Laserfiche WebLink
a ATTIC VENTILATION CALCULATIONS <br /> ATTIC AREA:2,575,008 S.I(17,882 SF) ROOF NOTES <br /> m CEILING ASSEMBLY AT BOTTOM CHORD OF ROOF '11` <br /> TRUSSES INCLUDES CLASS II VAPOR BARRIER. 1. SEE STRUCTURAL DRAWINGS 4v <br /> REQUIRED VENTILATION @ 1/300(IBC SECTION 1203.2 FOR ROOF FRAMING. <br /> EXCEPTION 2):8,583 S.I.(59.6 S.F.) 2. ALL ROOFING TO BE CLASS OHNSON BRAUNDIxc. <br /> a MINIMUM PER IBC SECTION 1505 AND 15200 52nd Ave.South <br /> EAVE VENTILATION:770'L.F.(110,880 L.I.) TABLE a 1505.1. Suite 300 <br /> BIRD BLOCKING WITH THREE 2"DIAMETER HOLES SeatOe,WA 98188 <br /> PER TRUSS BAY W/1/8"MESH SCREEN 2.50 S.I. 3. ALL ROOF SLOPES ARE 4 1/8"/FT.U.N.O phone 206.766.8300 <br /> (.0174 S.F.)NFA PER NOTCH.SEE DIAGRAM 4/A500 4. ALL ROOF OVERHANGS ARE V-0"U.N.O vmvjohnsonhmund- <br /> 3.75 S.I.(.026 S.F.)NET FREE AREA PER LINEAL 5. DRAFTSTOPS ARE NOT REQUIRED ARCHITECTURE <br /> FOOT=19,664 S.I.(13.66 S.F.)TOTAL. IN BUILDINGS EQUIPPED WITH AUTOMATIC <br /> SPRINKLER SYSTEMS PER IBC SECTION INTERIOR DESIGN <br /> CONTINUOUS SOFFIT VENTILATION:261 L.F.(37,584 L.I.) 903.3.1.1(NFPA 13) Gregg L.All—, <br /> • STRIP VENT WITH 2"WIDE ON BALCONY CEILING Jeffrey A.Williams, <br /> WITH 1/8"MESH SCREEN.NET FREE AREA PER 6. PER IBC SECTION 708.4,IN <br /> LINEAL FOOT=4,885 S.I.(33.9 S.F.) COMBUSTIBLE CONSTRUCTION WHERE <br /> THE FIRE PARTITIONS ARE NOT REQUIRED <br /> CONTINUOUS RIDGE VENTILATION:689 L.F. TO BE CONTINUOUS TO THE SHEATHING, <br /> • COR-A-VENT REVOLUTION @ 12 S.I.NET PER FT.= DECK OR SLAB,THE SPACE BETWEEN THE <br /> 544.45*12 S.I./FT=6,88.5 S.I.(47.8 S.F.)TOTAL CEILING AND THE SHEATHING,DECK OR <br /> SLAB ABOVE SHALL BE FIRE BLOCKED OR <br /> TOTAL PROVIDED VENTILATION:19,664 S.I+4,886 S.I+ DRAFTSTOPPED IN ACCORDANCE WITH IBC <br /> 19,66 S.I.=13,737 S.I.(95 S.F.) SECTIONS 718.2 AND 718.3 AT THE <br /> • EAVE&SOFFIT VENTS:(19,664+4,885/2,575,008)* PARTITION LINE.EXCEPTION#6: <br /> 100=79% FIREBLOCKING OR DRAFTSTOPPING IS NOT <br /> • RIDGE VENTS:(6,885/2,575,008)*100=80% REQUIRED AT THE PARTITION LINE IN <br /> BUILDINGS EQUIPPED WITH AN AUTOMATIC <br /> VENTILATION ALSO MEETS IBC SECTION 1203.2 SPRINKLER SYSTEM INSTALLED <br /> EXCEPTION 1 THROUGHOUT IN ACCORDANCE WITH IBX ass. <br /> SECTION 903.3.1.1.,.PROVIDED THAT REGISTERED <br /> AUTOMATIC SPRINKLERS ARE INSTALLED ARCHITECT <br /> IN COMBUSTIBLE FLOOR/CEILING AND - <br /> ROOF/CEILING