FASTEN TO STRUCTURE PER CISCA 3.4 EXCEPT AS INDICATED IN DETAILS C AND F,COMPONENTS OF FASTEN TO STRUCTURE PER CISCA 3.4 EXCEPT AS INDICATED IN DETAILS C AND F,COMPONENTS OF <br /> (FIGURES 2,3,4,AND 5)AS MODIFIED BY MECHANICAL,ELECTRICAL,PLUMBING AND FIRE PROTECTION (FIGURES 2,3,4,AND 5)AS MODIFIED BY MECHANICAL,ELECTRICAL,PLUMBING AND FIRE PROTECTION SHALL <br /> ASCE 7-05.SECTION 13.5.6.2.2 SHALL BE INDEPENDENTLY SUPPORTED AND BRACED FROM ASCE 7-05.SECTION 13.5.6.2.2 BE INDEPENDENTLY SUPPORTED AND BRACED FROM STRUCTURE W <br /> ---S�Ij STRUCTURE <br /> I <br /> HANGAR WIRE AT EACH PERIMETER HANGAR WIRE AT EACH PERIMETER MAIN 2M STARBUCKS COFFEE COMPANY <br /> MAIN TEE AND PERIMETER CROSS TEE WHERE HANGAR WIRES / TEE AND PERIMETER CROSS TEE WHERE HANGAR WIRES <br /> 12 GAGE MINIMUM HANGAR ARE MORE THAN 1:6OUT. / 12 GAGE MINIMUM HANGAR ARE MORE THAN 1:6OUT• STARBUCKS° <br /> WIRES AT 4'-0"OC EACH OF-PLUMB,PROVIDE 314"CLEAR AT ONE END IN EACH DIRECTION. WIRES AT 4'-0"OC EACH OF-PLUMB,PROVIDE O <br /> 3/4"CLEAR AT ONE END IN EACH DIRECTION. DIRECTION-NO MORE THAN 1:6 COUNTER-SLOPING WIRES O O DO NOT FASTEN THIS END TO THE CLOSURE DIRECTION-NO MORE THAN COUNTER-SLOPING O O 2401 UTAH AVENUE SOUTH <br /> DO NOT FASTEN THIS END TO THE CLOSURE OUT-OF-PLUMB,TYPICAL ANGLE.AT OTHER END IN EACH DIRECTION, 1:6OUT-OF-PLUMB,TYPICAL WIRES SEATTLE,WASHINGTON 98134 <br /> >00 ANGLE.AT OTHER END IN EACH DIRECTION, FASTEN TEES TO CLOSURE ANGLE. I� (206)318-1575 <br /> FASTEN TEES TO CLOSURE ANGLE. STABILIZER BAR TO MAINTAIN PERIMETER WIRE LOOPED AND WRAPPED r <br /> WIRE LOOPED AND WRAPPED MAINTAIN HANGAR WIRE METAL-FRAMED TRAPEZE TEE SPACING AROUND ITSELF 3 TIMES THESE DRAWINGS AND THE PROJECT MANUAL <br /> GRID SUSPENSION SYSTEM AROUND ITSELF 3 TIMES MINIMUM SPACING AND CAPACITY AS NECESSARY TO AVOID MINIMUM AT EACH END OF MAINTAIN HANGAR WIRE METAL-FRAMED TRAPEZE ,+ <br /> AT EACH END OF HANGAR WIRE BELOW OBSTRUCTION OBSTRUCTIONS MAIN TEE OR CROSS TEE(SUSPENSION HANGAR WIRE WITHIN A 3" SPACING AND CAPACITY AS NECESSARY TO AVOID U ARE CONFIDENTIAL AND SHALL REMAIN THE <br /> WITHIN A3"MAXIMUM LENGTH SYSTEM)HEAW DUTY MAXIMUM LENGTH BELOW OBSTRUCTION OBSTRUCTIONS SOLE PROPERTY OF STARBUCKS <br /> CORPORATION,WHICH IS THE OWNER OF THE <br /> COPYRIGHT IN THIS WORK.THEY SHALL NOT <br /> a/ BE REPRODUCED(IN WHOLE OR IN PART), <br /> . ..: -...:.,.,. - .,- •.:,*•. ,, SHARED WITH THIRD PARTIES OR USED IN ANY <br /> 5I8"GYPSUM BOARD ACOUSTICAL CEILING PANELS MANNER ON OTHER PROJECTS OR <br /> EXTENSIONS TO THIS PROJECT WITHOUT THE <br /> 2X 2 CLOSURE ANGLE,MINIMUM.SEE ,A 8"N1AX 2X2SHEET METAL ANGLE I.,MAX NOTE AT TOP N