VIBRATION ISOLATION / SEISMIC SCHEDULE LAST UPDATED: 091824 <br /> UNIT BASIS OF DEFL BASE SEISMIC H e r m a n s o n <br /> TAG SERVES DESIGN 3 INCH TYPE RESTRAINT REMARKS <br /> NA I WALL MOUNTED HEAT PUMPS 4 10 15 Building Today,Defining Tomorrow <br /> NA DUCTWORK CABLE RESTRAINT 5,8,15 <br /> GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS(ELECTRICAL,WEIGHT,SIZE,ETC-)WITH APPROVED SUBMITTALS Hermanson Company LLP <br /> PRIOR TO INSTALLATION;FIELD COORDINATE FINAL LOCATION&INSTALL PER MANUFACTURERS REQUIREMENTS 1221 2nd Avenue North <br /> NOTE: CTB=COOLING TOWER BASE,CIE=CONCRETE INERTIA BASE Kent,Washington 98032 <br /> 4 INTERNAL ISOLATION PROVIDED INTEGRAL WITH UNIT Tel: (206)575-9700 <br /> 5 PROVIDE FLEXIBLE HOSES FOR PIPING CONNECTIONS AT UNIT Fax:(206)575-9800 <br /> 8 CONFIRM EQUIPMENT RPM,REFER TO"REQUIRED DEFLECTION BASED ON RPM"SPREADSHEET TO DETEREMINE PROPER DEFLECTION www.hermanson.com <br /> 10 SEISMIC RESTRAINT AS REQUIRED BY CODE AND/OR LOCAL AUTHORITY HAVING JURISDICTION OR PER SMACNA GUIDELINES* Contractor Reg g:HERMACLO05BJ <br /> *SUSPENDED EQUIP WITH IP=1.0 AND>20LBS REQUIRES SEISMIC BRACING-IF THE COMPONENT/EQUIPMENT IS RIGIDLY ATTACHED TO THE DUCT AND THE DUCT IS BRACED,THEN NO ADDITIONAL <br /> SEISMIC IS REQ'D.COMPONENTS/EQUIP>75LBS REQUIRE INDEPENDENT VERTICAL SUPPORTS AND SEISMIC BRACING.EQUIP WITH IP=1.5 AND<20LBS AND FLEXIBLY CONNECTED MAY BE OMITTED <br /> 15 DEFLECTION AS REQUIRED PER ASHRAE APPLICATIONS,CHAPTER 49 BASED ON STRUCTURE ITEM WILL BE SUPPORTED FROM(VERIFY PRIOR TO ORDER)OR AS PER APPROVED BY DESIGN ENGINEER <br /> PIPING MATERIAL SCHEDULE LAST UPDATED: 31621 LITHIUM <br /> PIPE SERVICE LOCATION I MATERIAL JOINT METHODS REMARKS <br /> COILCONDENSATE LAB <br /> ABOVE GROUND PVC SCH 40 SOLVENT CEMENTED IF NOT IN A RA PLENUM,SOLID CORE(NOT FOAM) <br /> ,_ABOVE GROUND ........ COPPER(DWV) SOLDER _ <br /> ABOVEGROUND COPPER(L OR M) PRESSFIT(52"),SOLDER(->2 <br /> 1 2" ZAP ENERGY <br /> REFRIGERANT 5901 23RD DR. W. <br /> ALL COPPER(ACR) BRAZED,PRESSFIT(MAXIPRO, PROVIDE NITROGEN PURGE IF BRAZED EVERETT, WA 98203 <br /> ZOOMLOCK OR UAL <br /> ALL PRE-INSULATED COPPER LINE SETS BRAZOOZED,ML PRESSFKIT(MAXIPRO, <br /> O C OR UAL PROVIDE NITROGEN PURGE IF BRAZED <br /> ALL PRE-INSULATED PE COMPOSITE FLEX BRAZED,PRESSFIT(MAXIPRO, IF NOT IN A RA PLENUM <br /> PIPE WITH ALUM CORE ZOOMLOCK OR UAL) <br /> 304 BRAIDED STAINLESS STEEL BRAZED,PRESSFIT(MAXIPRO, <br /> ALL 580 PSI MIN WORKING PRESSURE REQUIRED <br /> WITH PTFE LINER _. ZOOMLOCK OR EQUAL) <br /> �NtoDokti <br /> NOTE: BOLD&UNDERLINE REPRESENTS THE HERMANSON CORPORATE STANDARD MATERIAL AND JOINT METHOD FOR EACH SERVICE TYPE Oe Ode��.r`''S w <br /> MINIMUM PIPE INSULATION LAST UPDATED: 04/04/24 <br /> FLUID DESIGN I INSULATION CONDUCTIVITY NOMINAL PIPE DIAMETER INCH �gc,, 3er4v9 <br /> OPERATING CONDUCTIVITY MEAN TEMP 7 1 TO 1-1/2 TO 4 TO cCsiON,U,tip' <br /> TEMP°F RANGE RATING°F <34 "1-1/2' <4 <8 >_8 Ocrober2Z 2024 <br /> HEATING SYSTEMS' STEAM CONDENSATE HYDRONIC HOT WATER <br /> >350 0.32-0.34 250 4.5 5.0 1 5.0 1 5.0 5.0 <br /> 251-350 0.29-0.32 200 3.0 4.0 4.5 4.5 4.5 <br /> 201-250 0.27-0.30 150 2.5 2.5 2.5 3.0 3.0 <br /> 141-200 0.25-0.29 125 1.5 1.5 2.0 2.0 2.0 <br /> 105-140' 0.71-0.28 100 1.07 1.07 I.5' 1.57 1.S' ISSUE FOR PERMIT <br /> DOMESTIC HOT WATER; DOMESTIC HOT WATER RECIRCULATION3 <br /> NA 0.21-0.28 1 100 1 0.5 0.75 6 1.0 1.25 6 1.5 2.0 6 2.0 2.0 <br /> DOMESTIC COLD WATERS;HORIZONTAL RAIN LEADERS&CONDENSATE PIPE TO MAIN VERTICAL RISER CONDENSATION PREVENTION ONLY <br /> NA 0.21-0.27 75 0.5 0.5 0.5 0.5 0.5 Key Plan <br /> COOLING SYSTEMS' CHILLED WATER BRINE AND WATERSIDE ECONOMIZER SYSTEM <br /> SZ <br /> 40f0 0.21-0.27 75 0.5 0.5 1.0 1.0 1.0 <br /> <40 0.20-0.26 75 0.5 1.0 1.0 1.0 1.5 <br /> REFRIGERANT PIPING SEE CODE SCHEDULES FOR EXPOSED PIPE DAMAGE PROTECTION REQUIREMENTS <br /> IN COND SPACE 0.21-0.26 75 0.5 0.5 0.5 0.5 0.5 <br /> OUT COND SPACE 0.21-0.26 75 1.0 1.0 1.0 1.0 1.0 <br /> UNLINED <br /> STORAGE TANKS ALL SIZES R-12.56 <br /> NOTES: <br /> GENERAL ALL PIPING EXPOSED TO WEATHER TO BE PROTECTED FROM SUNLIGHT,MOISTURE,WIND AND MAINTENANCE DAMAGE <br /> AND SHIELDED FROM SOLAR DEGREDATION,ADHESIVE TAPES ARE NOT ALLOWED <br /> 1 NOT REQUIRED FOR STRAINERS,CONTROL VALVES&BALANCING VALVES ASSOCIATED WITH PIPING 1"OR LESS IN DIA. <br /> 2 TYPICAL CONDENSER WATER PIPE IN NON-ECONOMIZER SYSTEMS IS NOT INSULATED <br /> 3 SEE R403 FOR RESIDENTIAL INSTALLATIONS <br /> 4 FOR PIPING SMALLER THAN 1-1/2 INCH AND LOCATED IN PARTITIONS WITHIN CONDITIONED SPACES,REDUCTION OF <br /> INSULATION THICKNESSES BY 1 INCH SHALL BE PERMITTED,BUT NOT TO A THICKNESS OF LESS THAN 1 INCH <br /> 5 DOMESTIC HOT WATER PIPE INSULATION SHALL HAVE A MINIMUM WALL THICKNESS OF NOT LESS THAN THE DIAMETER <br /> OF THE PIPE FOR PIPE UP TO 2 INCHES IN DIAMETER.INSULATION WALL THICKNESS SHALL NOT BE LESS THAN 2 INCHES <br /> FOR A PIPE OF 2 INCHES OR MORE IN DIAMETER.NOTE THAT THIS IS PER UPC SECTION 609.11.2.IN JURISDICTIONS <br /> THAT REQUIRE DOMESTIC HOT WATER PIPING TO BE INSULATED PER THE ENERGY CODE,USE THE 105-140 ROW <br /> FROM HEATING SYSTEMS ABOVE. <br /> 6 UNFIRED TANKS USED TO STORE WATER AT TEMPERATURES ABOVE 130T SHALL INCLUDE A MINIMUM OF R-2 Revisions <br /> ADDITIONAL INSULATION FOR EVERY 10T INCREASE IN STORED WATER TEMPERATURE OVER 130'F. <br /> 7 FOR HEATED WATER CIRCULATION