I N I Summary Of Outflowing Devices Job Number:230109 <br /> Report Description:Residential <br /> Actual Flow Minimum Flow K-Factor Pressure <br /> Device pm pm K psi <br /> Sprinkler 590 13.77 12.80 4.9 7.899 <br /> b Sprinkler 593 12.96 12.80 4.9 7.000 <br /> b Most Demanding Sprinkler Data <br /> ©M.E.P.CAD AutoSPRINK 2023 v18.1.33.0 3/28/2024 7:01:15PM Page 4 <br />