Laserfiche WebLink
PACKAGE ROOFTOP HEAT PUMP UNIT SCHEDULE VICINITY MAP <br /> UNIT NOM COOLING-MBH IEER/SEER HEAT-MBH OSA FAN AUX.HEAT ELECTRICAL SOUND WT <br /> NO. MFG&MODEL NO TONS TOTAL SENS. /EER MBH HSPF/COP CFM CFM ESP HP KW STAGES VOLTAGE MCA MOCP Db(a) LBS NOTES 00.) <br /> HP-3 TRANE 4WCZ6048B3000A 4 47.5 39.0 /16.0/12.0 42.0 8.5/3.8 1575 315 0.6 0.75 7.5 1 208-3-60 26 30 72 571 1,2,3,4,5,6 O o <br /> NOTES: � <br /> 1. TWO-STAGE COOLING. 4. PROVIDE ECONOMIZER W/LOW-LEAK DAMPERS WITH BAROMETRIC RELIEF. <br /> Soundbite Cider 4)© ®Everett Moder s�" <br /> 2. 2 SPEED INDOOR FAN CONTROLLED BY VFD. 5. RECONNECT TO EXISTING LOW VOLTAGE WIRING,ELECTRICAL DISCONNECT. ® 00 c <br /> 3. UNIT MEETS THE REQUIREMENTS OF C403.3.2(2). 6. WEIGHT INCLUDES ECONOMIZER. F"tF obv Is <br /> NOTES SCOPE OF WORK ® , <br /> 1. SEAL DUCTS PER 2018 W.S.E.C. SECTION C403.10.1.2. REPLACE 1 EXISTING PACKAGED ROOFTOP ® �/ <br /> 2. INSULATE DUCTWORK PER 2018 W.S.E.Q. SECTION C403.10.1 TABLE C403.10.1.1. UNIT WITH NEW IN THE SAME PLACE, 7raderJoe's Basil Authentic <br /> 9 Vietnamese Cuisine C CI <br /> 3. PROVIDE ECONOMIZER REQUIRED PER 2018 W.S.E.C. SECTION C403.5. <br /> 4. A 125-VOLT, SINGLE-PHASE, RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE <br /> LOCATION WITHIN 25 FT OF THE EQUIPMENT AS SPECIFIED IN 2020 NEC 210.63. Hantle Atm <br /> Carpet Liquidatorsit—V / e W <br /> 5. ROOF ACCESS TO EQUIPMENT TO COMPLY WITH 2O18 I.M.C. SECTION 306.5. <br /> FI°°rirg st°,e ® � <br /> 6. AIR INTAKE INLET SHALL BE LOCATED NOT LESS THAN 10 FEET HORIZONTALLY FROM EXHAUST S 99 <br /> / Keller Williams <br /> OUTLET, AND NOT LESS THAN 3 FEET BELOW EXHAUST OUTLET 2018 I.M.C. SECTION 401 A. >® BiggFoot Java Realty Everett <br /> ri / Keller Wlllla <br /> 7, THERMOSTAT PLACEMENT TO BE NO HIGHER THAN 48°AFF ADA 308.3. m RedftyEvef� <br /> o I Everett QPlatz Group-Keller <br /> a ®Applebee's Grill.Bar Williams Realty <br /> ABBREVIATIONS LEGEND <br /> (E) EXISTING DEMO EXISTING GIRD, EQUIPMENT, DUCTWORK, ELECTRICAL WIRE �� <br /> EXH EXHAUST Col e <br /> Beauty <br /> V <br /> D INSIDE DIMENSION NEW GIRD, EQUIPMENT, DUCTWORK, ELECTRICAL WIRE college <br /> IMC INTERNATIONAL MECHANICAL CODE <br /> OC ON CENTER EXISTING GRID, EQUIPMENT, DUCTWORK, ELECTRICAL WIRE OSA OUT SIDE AIR BUILDING INFORMATION <br /> PT PRESSURE TREATED <br /> PARCEL NUMBER: 28051800300400 z <br /> RA RETURN AIR 2 <br /> RTU ROOFTOP UNIT LEGAL DESCRIPTION: SEC 18 TWP 28 RGE 05RT-9B-12A) BEG SW CDR SEC 18 TH N 372. <br /> SA SUPPLY AIR 87FT TO NLY LN BDWY CUT-OFF TH NELY ALG N LN BDWY CUTOFF LU <br /> TYP TYPICAL 2015.66FT TO TPB TH CONT ALG N LN SO HWY 362.96FT TH N20*45 <br /> W/ WITH 40W 50 FT TH N69*1420E 86,77 FT TH N 411,61 FT TH W 403.74 FT <br /> WSEC WASHINGTON STATE ENERGY CODE TH S00*05 14E 617.78 FT TO TPB. <br /> LOT SIZE: 4.92 ACRES <br /> ZONING: MU <br /> OCCUPANCY TYPE: RETAIL <br /> OWNER: 909 BUSINESS CENTER LLC <br /> 2010 156TH AVE NE STE 100 <br /> BELLEVUE, WA 98007 5 <br /> N <br /> v <br /> N <br /> C � <br /> E O <br /> R <br /> sz a <br /> Cr <br /> LU v) LU <br /> BLDG.B <br /> BLDG.A <br /> BLDG.C M T <br /> R <br /> ; 00 <br /> LU c-4 <br /> f� r 00 <br /> fC <br /> 62'-5F" 330'-7j% y V Q <br /> BLDG <br /> HP-3 .E HP-3 .� M <br /> BLDG.D -- I O� <br /> fn <br /> s., M (D <br /> + ---� -- -- — -- -- — -- -- — -- -- — -- -- — -- -- — -- — — -- O > <br /> ROOF ———— LU <br /> DATE: 06-07-2023 <br /> r day <br /> DRAWN: VTD <br /> I 1 <br /> y ENGR: <br /> oo <br /> Vp�ej APPVD: <br /> JOB NUMBER: <br /> 118774 <br /> SITE PLAN 00 SOUTH ELEVATION <br /> SCA[E: 1/64"= P-0" a D SCALE:3/16"= 1'-0" M 2.O <br /> 1 OF 1 <br />