<br /> REFERENCE SYMBOLS yIDUC�TWOyR.K SYMBOLS GENERAL NOTES: HVAC SHEET INDEX
<br /> NEW PLUMBING WORK NEW DUCTWORK GENERAL: FIXTURES,EXPOSED DUCTS,PIPING AND SIMILAR ITEMS. SEISMIC-RESISTING COMPONENT LISTED IN THE STATEMENT MO.1 HVAC LEGEND.SCHEDULES
<br /> EXISTING PLUMBING WORK 1. COORDINATE MECHANICAL WORK WITH ELECTRICAL, 13.PROVIDE EQUIPMENT THAT FITS INTO THE SPACE ALLOTTED OF SPECIAL INSPECTIONS.
<br /> F-'- - -'-z1--1 RISE OR DROP DIRECTION ARCHITECTURAL,STRUCTURAL,CIVIL AND LANDSCAPE AND ALLOWS ADEQUATE ACCEPTABLE CLEARANCE FOR 4. HANGERS AND SEISMIC BRACING FOR THE MECHANICAL DH • -ct
<br /> EXISTINGPLUMBING WORK TO OF AIR FLOW WORK SHOWN ON OTHER CONTRACT DOCUMENTS.PROVIDE INSTALLATION,REPLACEMENT,ENTRY,SERVICING AND SYSTEMS SHALL BE DESIGNED AND PROVIDED BY THE M1.1 HVAC FLOOR PLAN
<br /> ADDITIONAL OFFSETS FOR COORDINATED INSTALLATION MAINTENANCE.COORDINATE WITH OTHER TRADES TO MECHANICAL CONTRACTOR.REFER TO CONTRACTOR SHOP
<br /> BE DEMOLISHED INTERNALLY LINED DUCT WHERE REQUIRED. ENSURE NO CONFLICT WITH REQUIRED CLEARANCES. DRAWINGS FOR LOCATIONS OF EQUIPMENT AND HUNG C L N
<br /> ENLARGED PLAN BORDER 1� 2. COORDINATE HVAC,PLUMBING AND FIRE PROTECTION 14.PROVIDE OFFSETS IN PIPING WHERE PLUMBING/PIPING WALL MECHANICAL SYSTEMS.THE MECHANICAL CONTRACTOR
<br /> MANUAL VOLUME DAMPER WORK PRIOR TO INSTALLATION.DUCTWORK AND IS LOCATED DIRECTLY ABOVE STRUCTURE.OFFSET PIPING SHALL COORDINATE THE SUPPORT SYSTEMS AND DESIGN
<br /> MATCHLINE EQUIPMENT ACCESS TAKES PRECEDENCE OVER PIPING INTOCASEWORKORSHAFTTIGHTTOWALLANDBACKINTO LOADS FOR HUNG MECHANICAL SYSTEMS WITH THE BUILDING CODES: SDH Architect
<br /> RfJfJ FOR AVAILABLE SPACE. WALL ONCE BELOW STRUCTURE.REFER TO STRUCTURAL GENERAL CONTRACTOR AND OTHER TRADES THAT MAY BE
<br /> DRAWINGS. IMPACTED. 730215th Ave NE
<br /> 1 BACKDRAFT DAMPER 3. WHERE USED,THE TERM"PROVIDE"SHALL MEAN"FURNISH 2O18 INTERNATIONAL BUILDING CODE
<br /> SECTION IDENTIFIER AND INSTALL'. 15.BUILDING SPACE IS LIMITED.STRONG ATTENTION TO DETAIL DEMOLITION: Seattle,WA 98115
<br /> AND CARE MUST BE TAKEN WHEN DEVELOPING SHOP 1. TAKE CAUTION IN DEMOLITION OF MECHANICAL EQUIPMENT. 206.369.8881
<br /> 4. COORDINATE EQUIPMENT CONNECTIONS WITH 2O18 UNIFORM PLUMBING CODE
<br /> DRAWING SO ROUTING IS COORDINATED WITH OTHER
<br /> 1 MOTOR OPERATED DAMPER MANUFACTURERS'CERTIFIED DRAWINGS.COORDINATE AND 2. CONTRACTOR SHALL REMOVE AND LEGALLY DISPOSE OF
<br /> e DISCIPLINES.
