MEANS OF EGRESS <br /> GENERAL NOTES 1. AREAS INCLUDED FOR OCCUPANT LOAD CALCULATION DO NOT INCLUDE 10. DEAD-END CORRIDORS(IBC SECTION 1020.4,EXCEPTION#2): 13. EXIT SIGNS(IBC SECTION 1013): <br /> CORRIDORS,STAIRS,RESTROOMS AND UNOCCUPIED AREAS. 2.IN OCCUPANCIES GROUPS R-2 AND S-2 WHERE THE BUILDING IS EQUIPPED A.PROVIDE AN APPROVED EXIT SIGN AT ALL EXITS AND EXIT ACCESS DOORWAYS <br /> 1. SEE SITE PLAN FOR ACTUAL AND ASSUMED PROPERTY LINES INCLUDING THOSE REQUIRED BY THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN (FROM SPACES REQUIRING TWO EXITS)IN A LOCATION THAT IS READILY VISIBLE OH NSON BRAD N DINc. <br /> .20151BC SECTION 705.3.ALL BUILDINGS MINIMUM FIRE SEPARATION DISTANCE=30'-0" 2. THE NUMBER OF OCCUPANTS HAVE BEEN ROUNDED UP. ACCORDANCE WITH SECTION 903.3.1.1.THE LENGTH OF THE DEAD-END CORRIDORS FROM ANY DIRECTION OF EGRESS TRAVEL.PLACE SIGNS SUCH THAT NO POINT <br /> a 15200 52nd Ave.South <br /> SHALL NOT EXCEED 50 FEET(15,240 MM). IN CORRIDOR OR EXIT PASSAGEWAY IS MORE THAN 100 FT FROM THE NEAREST Suite 300 <br /> a 2. 3 HR FLOOR/CEILING ASSEMBLY 3. DESIGN OCCUPANT LOAD PER IBC TABLE 1004.1.2:SEE CALCS.BY OCCUPANCY ON VISIBLE EXIT SIGN.SEE BUILDING PLANS FOR SIGN LOCATIONS. <br /> -SEE BUILDING SECTION&HORIZONTAL ASSEMBLY DETAILS ON SHEET A040,A041. THIS SHEET. 11. EGRESS WIDTH(IBC SECTION 1005.3.2,EXCEPTION): SHALL NOT BE LESS THAN B.EXIT SIGNS SHALL BE INTERNALLY OR EXTERNALLY ILLUMINATED PER IBC Seattle,WA 98188 <br /> A.STORAGE,BUILDING SERVICES&MECH.ROOM =300 SF/OCCUPANT(GROSS) THE TOTAL OCCUPANT LOAD SERVED BY THE MEANS OF EGRESS MULTIPLIED BY: SECTION 1013.5 AND 1013.6 Phone 206.766.8300 <br /> 3. TABLE 705.8 ALLOWS 45%OF WALL AREA TO HAVE UNPROTECTED OPENINGS IN R-2, B.RESIDENTIAL =200 SF/OCCUPANT(GROSS) A..15 INCHES PER OCCUPANT FOR OTHER COMPONENTS(SPRINKLERED) C.PROVIDE A TACTILE EXIT SIGN STATING"EXIT"AND COMPLYING WITH ICC vmvjohnsoni,mund- <br /> SPRINKLERED BUILDINGS WITH AFIRE SEPARATION DISTANCE FROM 10 FEET TO LESS PROPOSED 36"DOOR=34"/.15=226 OCCUPANTS ACCOMMODATED Al 17.1-2009 ADJACENT TO EACH DOOR TO AN AREA OF REFUGE,EXTERIOR ARCHITECTURE <br /> THAN 15 FEET. 5. NUMBER OF EXITS(IBC SECTION 10061:TWO EXITS SHALL BE REQUIRED FROM ANY B.SEE EXITING PLANS FOR ACTUAL NUMBER OF OCCUPANTS AT EACH DISCHARGE. AREA FOR ASSISTED RESCUE,EXIT STAIRWAY,EXIT RAMP,EXIT PASSAGEWAY INTERIOR DESIGN <br /> SPACE WHERE THE OCCUPANT LOAD EXCEED THE FOLLOWING VALUES PER IBC TABLE AND EXIT DISCHARGE. Greg L.Allwine, <br /> 4. MEANS OF EGRESS/CORRIDOR: 1006.2.1:SEE EXITING PLAN ON THIS SHEET. 