PCOR ORATIONRIOR WRITTEN CTTHESE DRAWINGS AND <br /> COMPLY WITH ADDITIONAL PROVISIONS OF ASTM C635, <br /> ASTM C636,CISCA 3-4.AND ASCE 7-05,SECTION 13.5.6. Z SP DESIGN F N INTENT OR ACIFICATIONS AREENDED PROTOTYP CA PRESS <br /> STARBUCKS STORE(WHICH IS SUBJECT TO <br /> O <br /> � CHANGE AT ANYTIME)AND DO NOT REFLECT <br /> ,++ ACTUAL SITE CONDITIONS.NEITHER PARTY <br /> ^ PERIMETER SUPPORT r/D \ GENERAL SUPPORT PERIMETER SUPPORT p GENERAL SUPPORT V THALL HAVE HE OTHER(EXCEPT OBLIGATION ATED ABOVE)UNTIL LIABILITY AO <br /> Y GYPSUM BOARD CONSTRUCTION SHALL COMPLY WITH ADDITIONAL PROVISIONS OF SBC SECTION 2508. <br /> WRITTEN AGREEMENT IS FULLY EXECUTED BY <br /> SUSPENSION SYSTEM SHALL CONFORM WITH ASCE 7,SECTION 13.5.8.2.1,ASTM C635,ASTM C838, <br /> ASTM C754,AND CISCA 34 BOTH PARTIES. <br /> STARBUCKS TEMPLATE VERSION:12021.10.22 <br /> LIGHT FIXTURES WEIGHING LESS O ARCHITECT OF RECORD <br /> THAN 10 POUNDS SHALL BE LIGHT FIXTURES WEIGHING LESS THAN 10 U. <br /> CONNECTED TO STRUCTURE ABOVE POUNDS SHALL BE CONNECTED TO STRUCTURE <br /> BY(1)12 GAGE TAUT OR SLACK WIRE ABOVE BY(1)12 GAGE TAUT OR SLACK WIRE GRAPHITE <br /> W GRAPHITE DESIGN GROUP,LLC,ARCHITECTS <br /> LIGHT FUTURES AND AIR TERMINALS Q 18077TH AVENUE,SUITE 700 <br /> SERVICES WEIGHING MORE THAN 56 SEATTLE,WA 98101 <br /> LIGHT FXTURES WEIGHING MORE THAN 10 POUNDS AND ALL PENDANT LIGHT (206)224.3335 <br /> LIGHT FUTURES WEIGHING MORE THAN 10 <br /> POUNDS AND LESS THAN 56 POUNDS,AND POUNDS AND LESS THAN 56 POUNDS,AND AIR FIXTURES SHALL BE SUPPORTED Z <br /> AIR TERMINALS I SERVICES WEIGHING DIRECTLY FROM STRUCTURE ABOVE <br /> MORE THAN 20 POUNDS AND LESS THAN 56 TERMINALS I SERVICES WEIGHING MORE THAN 20 USING APPROVED HANGARS <br /> POUNDS AND LESS THAN 56 POUNDS SHALL BE <br /> POUNDS SHALL BE CONNECTED TO CONNECTED TO STRUCTURE ABOVE BY 2 L LU <br /> STRUCTURE ABOVEBY HED GAGETAUT GAGE TAUT OR SLACK WIRES ATTACHED AT2 1�OR SLACK WIRES ATTACHED AT DIAGONAL DIAGONAL CORNERS /�933MI <br /> CORNERS. LIGHT FIXTURES AND AIR TERMINALS I <br /> SERVICES WEIGHING MORE THAN 56 POUNDS MARTIN LEE HILL <br /> AND ALL PENDANT LIGHT FOMSTRUTURES SHALL BE STATE OF WASH HILL N <br /> SUPPORTED DIRECTLY FROM STRUCTURE L <br /> ABOVE USING APPROVED HANGARS f <br /> O <br /> LIGHT FIXTURES,AIR TERMINALS,AND SERVICES LIGHT FIXTURES,AIR TERMINALS,AND SERVICES SHALL 'Z <br /> SHALL BE POSITIVELY ATTACHED TO THE CEILING BE POSITIVELY ATTACHED TO THE CEILING SYSTEM <br /> SYSTEM <br /> `T1 <br /> /r+ 1 IIGHT FU(TURF AND MECHANICAL SERVICE SUPPORT �� " <br /> V /r.1 LIGHT FU(TURF AND MECHANICAL SERVICE J T <br /> Z <br /> FOUR 12 GAGE MINIMUM WIRES