<br /> PROVIDE DUCT AND PIPING TRANSITIONS REQUIRED FOR ALL PIPING DUCTWORK AND EQUIPMENT INDICATED ON 2018 WASHINGTON STATE ENERGY CODE AND WASHINGTON STATE AMENDMENTS
<br /> PX.X DETAIL OR DRAWING IDENTIFIER FINAL EQUIPMENT ET.FIELD
<br /> VERIFY TIONS AND COO DINAT DU 16.MATERIALS AVEWIT A LAMEPLEN SPREAD
<br /> INDEX
<br /> NONCOMBUSTIBLE DRAWINGS VALVES,
<br /> PLENUM
<br /> WALLS,
<br /> DAMPERS,
<br /> INSULATION, amsx
<br /> DUCT SMOKE DETECTOR EQUIPMENT.FIELD VERIFY AND COORDINATE DUCT AND OR SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN HANGERS,VALVES,PLENUM WALLS,DAMPERS,ASSOCIATED
<br /> LD, AMERICAN SOCIETY OF CIVIL ENGINEERS(ASCE)7-16
<br /> PIPING DIMENSIONS BEFORE FABRICATION. 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WIRING,CONTROLS,AND APPURTENANCES ASSOCIATED
<br /> J REVISION CLOUD INDICATES WHERE �Ll�� �.�. 5. PROVIDE MISCELLANEOUS STEEL REQUIRED TO ENSURE WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. WITH EACH PIECE OF EQUIPMENT.
<br /> SECTION APPEARS 1--�� FIRE DAMPER PROPER INSTALLATION OF MECHANICAL SYSTEMS. 3. EXISTING CONTROL PATHWAYS MAY BE RE-USED.
<br /> 6. LOCATE VALVES,WATER HAMMER ARRESTERS,CLEANOUTS PLUMBING: COORDINATE CONTROLS DEMO WORK PRIOR TO
<br /> Q INDICATES REVISION&NUMBER I�.�. AND SIMILAR COMPONENTS SO THAT THEY ARE ACCESSIBLE. 1. DOMESTIC WATER TUBE,PIPE,FITTINGS,JOINING DEMOLITION.REMOVE ALL EXISTING THERMOSTATS SHOWN
<br /> 1--I-� SMOKE DAMPER PROVIDE ACCESS DOORS FOR MECHANICAL EQUIPMENT MATERIALS SPECIALTIES PLUMBING EQUIPMENT PLUMBING ON THE DRAWINGS ALONG WITH ASSOCIATED WIRING AND
<br /> INSTALLED BEHIND WALLS,ABOVE INACCESSIBLE CEILINGS FIXTURES,PLUMBING FITTINGS AND ALL OTHER RACEWAYS.
<br /> 1� FLAG NOTE AND BELOW FLOORS.COORDINATE ACCESS DOOR APPURTENANCES IN CONTACT WITH DRINKING WATER SHALL 4. WHERE EXISTING ITEMS PENETRATE A WALL OR ROOF,
<br /> LOCATIONS WITH ARCHITECTIENGINEER.INSTALL TAG ON BE LEAD-FREE EXCEPT THOSE EXPLICITLY EXEMPTED INCONTRACTOR SHALL PROVIDE RATE AT AL PENETRATIONS
<br /> P-XXX EQUIPMENT IDENTIFIER COMBINATION FIRE/SMOKE DAMPER CEILING GRID FRAME TO INDICATE LOCATION AND TYPE OF SECTION 3874 OF THE SAFE WATER DRINKING ACT. THROUGH OR SHALL
<br /> WITH LIKE MATERIALS.PATCH I om
<br /> EQUIPMENT THAT REQUIRES MAINTENANCE.PROVIDE 16 GA, LEAD-FREE SHALL MEAN(A)NOT CONTAINING MORE THAN REPAIR TO MATCH SURROUNDING SURFACES INCLUDING
<br /> STEEL,FLUSH TYPE ACCESS DOOR WITH CONCEALED HINGE 0.2 PERCENT LEAD WHEN USED WITH RESPECT TO SOLDER
<br /> POINT OF CONNECTION HORIZONTAL FIRE DAMPER AND SLOT SCREWDRIVER TYPE CAM LATCH.PROVIDE AND FLUX;AND(B)NOT MORE THAN A WEIGHTED AVERAGE PAINT.