SYSTEMS,BOTH SUPPLY AND RETURN PIPE INSULATION SHALL BE AT MINIMUM <br /> 1 INCH THICKER THAN ROW 105-140 FROM HEATING SYSTEMS,ABOVE,EXCEPT WHERE PIPING IS CENTERED WITHIN <br /> A FRAMING CAVITY 4"DEEPER THAN THE PIPE DIAMETER THAT IS COMPLETELY FILLED WITH BATT OR <br /> BLOWN-IN INSULATION. <br /> MINIMUM DUCT INSULATION LAST UPDATED 05/02/24 - <br /> INSULATION <br /> DUCT SYSTEM DUCT LOCATION AND USE R-VALUE REMARKS - <br /> CLIMATE ZONE 4C <br /> SUPPLY AIR OR OUTSIDE THE BUIDING(OUTDOORS AND EXPOSED TO WEATHER) R-8 1 <br /> RETURN AIR <br /> SUPPLY AIR OR UNCONDITIONED SPACE(ENCLOSED BUT NOT IN THE BUILDING CONDITIONED R-6 1 <br /> RETURN AIR ENVELOPE <br /> SUPPLY AIR OR UNCONDITIONED SPACE(DUCT CONVEYS AIR THAT IS WITHIN 15"F OF THE AIR <br /> R-3.3 2 <br /> RETURN AIR TEMPERATURE OF THE SURROUNDING UNCONDITIONED SPACE) <br /> SUPPLY AIR OR IN A BUILDING ENVELOPE ASSEMBLY <br /> R-16 3 <br /> RETURN AIR <br /> WITHIN CONDITIONED SPACE(SUPPLY DUCT CONVEYS AIR THAT IS LESS THAN 55-F R-3.3 1 <br /> SUPPLY AIR OR GREATER THAN 105° 10/25/24 BDG ISSUE FOR PERMIT <br /> WITHIN CONDITIONED SPACE THAT THE DUCT DIRECTLY SERVES AND WITHIN VIEW - <br /> SUPPLY AIR (SUPPLY DUCT CONVEYS AIR THAT IS LESS THAN 55•F OR GREATER THAN 105°F) NONE 1 No. Date By Description <br /> WITHIN CONDITIONED SPACE(SUPPLY DUCT CONVEYS AIR THAT IS 55•F OR NONE 1 <br /> SUPPLY AIR GREATER AND 105°F OR LESS <br /> RETURN OR WITHIN CONDITIONED SPACE,DOWNSTREAM OF AN ENERGY RECOVERY MEDIA, R-s - Design Team <br /> EXHAUST AIR UPSTREAM OF AN AUTOMATIC SHUT OFF DAMPER <br /> RELIEF OR WITHIN CONDITIONED SPACE AND DOWNSTREAM OF AN AUTOMATIC SHUT OFF R-16 - Design BDG <br /> EXHAUST AIR DAMPER <br /> OUTSIDE AIR INSIDE CONDITIONED SPACE AND UPSTREAM OF AN AUTOMATIC >2800 CFM R-16 4 Drawn FVP <br /> SHUT OFF DAMPER <br /> OUTSIDE AIR INSIDE CONDITIONED SPACE AND DOWNSTREAM OF AN AUTOMATIC i 2800 CFM R-8 Checked DTN <br /> SHUT OFF DAMPER TO HVAC UNIT OR ROOM <br /> OUTSIDE AIR INSIDE CONDITIONED SPACE <2800 CFM R-7 5 Pre-Construction Number 21-24-27429 <br /> Construction Number <br /> NOTES: <br /> 1 SEE ENERGY CODE SECTION C403.10.1.2 FOR DETAILS Issue Date 10/25/24 <br /> 2 SEE IMC SECTION 603.12 FOR ADDITIONAL REQUIREMENTS FOR CONDENSATION CONTROL AT DUCTWORK <br /> 3 DUCT OR PLENUM IS SEPARATED FROM BUILDING ENVELOPE ASSEMBLY WITH THE MINIMUM INSULATION VALUE <br /> 4 SEE ENERGY CODE SECTION C403.10.1.1 FOR ADDITIONAL REQUIREMENTS <br /> 5 SEE EXCEPTION 1 TO SECTION C403.10.1.1 FOR ADDITIONAL DETAILS <br /> CONSTRUCTION <br /> STANDARDS <br /> - HVAC <br /> FOR CITY USE: <br /> M0.01 <br /> L City of Everett Permit Services <br /> EVERETT Reviewed for Permit 12/19/2024 <br />