SPLAYED 90 DEGREES FOUR 12 GAGE MINIMUM WIRES SPLAYED 90 O T_�x >_ C"! <br /> — <br /> (INPLAN)FROM EACH OTHER AND SECURED O <br /> MAIN DEGREES(IN PLAN)FROM EACH OTHER AND W Q <br /> RUNNER <br /> EN <br /> RUNNER WITHIN 2"OF INTERSECTION.EACH END OF SECURED TO MAIN RUNNER WITHIN 2"OF ` > <br /> EACH 00 <br /> WIRE TO BE LOOPED AND WRAPPED AROUND INTERSECTION.EACH END OF EACH WIRE TO BE r <br /> ITSELF 3TIMES MINIMUM WITHIN A 3"MAX LENGTH, LOOPED AND WRAPPED AROUND ITSELF 3 TIMES Q <br /> MINIMUM WITHIN A 3"MAX LENGTH. Z Q Q <br /> co <br /> PROVIDE CEILING EXPANSION JOINTS W � O <br /> AS NECESSARY,DIVIDING CEILING INTO w <br /> N5 ° PROVIDE CEILING EXPANSION JOINTS N5 X},P1' as°,,• AREAS NO GREATER THAN 2500 SF. I..MAX C Z Q Q CO <br /> AS NECESSARY,DIVIDING CEILING INTO �QI- CLU <br /> I1 <br /> AREAS NO GREATER THAN 2500 SF I. <br /> I1V U Q U Z LU <br /> ' O a m a W <br /> e) <br /> 2 I W STORE#: 22817 <br /> B"MAX EACH SIL1E v PROJECT* 60007-039 <br /> ISSUE DATE: 1 0/2 712 0 2 3 <br /> .FOR SPANS UP TO 64%USE A SINGLE 20 GAGE 15/8" W DESIGN MANAGER: GRAPHITE <br /> COMPRESSION STRUT FASTENED TO MAIN TEE WITH(2)NOB PRODUCTION DESIGNER:GRAPHITE <br /> DIRECTION AND WITHIN 6-0 8'-0"O OF PERIMETER <br /> LOCATE BRACING 1EACH SCREWS AND TO STRUCTURE WITH(2)HILTI X-DNL145 DIAX314" FOR SPANS UP TO 6-0",USE A SINGLE 20 GAGE 15/8" CHECKED BY: GRAPHITE <br /> WALLS,PARTITIONS,OR EXPANSION JOINTS FOR SPANS UP TO Y-0",USE DOUBLE COMPRESSION STRUT COMPRESSION STRUT FASTENED TO MAIN TEE WITH(2)NO 8 <br /> SCREWS AND TO STRUCTURE WITH(2)HILTI X•DNI.145 DIAX 3/4". LOCATE BRACING AT 12'-0"OC EACH THESE DOCUMENTS HAVE NOT BEEN <br /> DIRECTION AND WITHIN 6-0"OF PERIMETER APPROVED FOR THE ISSUANCE OF Z Revision Schedule <br /> FOR SPANS UP TO 9-T.USE DOUBLE COMPRESSION STRUT. WALLS,PARTITIONS,OR EXPANSION JOINTS PUBLIC WORK,MECHANICAL,FIRE <br /> SUPPRESSION,ELECTRICAL OR ,^ Rev Date B Description <br /> LATERAL BRACING REQUIRED IF ANY OF THE FOLLOWING EXISTS: PLUMBING PERMITS V <br /> -GYPSUM BOARD CEILING THAT EXTENDS WALL-TO-WALL EXCEEDS 10008E \ / <br /> -GYPSUM BOARD CEILING THAT DOES NOT EXTEND WALL-TO-WALL EXCEEDS 144 SF �c ` EXPANSION JOINT FOR CEILINGS EXCEEDING 2500 SF ! c� LATERAL BRACING FOR CEILINGS EXCEEDING 144 SF <br /> C' TEGORY C: IQ r C / F ` EXPANSION JOINT FOR CEILINGS EXCEEDING <br /> GORY 2500 SF N <br /> W <br /> SHEET TITLE: <br /> CITY OF EVERETT G INTERIOR DETAILS- <br /> REVIEWED FOR PERMIT SUSPENDED CEILING <br /> 2 SUSPENDED GYP BD CEILING- IBC SEISMIC CATEGORY D, SUSPENDED ACOUSTICAL CEILING SYSTEM- IBC DESIGN CATEGORY-6 Ef SCALE:AS SHOWN <br /> SHEET NUMBER: <br /> 1504 <br />