INITIATING WIRING RECORD DRAWINGS
<br /> AS-BUILT/RECORD DRAWING REQUIREMENTS: CO nve rg j nt'
<br /> SIGNATURE LOOP WIRING LIMITATIONS:
<br /> THE FOLLOWING INFORMATION SHOULD BE RECORDED ON A SEPARATE SET OF O
<br /> SIGNATURE DUAL DRIVER CONTROLLER MODULES SUPPORTS UP TO 250 DRAWINGS FOR EACH PROJECT:
<br /> INTELLIGENT SIGNATURE DETECTORS AND 250 INTELLIGENT SIGNATURE o 450 Shattuck Avenue South,Renton,Washington 98057
<br /> MODULES 1. ANY CHANGES IN THE LOCATION OF ANY ASSOCIATED FIRE ALARM OR a W o w Phone:425-272-2250 Fax:425-251-0949
<br /> WIRE LENGTH LIMITATIONS: INTERFACE EQUIPMENT.CONTROL PANELS,ANNUNCIATORS,DETECTORS, o 0-
<br /> CONTROL RELAYS,INPUT AND OUTPUT MODULES,TERMINAL CABINETS, a �" 'm 0
<br /> NON-TWISTED,NON-SHIELDED WIRE ETC. LL This document ana the Inf-eaGNdeplcanns mnWinedlshown
<br /> 16AWG-20pf/FT&4.02 OHMS 1000 FEET 2. ANY CHANGES TO CIRCUIT WIRING.THIS INCLUDES DELETION OR SEQUENCE OF OPERATIONS ¢ 0 0 o m w w is the e.dwsmePrepery OfCOT-mint Te,hnoloaies uC and shall
<br /> 18AWG-20pfIFT&6.38 OHMS/1000 FEET ADDITIONAL WIRING RUNS.ANY RE-ROUTING OF CIRCUIT WIRING.ANY -0 be handled as prepnetary and wnfidential information ana must be
<br /> DETECTORS ONLY 16AWG-125 DETECTORS-9.275' ADDITIONS OR DELETIONS TO THE NUMBER,LOCATION,AND ORDER OF a i w 3 a N retu..d upon request.This dowmenl cannot be reproduced by any
<br /> MODULES ONLY 16AWG-125 MODULES-7,921' DEVICE WIRING ON A CIRCUIT. ' ens without the wdtlen eulhodzatlon of Convergint Technologies LLC.
<br /> o
<br /> DETECTORS AND MODULES 1
<br /> 6AWG-125 OF EACH-3,608' 3. ADDRESSES AND/OR LABELS FOR ALL ADDRESSABLE DEVICES. p 'J
<br /> DETECTORS ONLY 18AWG-125 DETECTORS-5,839' 4. CANDELA SETTINGS OF ALL VISUAL NOTIFICATION DEVICES.
<br /> MODULES ONLY 18AWG-125 MODULES-4,986' 5. WATTAGE TAP SETTINGS OF ALL SPEAKER NOTIFICATION DEVICES.
<br /> DETECTORS AND MODULES 18AWG-125 OF EACH-2,271'
<br /> ANY CHANGES SHALL BE DISCUSSED WITH CONVERGINT PROJECT MANAGER
<br /> TWISTED PAIR,NON-SHIELDED WIRE TO ENSURE SYSTEM AND CODE PARAMETERS ARE MET.CONVERGINT SHALL
<br /> 16AWG-36pf/FT&4.02 OHMS/1000 FEET NOT BE HELD ACCOUNTABLE FOR CHANGES MADE WITHOUT APPROVAL.
<br /> 18AWG-25pf/FT&6.38 OHMS/1000 FEET
<br /> DETECTORS ONLY 16AWG-125 DETECTORS-9,275' THIS INFORMATION SHALL BE NEAT AND LEGIBLE WHEN PRESENTED TO THE v v v v v v V
<br /> MODULES ONLY 1GAWG-125 MODULES
<br /> -7,921' TECHNICIAN AT THE CONCLUSION OF THE PROJECT.PLEASE NOTE CONTACT ACTIVATION OF LOCAL ALARM AT UT&2120 HEADEND(LED DISP,ZONE LED&AUDIBLE IND.) X X X X A A A
<br /> DETECTORS AND MODULES 16AWG-125 OF EACH-3,608' INFORMATION ON DRAWINGS FOR INDIVIDUALS WITH FAMILIARITY OF
<br /> DETECTORS ONLY 18AWG-125 DETECTORS-5,839' INSTALLATION IN THE EVENT QUESTIONS ARISE DURING THE CLOSEOUT ACTIVATE ALL AUDIBLE&VISIBLE ALARMS X X X X X X
<br /> MODULES ONLY 18AWG-125 MODULES-4,986 PROCESS.