SPACES. <br /> 7. DRAFTSTOPPING MATERIALS TO exaev>aTxors wnJJAM <br /> BE 1/2"GYP.SHEATHING OR 1/2"PLYWOOD sTATe av wnswxcTox <br /> OR OSB SHEATHING PER IBC SECTION <br /> 718.3.1. <br /> STAMP <br /> 8. PER IBC SECTION 1203.2 EXCEPTION: <br /> THE NET FREE CROSS-VENTILATION AREA <br /> SHALL BE PERMITTED TO BE REDUCED TO k <br /> 11300 PROVIDED BOTH OF THE FOLLOWING <br /> CONDITIONS ARE MET: <br /> 1.IN CLIMATE ZONES 6,7,AND 8,A CLASS I e E <br /> OR II VAPOR RETARDER IS INSTALLED ON o <br /> THE WARM-IN-WINTER SIDE OF THE CEILING. <br /> 2.AT LEAST 40 PERCENT AND NOT MORE <br /> THAN 50 PERCENT OF THE REQUIRED <br /> VENT IN ru <br /> G AREA IS PROVIDED BY a <br /> VENTILATORS LOCATED IN THE UPPER o$ <br /> PORTION OF THE ATTIC OR RAFTER SPACE. <br /> UPPER VENTILATORS SHALL BE LOCATED <br /> 2-HOUR STAIR ENCLOSURE <br /> FRAMING CONTINUOUS NOT MORE THAN 3 FEET BELOW THE RIDGE <br /> UNDERSIDE OF ROOF SHEATHING. 5 OR HIGHEST POINT OF THE SPACE, <br /> A311 MEASURED VERTICALLY,WITH THE BALANCE <br /> STAIR ENCLOSURE ROOF FRAMING <br /> A.a A412 A.B OF THE VENTILATION PROVIDED BY EAVE OR <br /> TO BE ENTIRELY INDEPENDENT OF <br /> MAIN ROOF FRAMING CORNICE VENTS.WHERE THE LOCATION OF <br /> 1 WALL OR ROOF FRAMING MEMBERS <br /> HOOD FOR STAIRWELL CONFLICTS WITH THE INSTALLATION OF 2 <br /> PRESSURIZATION FAN UPPER VENTILATORS,INSTALLATION MORE <br /> THAN 3 FEET BELOW THE RIDGE OR `u <br /> HIGHEST POINT OF THE SPACE SHALL BE d <br /> iv 0 o= PERMITTED. <br /> iv p tO= 9. BATHROOMS SHALL BE <br /> x r 0 MECHANICALLY VENTILATED IN <br /> N O ACCORDANCE WITH THE IMC PER IBC <br /> o a SECTION 1203.5.2.1. <br /> DS DS DS D D DS <br /> D <br /> U' _ _ _ — ————— <br /> A410 _—_—_ _ _—_ _— `�< _—� _ J__ —�; Mil <br /> oil iii p <br /> i �u ul rc <br /> I u ul <br /> 10 <br /> iM w�u iii zo <br /> II IIIzo <br /> HATCH INDICATES EXTENT OF ATTIC ACCESS CATWALK iii <br /> SEE ELECTRICAL DRAWINGS FOR LIGHTING lil <br /> VENT CAP FOR TOP li I�u iii <br /> FLOOR UNITS,TYP. _ it <br /> -Ou ul <br /> ul <br /> IIII IIIIw <br /> I a <br /> A.3 --------------- -----------------s ====z---------------��' L----------------- ----- _____�-----------------------ii ----------------------- A.3 �€ <br /> 2 A31 2 °z <br /> 30 <br /> A.4 z=====s _ _ _ -��rynr _ _ _ _ _ _z===- 1 _ _ _ _ _ 1¢¢�hhr"� _ _ _ z=====s _ _�r r---- , 1-1 <br /> �PV�PV�PV 77 PV�PV 77 PV�PV�PV�PV�P_71 VJ V�PV�ry1��PV�PV�PV�PV�PV�PV�PV