VIBRATION ISOLATION/ SEISMIC SCHEDULE LAST UPDATED: 042023 DUCT CONSTRUCTIONSTANDARDS STANDARD INSERT METHODS <br /> UNIT BASIS DER BASE SEISMIC <br /> TAG SERVES DESIGN° INCH TYPE RESTRAINT REMARKS NEW AND EXISTING CONDITIONS <br /> NA ROOFTOP UNITS(SMALL,MFG CURB - - SCREW TO CURB 2 4 10 <br /> NA DUCTWORK - - CABLE RESTRAINT 5815 . .: - 0 <br /> GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS(ELECTRICAL,WEIGHT,SIZE,ETC...)WITH APPROVED SUBMITTALS HARDWARE REQUIRED HARDWARE REQUIRED HARDWARE REQUIRED HARDWARE REQUIRED H e r m a n s o n <br /> BANGER INSERT MINI-UNDERCUT INSERT BANGER INSERT WEDGE ANCHOR BOLT <br /> PRIOR TO INSTALLATION;FIELD COORDINATE FINAL LOCATION&INSTALL PER MANUFACTURERS REQUIREMENTS •CABLE WITH 90'EYELET END •CABLE WITH UT EYELET END •THREADED ROD •NUT AND ROD COUPLING <br /> NOTE: CTB=COOLING TOWER BASE,CIB=CONCRETE INERTIA BASE •BOLT AND WASHER •BOLT AND WASHER •THREADED ROD Building Today,Defining Tomorrow <br /> 1 OR EQUAL ISOLATION(ISAT,MASON,VIBRACOUSTICS OR AS APPROVED),CONFIRM INSTALL METHOD WITH FIELD PRIOR TO ORDER <br /> 2 SEISMIC RATED CURB ISOLATOR <br /> 3 USE HEIGHT SAVING BRACKETS FOR SPRING ISOLATORS Hermanson Company LLP <br /> 4 INTERNAL ISOLATION PROVIDED INTEGRAL WITH UNIT 1221 2nd Avenue North <br /> 5 PROVIDE FLEXIBLE HOSES FOR PIPING CONNECTIONS AT UNIT - Kent,Washington 98032 <br /> 6 WHERE DESIGNATED AS REQUIRED BY DESIGN ENGINEER BASED ON UNIT MOUNTING LOCATION IN ACOUSTICALLY/VIBRATIONALLY SENSATIVE AREAS _ Tel:(206)575-9700 <br /> 7 LAG BOLT(WOOD)OR WEDGE ANCHOR(CONCRETE)TO CONCRETE PAD WITH NEOPRENE GROMMET IF NON-SEISMIC RATED ISOLATOR USED •�1 '` -} Fax:(206)575-9800 <br /> 8 CONFIRM EQUIPMENT RPM,REFER TO"REQUIRED DEFLECTION BASED ON RPM"SPREADSHEET TO DETEREMINE PROPER DEFLECTION _,Y I I www.herm neon.com <br /> 9 THREE SPRING HANGERS FROM ROTATING EQUIPMENT CONNECTIONS 444111 Contractor Reg/:HERMACLO05BJ <br /> 10 SEISMIC RESTRAINT AS REQUIRED BY CODE AND/OR LOCAL AUTHORITY HAVING JURISDICTION OR PER SMACNA GUIDELINES <br /> *SUSPENDED EQUIP WITH IP=1.0 AND>20LBS REQUIRES SEISMIC BRACING-IF THE COMPONENT/EQUIPMENT IS RIGIDLY ATTACHED TO THE DUCT AND THE DUCT IS BRACED,THEN NO ADDITIONAL <br /> SEISMIC IS REQ'D.COMPONENTS/EQUIP>75LBS REQUIRE INDEPENDENT VERTICAL SUPPORTS AND SEISMIC BRACING.EQUIP WITH IP=1.5 AND<20LBS AND FLEXIBLY CONNECTED MAYBE OMITTED <br /> 11 FLOOR STAND PROVIDED BY MECHANICAL CONTRACTOR HARDWARE REQUIRED HARDWARE REQUIRED HARDWARE REQUIRED HARDWARE REQUIRED <br /> 12 4"MINIMUM(CONFIRM WITH STRUCTURAL ENGINEER BASED ON EQUIPMENT WEIGHT AND EMBED ANCHOR DEPTH REQD)CONCRETE HOUSEKEEPING PAD INSTALLED UNDER UNIT BY GC •CABLE WITH REBAR OR •WEDGE ANCHOR BOLT W•DEWALT 109 INSERT • EDGE ANCHOR BOLT <br /> 13 FOR UNITS THAT ARE GREATER THAN 2 HP IN SIZE TOGGLE END •CABLE W T T <br /> ITH 90'EYELET END .ROD COUPLING AND NUT •NUT AND ROD COUPLING . <br /> ♦ • • <br /> 14 PROVIDE 1.5X5 UNIT WEIGHT IN CONCRETE BELOW UNIT AND MAXIMUM OF 1/8"DEFLECTION ACROSS LENGTH OF UNIT BY GC NUT AND WASHER HREADED ROD HREADED ROD <br /> 15 DEFLECTION AS REQUIRED PER ASHRAE APPLICATIONS,CHAPTER 48 BASED ON STRUCTURE ITEM WILL BE SUPPORTED FROM(VERIFY PRIOR TO ORDER) <br /> 16 COMPONENT IMPORTANCE FACTOR(Ip=1.5) <br /> MINIMUM DUCT INSULATION LAST UPDATED ° — T <br /> OS/03/21 — � NEIGHB NEIGHBORHOOD FINANCIAL CENTER <br /> INSULATION �����•]]] J �--/ 11127 EVERGREEN WAY <br /> DUCT SYSTEM DUCT LOCATION AND USE R-VALUE REMARKS EVERETT,WA 98204 <br /> CLIMATE ZONE 4C <br /> SUPPLY AIR OR OUTSIDE THE BUIDING(OUTDOORS AND EXPOSED TO WEATHER) R-8 1 <br /> RETURN AIR <br /> SUPPLY AIR OR UNCONDITIONED SPACE(ENCLOSED BUT NOT IN THE BUILDING CONDITIONED R-6 1 <br /> RETURN AIR ENVELOPE HARDWARE REQUIRED HARDWARE REQUIRED HARDWARE REQUIRED HARDWARE REQUIRED NEODOR <br /> SUPPLY AIR OR UNCONDITIONED SPACE(DUCT CONVEYS AIR THAT IS WITHIN 15-F OF THE AIR ♦BEAM CLAMP ♦CABLE WITH LOOP END •SEAM CLAMP •BEAM CLAMP ,Q'SU WASy,N�. <br /> RETURN AIR TEMPERATURE OF THE SURROUNDING UNCONDITIONED SPACE) R-3.3 2 •CABLE WITH SO'EYELET END .THRE4OED ROD THREADED ROD ♦ Y 'Y <br /> SUPPLY AIR OR IN A BUILDING ENVELOPE ASSEMBLY R-16 3 BOLT AND WASHER .NUT NUT <br /> RETURN AIR <br /> WITHIN CONDITIONED SPACE(SUPPLY DUCT CONVEYS AIR THAT IS LESS THAN 55-F R-3.3 1 <br /> SUPPLY AIR ORGREATERTHAN 1050 •;P ,p��bl � <br /> SUPPLY AIR WITHIN CONDITIONED SPACE THAT THE DUCT DIRECTLY SERVES SUPPLY DUCT NONE 1 <br /> WITHIN CONDITIONED SPACE(SUPPLY DUCT CONVEYS AIR THAT IS 55-F OR NONE l ONAL <br /> SUPPLY AIR GREATER AND 105-F OR LESS LI May 25,2023 <br /> RETURN OR WITHIN CONDITIONED SPACE,DOWNSTREAM OF AN ENERGY RECOVERY MEDIA, R-8 _ <br /> EXHAUST AIR UPSTREAM OF AN AUTOMATIC SHUT OFF DAMPER <br /> RELIEF OR WITHIN CONDITIONED SPACE AND DOWNSTREAM OF AN AUTOMATIC SHUT OFF R-16 OUTSIDE AIR <br /> DAMPER ISSUE FOR PERMIT <br /> OUTSIDE AIR INSIDE CONDITIONED SPACE OOFDDAM ER M OF AN AITOMATIC z 2800 CFM R-16 4 <br /> OUTSIDE AIR INSIDE CONDITIONED SPACE AND DOWNSTREAM OF AN AUTOMATIC z 2800 CFM R-8 <br /> SHUT OFF DAMPER TO HVAC UNIT OR ROOM <br /> OUTSIDE AIR INSIDE CONDITIONED SPACE <2800 CFM R-7 5 Revisions <br /> NOTES: B • • STANDARDS DUCTWORK HANGER REQUIREMENTS <br /> 1 SEE ENERGY CODE SECTION C403.10.1.2 FOR DETAILS ROUND, OVAL AND RECTANGULAR WermansI <br /> 2 SEE IMC SECTION 603.12 FOR ADDITIONAL REQUIREMENTS