12. MEANS OF EGRESS ILLUMINATION(IBC SECTION 1008): Jeffrey A.Williams, <br /> IBC SECTION 1020.2 THE MINIMUM WIDTH OF CORRIDOR SPECIFIED IN TABLE 1020.2 A.ILLUMINATION SHALL BE PROVIDED AT EVERY POINT IN THE MEANS OF EGRESS.THE <br /> SHALL BE AS DETERMINED IN IBC SECTION 1005.1. 6. SEPARATION OF EXITS(IBC SECTION 1007.1.1):WHERE TWO EXITS ARE REQUIRED ILLUMINATION LEVEL SHALL NOT BE LESS THAN 1 FOOT-CANDLE(11 LUX)AT THE <br /> STAIR: THEY SHALL BE PLACED A DISTANCE APART EQUAL TO NOT LESS THAN 1/2 THE WALKING SURFACE AT ALL TIMES THE SPACE SERVED BY THE MEANS OF EGRESS IS <br /> IBC SECTION 1011.2 THE WIDTH OF STAIRWAYS SHALL BE DETERMINED AS DIAGONAL DIMENSION OF THE AREA SERVED.SEE EXITING PLANS ON THIS SHEET FOR OCCUPIED.LUMINARIES SHALL BE INSTALLED WHENEVER EXIT SIGNS ARE <br /> SPECIFIED IN IBC SECTION 1005.1,BUT SUCH WIDTH SHALL NOT BE LESS THAN 44". SEPARATION DIMENSIONS. REQUIRED. <br /> SEE IBC SECTION 1009.3 FOR ACCESSIBLE MEANS OF EGRESS STAIRWAYS. B.POWER SUPPLY TO BE PROVIDED BY PREMISES'ELECTRICAL SUPPLY.IN EVENT OF <br /> 7. COMMON PATH OF EGRESS TRAVEL(IBC TABLE 1006.2.1): POWER SUPPLY FAILURE,AN EMERGENCY POWER SYSTEM SHALL AUTOMATICALLY <br /> A. 100'MAX GROUP S-2 WITH OCCUPANT LOADS OVER 30(SPRINKLERED BUILDING) ILLUMINATE AREAS REQUIRED PER IBC SECTION 1008.3 INCLUDING:CORRIDORS,EXIT <br /> 7. SEE STAIR SECTIONS REFERENCED PER BUILDING BELOW FOR EMERGENCY LIGHT FIXTURE LOCATION. B. 125 MAX GROUP R-2 WITH OCCUPANT LOADS OVER 30(SPRINKLED BUILDING) ENCLOSURES,EXIT PASSAGEWAYS,INTERIOR EXIT DISCHARGE ELEMENTS AND <br /> BLDG A SEE SHEETS A480&A481 EXTERIOR LANDINGS FOR EXIT DISCHARGE DOORWAYS. <br /> BLDG B SEE SHEETS A481&A482 9. EXIT ACCESS TRAVEL DISTANCE(IBC SECTION 1017): C.EMERGENCY POWER SYSTEM SHALL PROVIDE POWER FOR A DURATION OF <br /> BLDG C&D SEE SHEETS A481 A.GROUP S-2 =400 FT(SPRINKLERED) NOT LESS THAN 90 MINUTES AND SHALL CONSIST OF STORAGE BATTERIES,UNIT <br /> B.GROUP R-2 =250 FT(SPRINKLERED) EQUIPMENT OR AN