PV�PVC PV�PV�PV�PV�MV�P �PV�PV�PV�PV�PV�PV'hi�V�PV PV y s'az. <br /> \ /I\ /I\ /I\ /I\ /I\ /I\ /I\ /I\ /I\ /I\ /I\ /I\ /1\III\ /I\ /I\ /I\ /I\ /I\ /I\ /Ir /I\ /I\ /I\ /I\ /I\ /I\n/I\�I\ /I\ /I\ /I\ /I\ /I\ L3 <br /> I X I X X X x X x X x X x X x 1 4 1 X X X X X X X X I X I X I X I X I X 1 :� I XI I X I X I X I X I X X Iipx d w' R �® <br /> I/ \1/ \I/ \1/ \I/ \1/ \I/ \1/ \I/ \I/ \1/ \I/ \1/ \I/i;h1/ \I/ \1/ \I/ \1/ \I/ \1/ \11/ \I/ \I/ \I/ \1/ \I/ \1N;ii\I/ 11/ \I/ \1/ \I/ \I/ \I/ \1;I/; \1 <br /> �PV PV PV PV�PV PV — PV PV PV PV P PV PV PV PV PV PV PV PV PV PV PA *—ft* V PV PV PV P-*F k P <br /> \ /I\ /I\ /I\ /I\ /I\ /1 1\ /1\ /I\ /I\ /Iv, \ /I\ /I\ /I\ /I\ /I\ /I\ /II\ /I\ /I\ /I\ /I\ /I\ /I II/I\ (I\ /1\ /1\ /I\ /I\ /I\ /I;q /I \ u U�v w aw <br /> X X X X X X I x I x I x x I NI x I x I x I x I x x I x I x I x I x I x I x I x 114 1 x I x I x I x I x 1 x I x I;I'X I V q.x I/ \1/ \I/ \1/ \I/ \1/ \I I/ \I/ \I/ \1/ \I/;I�1/ \I/ \1/ \I/ \I/ \I/ \I/ \1� \I/ \I/ \I/ \1/ \I/ \11,�I\I/ I/ \I/ \I/ \I/ \I/ \I/ \Ili{ \I / L o ¢@- M <br /> m y v Ili Y—Y— i—� 3 a w=o o� <br /> zi k\ \ \ \ \ — P \ v — gyp i 11;P i V PV w o° m <br /> 2 1 x I x I x I x I x I x I x 1 401 <br /> 1 x I x I x I x I x I X I x I x I x I x I xi x I x I x x x x I;ax LL <br /> / \I/ \1/ \I/ \I/ \1 / \I/ \1/I�1/ \1/ \I/ \I/ \I/ \1 I/ \I/ \1/ \I/ \1/ \1 \I/ \I/ \I/ \I/ <br /> U DS �PV)(PVX PV y �-� L —xPM PVx— y PVX PV PV by P xPVx PVx PV ` (PV'pVXPV PV <br /> `I F q(� \ / \II/ \ / \ /I\ / z \ / \ / \ / xl,/ \ \ / \ / \ / \ <br /> Q I X I X I X I J� Z FL I X I o! I X I X X w I X I X I X I X I X I X I X I X Iq'X <br /> E I/ \I/ \I/ \1 > I/ \I/:NI/ \I/ \I/ \I w I/ \I/ \I/ \1/1i\I/ 1/ \I/ \I/ \I I/ \II� \I / <br /> IL <br /> �2 DS DS D DS DS w <br /> y w <br /> c o <br /> N o N,O ry 0 o f 6"PREFINISHED ALUMINUM <br /> 0 N O K-STYLE GUTTERS A310 o= KEY PLAN PROJECT#: 1827 <br /> j� ICE&WATER SHIELD,TYP. VENT CAP FOR TOP FLOOR CUT 18"x 18"OPENINGS IN MAIN O DRAWN BY: AT <br /> N EXTEND 24"PAST FACE UNITS,TYP.ADJUST LOCATIONS ROOF SHEATHING TO ALLOW <br /> OF EXTERIOR WALL IN FIELD TO AVOID CONFLICTS VENTING OF OVERFRAMED AREAS CHECKED BY: ST <br /> g Aa SEE 12/XBE 6.00 TYP. WITH SOLAR HW AND SOLAR PV Ae <br /> so COMPONENTS. <br /> so BLDG A-ROOF PLAN <br /> wv:�]Ci <br /> WEST <br /> w A216A <br /> BUILDINGA <br /> �1�BLDG A-ROOF PLAN WEST PERMIT PERMIT SET 10/09/2020 <br /> z <br /> w <br /> 1 1/8"=1'-0" <br />