<br /> FACTORY PRIMED IN PAINTED SURFACE AREAS FOR FIELD OF 0.25 PERCENT LEAD WHEN USED WITH RESPECT TO 5. CONTRACTOR SHALL PROVIDE TEMPORARY SUPPORT OF ROIC of WASHINGTON
<br /> OER HORIZONTAL SMOKE DAMPER PAINTING.PROVIDE STAINLESS STEEL FOR ALL OTHER WETTED SURFACES OF DOMESTIC WATER TUBE,PIPE, EXISTING MECHANICAL EQUIPMENT WHERE REQUIRED BY
<br /> AREAS.PROVIDE ILL LISTED AND LABELED DOOR WHERE FITTINGS,JOINING MATERIALS,SPECIALTIES,PLUMBING DEMOLITION OR ALTERATION OF EXISTING STRUCTURE 8905 Towne Center Drive,Suite 108
<br /> NORTH ARROW HORIZONTAL COMBINATION FIRE-RESISTANCE RATING IS INDICATED ON DRAWINGS. EQUIPMENT,PLUMBING FIXTURES,AND PLUMBING FITTINGS. DURING CONSTRUCTION.COORDINATE WITH GC AND San Diego,CA 92122
<br /> FIRE/SMOKE DAMPER ACCESS DOOR SHALL BE SIZED SO THAT ADJACENT 2. PROVIDE WATER HAMMER ARRESTORS IN DOMESTIC WATER PROVIDE NECESSARY SUPPORTS AND HANGERS TO
<br /> EQUIPMENT IS ACCESSIBLE.PROVIDE ACUDOR,ELMDOR, PIPING IN ACCORDANCE WITH PDI-WH 2O1. MAINTAIN INTEGRITY,SAFETY AND PROPER OPERATION OF
<br /> MECHANICAL ACCESS 3. PROVIDE LINE SIZE STRAINER UPSTREAM OF EACH
<br /> FLEXIBLE CONNECTION MILCOR,OR APPROVED. EXISTING MECHANICAL SYSTEMS.
<br /> orvsuLr a
<br /> J 7. COORDINATE ATTACHMENTS TO STRUCTURE TO VERIFY BACKFLOW PREVENTER,WATER PRESSURE REDUCING 6. THE OWNER HAS THE RIGHT TO RETAIN OWNERSHIP OF ANY
<br /> UC UNDERCUT DOOR THATATTACHMENT POINTS ON EQUIPMENT AND STRUCTURE VALVE,CONTROL VALVE,SOLENOID VALVE AND PUMP. MATERIALS BEING REMOVED.DELIVER ITEMS TO THE
<br /> CAN ACCEPT SEISMIC,WEIGHT,AND OTHER LOADS IMPOSED. PROVIDE SHUTOFF VALVE ON EACH SIDE OF STRAINER. OWNER'S REPRESENTATIVE AS INDICATED IN THE
<br /> ® ® SUPPLY AIR DUCT SECTION 8. REFER TO TYPICAL DETAILS PROVIDED IN THIS DWG SET FOR q, VALVES,EXPANSION FITTINGS/LOOPS,AND PIPING CONTRACT DOCUMENTS.NOTIFY OWNER IN WRITING AT
<br /> DUCTWORK,PIPING,AND EQUIPMENT INSTALLATION. SPECIALTIES SHALL BE FULL SIZE OF PIPE UNLESS NOTED LEAST 7 DAYS IN ADVANCE OF DEMOLITION.)
<br /> CONTRACTOR IS RESPONSIBLE FOR CONFORMANCE WITH OTHERWISE.
<br /> RETURN OR OUTSIDE AIR DUCT SECTION DETAILS.