ON-SITE GENERATOR.REFER TO ELECTRICAL BIDDER/DESIGN <br /> TACTILE EXIT SIGN PLANS FOR SYSTEM DESIGN. <br /> 18"MIN.CUR FUR SPACE CENTERED <br /> ON TACTILE CHARACTERS �6 <br /> 4" REGISTERED <br /> ARCHITECT <br /> 3" 11.. <br /> I FFRF.Y ARTH[IR riII.I.IAM <br /> STATE OF WASHINGTON <br /> C <br /> STAMP <br /> uLL <br /> k <br /> LL 5� <br /> s o� <br /> z_ a <br /> R <br /> NOTES: <br /> 1. 4"WIDE x 3"HIGH x 1/8"THICK SIGN MOUNTED AT STRIKE SIDE <br /> OF EXIT DOORS. <br /> 2. LETTER CHARACTERS TO BE RAISED 1/32"x 7/8"HIGH UPPER <br /> CASE,SAN SERIF TYPE AND ACCOMPANIED BY GRADE 2 267'-4112" <br /> ROUNDED OR DOMED SHAPED BRILLE. EXIT FSD=>30' <br /> 3. BRAILLED CHARACTERS TO CONFORM WITH STANDARD STAIR 1 _ <br /> DIMENSIONS FOR LITERARY BRAILLE AND AS INDICATED IN 2� 2 SA SF ocaoss c <br /> 20091CC/ANSI A117.1703.3. eo sF soo GROSS s- +occ) - <br /> 4. LOCATE SIGN AT EACH REQUIRED EXTERIOR EXIT DOOR. 1 occ+ExIT so SF soo GROSS LONGEST EXIT ACCESS <br /> (EXTERIOR DOORS WITH ILLUMINATED EXIT SIGN ABOVE.) +occ 1 Exlr MAX DIAGONAL TRAVEL DISTANCE 142'-6" <br /> d <br /> 0 <br /> sio RoT I s F T­ ITS <br /> 1111 Ross F <br /> A / 81 o <br /> LL <br /> O <br /> iI48A9E �� 201'-7 1/4" L....... .................................. <br /> 'OSF 30a GROSS ; 6 RAGE A <br /> OCC 1 EXR 2 I. <br /> [ m �1♦ O o "® ®® "4) o EFF&GROSS y <br /> I ® ® a <br /> WEIGHTED AVERAGE CALCULATIONS BUILDINGA i x <br /> g ;6 SF 300 GROSS <br /> L1=267.3' W1=30 oc z occ1EXR <br /> L2=69.1' W2=30 W=(L1XW1)+(L2XW2)+(L3XW3)+(L4XW4) PER IBC506 / i <br /> L3-199.2' W3-30 F=(Li+L2+L3+L4) EXIT <br /> L4=69.1' W4=30 STAIR 1 <br /> (267.3x30)+(69.1x30)+(199.2x30)+(69.1 x30) (8,019)+(2,073)+(5,976)+(2,073)=18,141 18,141=30 -- - - - - - --_ ___ _ <br /> 267.3+69.1+199.2+69.1 604 604 LONGEST COMMON PATH -RAGE <br /> -- -- - - _ _ _ _ y <br /> OF EGRESS TRAVEL:90'-6" s-z MAX DISTANCE BETWEEN - -- <br /> SF SIX GROSS EXITS - <br /> 63'-0" 1 occ 1 E- 199'-2 3/4" 6 <br /> FSD=>30' FSD=>15' <br /> AREA OF INCREASE CALCULATIONS BUILDING A }� E <br /> P=698.2' y <br /> W=30' <br /> 2 LEVEL 2-BLDG A <br /> 1v1 Vrl � <br /> [F/P-0.25]x W/30=[604/604-0.251 x 30/30 1"=20'-0" 3 c LL <br /> [1-.25]X 1 <br /> FRONTAGE INCREASE FACTOR: 265'-81/2" w <br /> If=.75 <br /> EXIT