/11/24 <br />D <br />WA <br />FT <br />59941 <br />ICNA7, �' <br />1211W94 <br />z_j <br />0 Q <br />U Ld <br />,Ld = <br />V / <br />U Q <br />LL_ 0 <br />U <br />nQ Q <br />LLJ W <br />U m <br />LLJ <br />0 <br />00 <br />n� J <br />I__L LL <br />242095 <br />aeAWN CEI <br />ON <br />PERMIT SET <br />08/22/24 <br />PLUMBING <br />SPECIFICATIONS <br />J <br />P0.2 <br />City of Everett Permit Services <br />EVERETT Reviewed for Permit 01/14/2025 <br />