Laserfiche WebLink
Seismic Load Calculation for Components and System <br />(Reference: 2018 IBC Section 1613 & ASCE 7-16 Section 13.3) <br />0.2s Spectral Response Acceleration, Site Class B, S, = <br />1.245 <br />(ASCE 7, Figure 22-1 thru 22-8) <br />1.0s Spectral Response Acceleration, Site Class B, S, = <br />0.442 <br />(ASCE 7, Figure 22-1 thru 22-8) <br />Site Class = <br />D <br />(ASCE 7, Section 11.4.3) <br />Seismic Design Category = <br />(ASCE 7, Tables 11.6-1 & 11.6-2) <br />Site Coefficient per S, & Site Class, F. - <br />1.20 <br />(ASCE 7, Table 11.4-1) <br />Site Coefficient per S, & Site Class, F <br />(ASCE 7, Table 11.4-2) <br />SMs = F,S, <br />1.494 <br />(ASCE 7, Section 11.4.4) <br />S,= FvSl = <br />Z <br />0.821 <br />(ASCE 7, Section 11.4.4) <br />SDs = 2/3 SMs = <br />0.996 <br />(ASCE 7, Section 11.4.5) <br />SDI = 2/3 SMt = <br />0.547 <br />(ASCE 7, Section 11.4.5) <br />(Per ASCE 7-16, 13.3) <br />Component Amplification Factor, ap = <br />1.0 <br />(ASCE 7, Table 13.6-1) <br />Component Response Modification Factor, Rp = <br />2.5 <br />(ASCE 7, Table 13.6-1) <br />Overstrength Factor, (1, = <br />2.0 <br />(ASCE 7, Table 13.6-1) <br />Component Importance Factor, Ip = <br />1.0 <br />(ASCE 7, Table 1.5-2) <br />Component Operating Weight, W. = <br />Wp <br />(Ib) <br />Height in structure at lowest point of attachment of component, z, = <br />128 <br />(ft) <br />Height in structure at highest point of attachment of component, zZ = <br />133 <br />(ft) <br />Average Roof Height of Structure, h = <br />128 <br />(ft) <br />Seismic design force, FP = <br />0.4apSDsWP <br />(1+2z/h) <br />v/ P <br />E <br />(q 13.3-1 ) <br />Max. seismic design force, Fp,,,,, = <br />1.65DSIPWP <br />(Eq. 13.3-2) <br />Min. seismic design force, Fp,,, = <br />0.3SDSIpWp <br />(Eq. 13.3-3) <br />Seismic design force at lowest point, Fp, = <br />Seismic design force at highest point, Fp2 = <br />Min. seismic design force, Fp,,,i = <br />Max. seismic design force, Fp,,,,, _ <br />0.478 Wp <br />Fp IpvGi= 0.484 <br />0.491 Wp <br />0.299 Wp <br />1.594 Wp <br />Seismic design force, Fp (ASD) = 0.346 Wp <br />BEL <br />C ChlllM <br />ENGINEERING <br />Seismic Loads For Components &Systems <br />250 4th Ave. South EVERETT CITY HALL I <br />N.T.S. <br />Suite 200 lob N. <br />Edmonds, WA 98020 21015.312 <br />9/27/2023 <br />M <br />