FSD=>30'-0" <br /> CONVERGENCE STAIR 1 = wo>� � <br /> NMAX DIAG e® <br /> 1Gcc 2Fxn r--- J r--------------- ` mw Q <br /> ONAL .. <br /> Ross <br /> O <br /> y w k uzs <br /> OCCUPANT LOAD ` r-----„ ___ r--- -, ----, F3 F3 (� w aw <br /> s-z <br /> z r- ___ a t¢ i" <br /> a1 L ❑ ¢Ewe az <br /> ZI OCCUPANTS EXITS PROVIDED EXIT Q a 3 <br /> LEVELLE 5 96 2 _ iv _ O F�J 96 2 GG Ou°OpGO FE <br /> C LEVEL4 96 2 ♦ <br /> N <br /> LEVEL 3 96 2 <br /> �I LEVEL 2 96 2 Mec s oo caoss - 4 �26 70.. 1 RewGaoss <br /> sa sF s 203 4 <br /> LEVELI 108 3 0 �` occ ztxls czExiTs 4 <br /> E TOTAL 588 c�i cRAwcA� ____ - eua :.oe""E -----70 UNITS ____ ___ <br /> N <br /> U ONLY 2 EXITS ARE REQUIRED AS NO INDIVIDUAL STORY HAS>500 OCCUPANTS PER TABLE 1006.3.1 ° ss sF sooc-- 50 STALL l ____ _____ _____ ----- ECEcrRx:u <br /> ❑ - �occ�e-ars x'6O n,ass xx, �� 795 71/2 � � sz ❑ <br /> 3 N S - _ LL <br /> , _ -� I SF 2 E GROSS <br /> UL '. ..�... ................. xix I• . . . .i....L ..s.a.............. <br /> tOCC 2EXRa <br /> m <br /> y EGRESS LEGEND <br /> EXIT <br /> O DOOR EAGRESS WIDTH EXIT STAIR EGRESS WIDTH O AELEVATOR TOCCOMMODATE , "---- \ • STAIR 2 CONVERGENCE / <br /> E <br /> NT LOAD PER <br /> E <br /> 4 <br /> p _ _ L_____� -�____� L _�; �____� - � _j �____� ® / PROJECT#: 1827 <br /> E <br /> _ _ _ --- <br /> ., TOTAL NUMBER OF OCCUPANTS SERVED TOTAL#OF OCCUPANTS SERVED STRETCHER _ _ _ ZM;; <br /> 32'-6"LONGEST EXIT ACCESS <br /> REQUIRED DOOR WIDTH 2 REQUIRED STAIR WIDTH(.2) _ _ _ _ �_______ / DRAWN BY: AT,SK,ST <br /> N 0" ( ) 74'-6"LONGEST COMMON PATH TRAVEL DISTANCE_ _ _ <br /> g PROVIDED DOOR WIDTH PROVIDED STAIR WIDTH OF EGRESS DISTANCE TANCE BETWEEN EXITS - - - - - - - CHECKED BY: ST <br /> •"""""'• MAXIMUM EXIT ACCESS TRAVEL DISTANCE TO NEAREST EXIT(250'PER TABLE 1017.2) ACCESSIBLE 61'-5' - - - - - - - - 199'-1 1/2_ <br /> so MAXIMUM COMMON PATH OF EGRESS TRAVEL(125'PER TABLE 1006.2.1) * MEANS OF FSD=>30'-0" FSD=>15'-0" BLDG A-CODE <br /> EGRESS <br /> �j SUMMARY AND <br /> EXIT RAISED CHARACTER&BRAILLE EXIT SIGN PER IBC SECTION 1011.4 ELEVATOR <br /> OCCUPANCY <br /> F.E.C. FIRE EXTINGUISHER CABINET SEE DETAIL TYPE 5LB AC / 1 \ LEVEL 7-BLDG A <br /> A750 SIZE 2A 10BC v (/ <br /> 1"=20'-0" <br /> w 02 <br /> w PERMIT SET 10/09/2020 <br />