<br /> Permit#: M2307-003 NON-STRUCTURAL MECHANICAL COMPONENTS:
<br /> 9. LOCATIONS AND SIZES OF FLOOR,WALL,AND ROOF 1. THE FOLLOWING ITEMS ARE TAKEN DIRECTLY FROM THE
<br /> Site Address: 10121 Evergreen Way 1st Fir Ste 1 ® ® EXHAUST AIR DUCT SECTION OPENINGS SHALL BE COORDINATED WITH OTHER TRADES 2012 INTERNATIONAL BUILDING CODE AND FROM THE
<br /> Owner: ROIC WASHINGTON LLC INVOLVED.INCLUDE IN THE COST OF MECHANICAL WORK, AMERICAN SOCIETY OF CIVIL ENGINEERS(ASCE)STANDARD
<br /> A Date: 7/3/2023 CUTTING,CORING,PATCHING AND PAINTING OF EXISTING
<br /> PP RECTANGULAR DUCT UP WALLS,CEILINGS,FLOORS AND ROOFS AS REQUIRED TO 7-10.THE CONTRACTOR SHALL REFER TO THE ABOVE FOR
<br /> Des cription: Repair Fire Damaged Storefront Like ACCOMMODATE WORK AS INDICATED IN THE MECHANICAL ADDITIONAL INFORMATION,EXCEPTIONS,AND FURTHER
<br /> For Like 2 Hvac Units RECTANGULAR DUCT DOWN CONTRACT DOCUMENTS,UNLESS SPECIFICALLY SHOWN ON DESCRIPTIONS.THE CONTRACTOR SHALL ADHERE TO
<br /> ARCHITECTURAL DRAWINGS. REQUIREMENTS AND AS SUCH,SHALL BE INCLUDED WITHIN
<br /> BID.
<br /> (� ROUND DUCT UP 10.PROVIDE ELASTOMERIC FOAM MATERIAL ON MECHANICAL 2. 20121BC 1613.1 SCOPE:ARCHITECTURAL,MECHANICAL,
<br /> EQUIPMENT THAT PRESENT A SAFETY HAZARD. ELECTRICAL,AND NON-STRUCTURAL COMPONENTS THAT
<br /> ® ROUND DUCT DOWN 11.THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE ARE PERMANENTLY ATTACHED TO STRUCTURES AND THEIR
<br /> SAFEKEEPING OF HIS OWN PROPERTY ON THE JOB SITE. SUPPORTS AND ATTACHMENTS SHALL BE DESIGNED AND
<br /> OWNER ASSUMES NO RESPONSIBILITY FOR PROTECTION OF CONSTRUCTED TO RESIST THE EFFECTS OF EARTHQUAKE
<br /> FLEXIBLE DUCTWORK PROPERTIES AGAINST FIRE,THEFT AND ENVIRONMENTAL MOTIONS IN ACCORDANCE WITH ASCE 7-10,EXCLUDING
<br /> City of Everett Permit Review CONDITIONS. CHAPTER 14 AND APPENDIX 11A.
<br /> EVERETT Status:Approved 12.CLEAN THE JOB SITE DAILY AND REMOVE FROM THE 3. 20121BC 1705.11 CONTRACTOR RESPONSIBILITY:THE
<br /> PREMISES ANY DIRT AND DEBRIS CAUSE BY THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN
<br /> 06/07/2024 2:24:47 PM PERFORMANCE OF THE WORK INCLUDED IN THIS CONTRACT. AND CONSTRUCTION OF A SEISMIC-FORCE-RESISTING
<br /> BEFORE SUBSTANTIAL COMPLETION,CLEAN EQUIPMENT, SYSTEM,DESIGNATED SEISMIC SYSTEM,OR
<br /> SUBJECTINSPECTION LD PACKAGED ROOFTOP HEAT PUMP UNIT SCHEDULE
<br /> TAG MANUFACTURER/MODEL SUPPLY FAN HEATING COOLING ELECTRICAL FILTER DIMENSIONS WEIGHT NOTES
<br /> APPROVED FLOW ESP SPEED MOTOR CAPACITY EAT LAT AMBIENT COP TOTAL SENSIBLE EAT LAT AMBIENT SEER MCA MOP VOLTAGE/ (LXWXHT) !�
<br /> Office of Community,Planning&Economic Development TEMP CAPACITY CAPACITY DB/WB DB/WB TEMP PHASE L�9A
<br /> PLANNING DEPARTMENT CFM N WC RPM BHP MBH F F F MBH MBH °F °F °F AMPS AMPS V/0 #-WXHxD INANAN LBS q
<br /> NAME: Jessica Jarvi RTU-1 CARRIER/50GCQM05A2A5-OAOAO 1600 0.6 1780 0.61 46 70 96 47 3.7 49 37 80/87 58/57 95 16.2 51 60 20813 4-i6zi6x2 74x46x41 725 1,2,3 AO.�P Boa�(f
<br /> DATE: 06/14/2024 RTU-2 CARRIER I50FCQA04A2A5-OAOAO 1200 0.6 1718 0.37 34 70 96 23 3.7 37 28 80/67 58/57 95 14.3 5.1 35 20813 2-16x25x2 74x46x33 592 1,2,3 ^,��S7ONS5TT�£.
