Laserfiche WebLink
Space Input Data <br />EVE ZAP ENERGY-v5-11 10/22/2024 <br />HERMANSON COMPANY LLP 11:16AM <br />ZAP -OFFICE 3 <br />1. General Details: <br />Floor Area ................... <br />............................................ 353.0 <br />ft2 <br />Avg. Ceiling Height <br />9.0 <br />ft <br />Building Weight...................................................30.0 <br />Ib/ft2 <br />1.1. OA Ventilation Requirements: <br />Space Usage .................................................... <br />User -Defined <br />OA Requirement 1 <br />5.0 <br />CFM/person <br />OA Requirement 2 <br />.............................................. 0.06 <br />CFM/ft2 <br />Space Usage Defaults <br />ASHRAE Std 62.1-2016 <br />2.lnternals: <br />2.1. Overhead Lighting: <br />Fixture Type __________________ <br />Recessed (Unvented) <br />Wattage................................................................................ <br />0.78 <br />W/ft2 <br />Ballast Multiplier <br />1.08 <br />Schedule.........................................90.1 <br />Office Lights/Elec <br />2.2. Task Lighting: <br />Wattage 0.00 W/ft2 <br />Schedule............................................................................. None <br />2.3. Electrical Equipment: <br />Wattage .............................................. 405.0 Watts <br />Schedule 90.1 Office Lights/Elec <br />3. Walls, Windows, Doors: <br />(No Wall, Window, Door data). <br />4. Roofs, Skylights: <br />(No Roof or Skylight data). <br />5. Infiltration: <br />Design Cooling ................................................. 0.00 CFM <br />Design Heating 0.00 CFM <br />Energy Analysis 0.00 CFM <br />Infiltration occurs at all hours. <br />6. Floors: <br />Type ........................ Floor Above Unconditioned <br />Space <br />Floor Area <br />353.0 <br />ft2 <br />Total Floor U-Value......................................................... <br />0.029 <br />BTU/(hr•ft2•OF) <br />Unconditioned Space Max Temp. <br />86.0 <br />OF <br />Ambient at Space Max Temp ........................................ <br />86.0 <br />OF <br />Unconditioned Space Min Temp. <br />44.0 <br />OF <br />Ambient at Space Min Temp ....................................... <br />18.0 <br />OF <br />7. Partitions: <br />(No partition data). <br />2.4. People <br />Occupancy <br />3.0 <br />People <br />Activity Level ........................................................Office <br />Work <br />Sensible <br />245.0 <br />BTU/hr/person <br />Latent.................................................................................. <br />205.0 <br />BTU/hr/person <br />Schedule <br />90.1 Office Occupancy <br />2.5. Miscellaneous Loads: <br />Sensible <br />0 <br />BTU/hr <br />Schedule ......................................... <br />90.1 Office Lights/Elec <br />Latent <br />0 <br />BTU/hr <br />Schedule ......................................... <br />90.1 Office Lights/Elec <br />Hourly Analysis Program v5.11 Page 1 of 2 <br />