FOR CONDENSATION CONTROL AT DUCTWORK <br /> 3 DUCT OR PLENUM IS SEPARATED FROM BUILDING ENVELOPE ASSEMBLY WITH THE MINIMUM INSULATION VALUE <br /> 4 SEE ENERGY CODE SECTION C403.10.1.1 FOR ADDITIONAL REQUIREMENTS <br /> 5 SEE EXCEPTION 1 TO SECTION C403.10.1.1 FOR ADDITIONAL DETAILS <br /> RECTANGULAR DUCT RECTANGULAR DUCT RECTANGULAR DUCT RECTANGULAR DUCT RECTANGULAR DUCT RECTANGULAR DUCT RECTANGULAR DUCT <br /> IWo 510"R W+ so•1 (w.o 5loo"sw so'1 Iw.Dsgs-sW rs'1 Iw.ostxo'sw <gE"1 (w.D<+gz'aw gs") Stgx'awIw•Os tgx"sw < an'1 <br /> SUPPORTS REQUIRED SUPPORTS REQUIRED SUPPORTS REQUIRED SUPPORTS REQUIRED SUPPORTS REQUIRED SUPPORTS REQUIRED 9UPPORTS REQUIRED <br /> uo IrLAT1 .xog cneLE:sruD IrLATI .-.ALVTHREAoro Roo •..P.ALV TxREsoeo NO. .11—v TxREAD--woo .I zcAIV THREAOEO Roo i11—A-TxREA000 NO. <br /> BEARER LREQUIRED x BEARERLREOUIRED HI BEARER REQUIRED BEARER REQUIRED BEARER REQUIRED BEARER REQUIRED BEARER REQUIRED <br /> Rne TIMPEL!SRAexeT .—AHITEELAxoLE —.1-1EELAINNA <br /> LA L<1 I>< I <br /> - 1 <br /> OVAL DUCT OVAL DUCT OVAL DUCT OVAL O+um OVAL Du OVAL DUCT A <br /> Iw.o Sro-aw DD-1 Iwm s+oo-Aw ao-1 Iw.osxE"ew tR� (w.eslm-a ae� Av.osnx•a aR•T Iw.o s+gzRaw zo-1 Iw.esn «j 05/23/23 MG ISSUE FOR PERMN <br /> SUPPORTS REQUIRED S UPPORTS REQUIRED SUPPORTS REQUIRED SUPPORTS REQUIRED SUPPORTS REQUIRED SUPPORTS REQUIRED SUPPORTS REQUIRED No. Date By Description <br /> uo(`(-T1 uo I -T1 :e eaLV rxR--xoo Ie OALV THREADED Roo :z cALV THREAoso Roo �z GALV TxREAoeo Roo z oAly T. 2.Roo <br /> REL IPsx1 REL(anxl <br /> BEARER REQUIRED BEARERLREpU1RED BEARER REQUIRED BEARER REQUIRED BEARER REQUIRED BEARER REOUIREO BEARER REQUIRED <br /> •R+ooD:t s:e"uxl srsuT .,,.,ER <br /> P1oo1:1-M DO.—sTRUT .e+so+:+-s:n DousLE srxuT •g.g.+�a SiEEI .A.a.+a STEEL AxeLE <br /> Design Team <br /> Design MG <br /> Drawn FVP <br /> Checked DTN <br /> Pre-Construction Number 15-23-23919 <br /> HANGER SPACING GUIDE Construction Number <br /> INSTALL HANGERS SHOWN ON... ROUND DUCT ROUND DUCT ROUND DUCT ROUND DUCT ROUND DUCT Issue Date 05/23/23 <br /> ROUND P 1 EVERY 10 FEET (NANETER51so-) (DIAMETERS ao•1 (DIAMETERS]60.1 IDIAMETERS840.1 IDIAAN—RS_.IS ALL SEHM.0 <br /> :. .. .• ,. <br /> OVAL C 1 EVERY 08 FEET SUPPORTSREQVIRED SUPPORTS REQUIRED SUPPORTS REQUIRED SUPPORTS REQUIRED SUPPORTS REQUIRED <br /> RECT @ 1 EVERY 08 FEET uo lRumlD rT uo lrunurT .D.LV THREADED Roo aGALVTHRE-11 Roo aAw rHRuoso Roo <br /> .xo:DA.LE:.ARREL xxx 1D ET .xo:cA.LE:_EI- <br /> BEARER REQUIRED BEARER REQUIRED BEARER REQUIRED BEARER REQUIRED BEARER REQUIREA.—ONLY .12GATOPA DINDYTONISAINDLE <br /> CONSTRUCTION <br /> STANDARDS <br /> - HVAC <br /> FOR CITY USE: <br /> M0 .04 <br />