<br /> NOTES:
<br /> 1)PROVIDE WITH FACTORY STANDARD ROOF CURB. 1,�
<br /> 2)PROVIDE WITH ULTRA LOW LEAK ECONOMISER. COI ITI„IPOIIYT PLAZA
<br /> 3)PROVIDE WITH ELECTRIC HEATER FOR SECONDARY HEATING. J lJ
<br /> SUITE 1 -REPAIR
<br /> EXHAUST FAN SCHEDULE 10203 EVERGREEN WAY,
<br /> TAG AREA EQUIPMENT LOCATION MANUFACTURER/MODEL FAN MOTOR DRIVE DIMENSIONS WEIGHT NOTES EVERETT,WA,98204
<br /> SERVED FLOW ESP SPEED POWER VOLTAGE/PHASE TYPE (LXWXHT)
<br /> CFM IN WC RPM W /0 INANAN LBS ISSUED/REVISED DATE
<br /> EF-1 PUBLIC RESTROOM-MEN'S CEILING COOK/GC-124 1 70 0.15 900 50 1 120/1 DIRECT 1406 13 -
<br /> PERMITSET 06.26.23
<br /> SUMP PUMP DELETE 10.27.23
<br /> PR 01-SOCCER POST 01.26.24
<br /> DIFFUSER AND GRILLE SCHEDULE
<br /> TAG MANUFACTURER/MODEL TYPE MATERIAL FINISH FACE FACE DUCT MOUNTING PATTERN DAMPERS ACCESSORIES NOTES
<br /> NOTE 6 STYLE SIZE INLET
<br /> s PRICE/520RS SUPPLY GRILLE ST WHITE - NOTE 2 NOTE 3 NOTE 4 FA OPD - 5
<br /> R PRICE/530RL RETURN/EXHAUST GRILLE ST WHITE - NOTE 2 NOTE 3 NOTE 4 - NONE - -
<br /> NOTES:
<br /> 1)SEE DRAWINGS FOR FACE SIZE(24x24 OR 12x12).PROVIDE 24x24 FOR LAY IN CEILINGS.
<br /> 2)FACE SIZE DETERMINED FROM DUCT INLET SIZE.
<br /> 3)SEE AIR DEVICE TAG FOR DUCT INLET SIZE. PR•01 SOCCER POST 01.26.24
<br /> 4)COORDINATE BORDER TYPE(SURFACE MOUNT,SNAP IN,LAY-IN,SPLINE,DROPPED FACE,AND BEVELED DROP FACE)WITH ARCHITECTURAL CEILING PLANS.
<br /> 5)PROVIDE WITH FIELD ADJUSTABLE VERTICAL TO HORIZONTAL DISCHARGE PATTERN.
<br /> 6)PROVIDE ALUMINUM DIFFUSERS,REGISTERS AND GRILLES IN KITCHENS,LOCKER ROOMS,ROOMS CONTAINING SHOWERS AND OTHER AREAS SUBJECT TO MOISTURE. HVAC
<br /> C
<br /> ABBREVIATIONS: LEGEND,
<br /> ST=STEEL,AL=ALUMINUM,BE=BAKED ENAMEL,AA=ANODIZED ALUMINUM,FA=FULLY ADJUSTABLE,TP=TWO POSITION,QED=OPPOSED BLADE DAMPERS,ADJ=ADJUSTABLE,BA=BAKED ACRYLIC,
<br /> BO=BLANK OFF,DB=DIRECTIONAL BLADES,AND P=PLENUM. SCHEDULE
<br /> M0.1