PACKAGED ROOFTOP AC UNIT SCHEDULE - DEMO UNIT UPDATED: 04/20/23 <br /> HEATER <br /> UNIT AREA BASIS OF SUPPLY OSA ESP IT COOLING CAPACITY SUPPLY FAN ELEC WEIGHT <br /> TAG LOCATION SERVED DESIGN CFM CFM IN WG DBIF I TOTAL MBH I SENS.MBH KW) QTY I RPM BHP SEER MCA V PH LES REMARKS <br /> AC-2 ROOF E IP.RN TRANE TM O60 2,400 0.40 55 59.0 57.0 6 CENTR 1 850 0.8 10 1 1 460 3 600 1 REMARKS: H e r m a n s o n <br /> 1 DEMO EXISTING UNIT <br /> Building Today,Defining Tomorrow <br /> PACKAGED ROOFTOP AC UNIT SCHEDULE - REPLACEMENT UNIT UPDATED: 05/23/23 Hem anson Company LLP <br /> 1221 2nd Avenue North <br /> HEATER Kent,Washington 98032 <br /> UNIT AREA BASIS OF SUPPLY MIN OSA ESP SAT COOLING CAPACITY SUPPLY FAN ELEC WEIGHT Tel:(206)575-9700 <br /> TAG LOCATION SERVED DESIGN CFM CFM IN WG DB OF TOTAL MBH I SENS.MBH KW TYPE QTY I RPM BHP HP SEER/EER MCA V/PH LBS REMARKS Fax:(206)575-9800 <br /> AC-2 ROOF EQUIP.ROOM TRANE THC067E4RI 2,000 NA 0.50 55 58.0 43.3 CENTR 1 922 0.7 1 17.2 13 1 15 46013 915 1-15 www.hennanson.com <br /> GENERAL: ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS(ELECTRICAL,WEIGHT,SIZE,ETC...)WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION;FIELD COORDINATE FINAL LOCATION&INSTALL PER MANUFACTURERS REQUIREMENTS Contractor Reg#:HDRMACLO05B1 <br /> UNIT CAPACITY RATED AT 85/67 OUTSIDE AIR DESIGN TEMPERATURES <br /> REMARKS: <br /> 1 ELECTRICAL CONTRACTOR TO PROVIDE SCCR PROTECTION DIRECTION FOR EQUIPMENT AS REQUIRED BY LATEST APPROVED VERISON OF THE NATIONAL ELECTRICAL CODE,PRIOR TO ORDER. <br /> MANUFACTURER TO PROVIDE SCCR LISTING(5 KAIC MINIMUM OR PER ELECTRICAL CONTRACTOR CALCULATION)INSIDE CONTROL PANEL AS REQUIRED BY NATIONAL ELECTRICAL CODE. <br /> 2 PROVIDE DOWNFLOW ENTHLAPHY ECONOMIZER WITH BAROMETRIC RELIEF SYSTEM <br /> 3 ECONOMIZER SHALL BE CAPABLE OF PROVIDING PARTIAL COOLING IN ADDITION TO MECHANICAL COOLING AS REQUIRED TO MEET THE REMAINDER OF THE LOAD PER ENERGY CODE SECTION C403.5.1 <br /> 4 MINIMUM UNIT EFFICIENCY TO MEET THE ENERGY CODE TABLE C403.3.2(2) <br /> 5 NOT USED om <br /> 6 NOT USED <br /> 7 REUSE EXISTING SMOKE DETECTORS,PROVIDED REPLACEMENT IF NEEDED (BY MECHANICAL)AND INSTALLED(BY ELECTRICAL)IN THE RETURN AIR. EVERETT <br /> 8 PROVIDE WITH MERV 8 FILTERS NEIGHBORHOOD FINANCIAL CENTER <br /> 9 REPLACEMENT UNIT TO BE INSTALLED ON EXISTING ROOF CURB USING CURB ADAPTOR 11127 EVERGREEN WAY <br /> 10 RECONNECT TO EXISTING CONTROLS,ADJUST OR REPLACE AS NEEDED EVERETT,WA 98204 <br /> 11 RECONNECT TO EXISTING DUCTWORK AND BALANCE TO EXISTING COOLING CAPACITY <br /> 12 HEATING&COOLING FANS/PUMPS SHALL SHUT OFF WHEN THERE IS NO CALL FOR HEATING AND COOLING IN THE ZONE PER WSEC 2018 C403.3.5.2,EXCEPT IF HEATING/COOLING FANS<0.12W/CFM <br /> 13 PROVIDE VARIABLE SPEED FAN CONTROL FOR SUPPLY FANS>5 TONS(<66%OF DESIGN SPEED AT LOW SPEED SETTING MAXIMUM)PER ENERGY CODE C403.2.11.5 <br /> 14 IF>5 TONS&ECONOMIZER PROVIDED,UNIT TO INCLUDE TWO STAGE MIN COOLING(3 STAGE IF BETWEEN 5&20 TONS,4 STAGE FOR>20 TONS)AS DEFINED BY ENERGY CODE C403.3.1.2 �NEODO11 <br /> 15 SEE STRUCTURAL CALCULATIONS FOR MOUNTING DETAILS Q�,Q�OF WASy7�F'Y�'2 <br /> 61SIE1�+O� <br /> ONAL C <br /> May 25,2023 <br /> ISSUE FOR PERMIT <br /> Revisions <br /> _05/23/23 MG ISSUE FOR PERMIT <br /> No. Date By Description <br /> Design Team <br /> Design MG <br /> Drawn FVP <br /> Checked DTN <br /> Pre—Construction Number 15-23-23919 <br /> Construction Number <br /> Issue Date 05/23/23 <br /> SCHEDULE <br /> SHEET <br /> - HVAC <br /> FOR CITY USE: <br /> M0 .02 <br />