<br /> DETECTORS AND MODULES 18AWG-125 OF EACH-2.271' IN DICATION OF ALARM ON AN N UNCIATOR X X X X X X X
<br /> 16AWG TWISTED PAIR,&4.02 SHIELDED WIRE NETWORK WIRING X
<br /> 16AWG-82pf/FT&4.02 OHMS/1000 FEET IN ITIATE PRI MARY ELEV.RECALL SEQUENCE TO MAIN FLOOR(IF APPLICABLE)
<br /> 18AWG-58pf/FT&6.38 OHMS/1000 FEET
<br /> DETECTORS ONLY i6AWG-125 DETECTORS-6,098' DATA NETWORK SPECIFICATIONS: INITIATE ALTERNATE ELEV.RECALL SEQUENCE TO FIRST FLOOR(IF APPLICABLE) X
<br /> MODULES ONLY 16AWG-125 MODULES-6,098'
<br /> DETECTORS AND MODULES 16AWG-125 OF EACH-S-51 MAXIMUM ALLOWED VALUES BETWEEN ANY THREE NODES OF A NETWORK. RELEASE ALL DOOR HOLDERS&CLOSURES ON FLOOR IN ALARM(OR GEN.ALARM) y x y x x y
<br /> DETECTORS ONLY 18AWG-125 DETECTORS-5,839' • RESISTANCE:90 OHMS ^ X ^ ^ ^ ^
<br /> MODULES ONLY 18AWG-125 MODULES-,271' • CAPACITANCE:0.3 MICROFARADS
<br /> DETECTORS AND MODULES 18AWG-1250F EACH-2,271' DISTANCE:5,000 FEET TRAMS MITTROUBLES,SUPERVISORYSIGNATURE 0LOOP WIRING c-ASS E O SIGNATURE DATA LOOP.o-ASS BONLY X X X X X X
<br /> THE FOLLOWING TABLE LISTS THE MAXIMUM CUMULATIVE CAPACITANCE FOR TRANSMITALARM SIGNALTO CENTRAL STATION MONITOR X X X X X X
<br /> THE ENTIRE DATA NETWORK GIVEN VARIOUS WIRE SIZES AND TRANSMISSION
<br /> RATES.MAXIMUM CUMULATIVE CAPACITANCE IS THE TOTAL CAPACITANCE OF SHUTDOWN RESPECTIVE HVAC FAN I
<br /> ,aoa,x n I.,of .aoP�h ALL INSTALLED COPPER WIRE USED IN THE DATA NETWORK.
<br /> MAXIMUM CUMULATIVE CAPACITANCE IN MICROFARADS TROUBLE INDICATION ON FACP&ANNUNCIATOR X dx
<br /> e0 em
<br /> BAWG-1.4 D/2.8 @38.4K BAU@19.2K BAUD TRANSMITTROUBLE SIGNALTO CENTRALSTATION MON ITOR X
<br /> i 6AWG-1.8 @ 38.4K BAUD/2.1 @ 19.2K BAUD
<br /> US JNACCEPTAISUE 14AWG-2.1 @ 38.4K BAUD/4.2 @ 19.2K BAUD NOTE:THE SEQUENCE OF OPERATIONS IS NOT AFFECTED BY THE CHANGES MADE IN THIS PROJECT.
<br /> CABLE PROPERTIES
<br /> DATA AND AUDIO NETWORKS IN AN EST3 SYSTEM DO NOT REQUIRE THE USE OF
<br /> SHIELDED CABLE,AND NETWORKS DESIGNED WITH TWISTED-PAIR CAN BE
<br /> ABOUT TWICE AS LONG AS THOSE DESIGNED WITH SHIELDED CABLE.THE
<br /> raoP,u o o re'. r_>..a ��GE- MAXIMUM LENGTH OF A DATA NETWORK VARIES WITH THE PROPERTIES OF THE
<br /> WIRE USED.WIRE MANUFACTURERS TYPICALLY PROVIDE SPECIFICATIONS FOR
<br /> WIRE RESISTANCE AND CAPACITANCE.
<br /> eTAR-TARRiN..UH EPTAELE SURVIVABILITY WIRING
<br /> PATHWAY SURVIVABILITY LEVELS
<br /> PATHWAY SURVIVABILITY MUST MEET THE REQUIREMENTS OF NFPA 72;SECTION
<br /> 12.4 FOR THE CORRESPONDING LEVEL OF SURVIVABILITY REQUIRED BY NFPA 72,
<br /> NOTIFICATION WIRING CHAPTER 24.THE FOLLOWING IS A CONDENSED DESCRIPTION OF THE
<br /> SURVIVABILITY LEVELS.
<br /> SPEAKER CIRCUIT WIRING LIMITATIONS: PATHWAY SURVIVABILITY LEVEL 0.LEVEL 0 PATHWAY SHALL NOT BE REQUIRED TO
<br /> WIRE LENGTH LIMITATIONS: HAVE ANY PROVISIONS FOR PATHWAY SURVIVABILITY.
<br /> THE MAXIMUM ALLOWABLE WIRE LENGTH IS THE FARTHEST DISTANCE THAT A PATHWAY SURVIVABILITY LEVEL 1.PATHWAY INSTALLED IN FULLY SPRINKLED
<br /> SPEAKER CIRCUIT CAN EXTEND FROM THE AMPLIFIER TO THE LAST SPEAKER BUILDING MEETING THE REQUIREMENTS OF NFPA 13 WITH ANY INTERCONNECTING
<br /> WITHOUT LOSING 0.5 dB OF SIGNAL.THE FOLLOWING ARE MAXIMUM DISTANCE CONDUCTORS,CABLES OR OTHER PHYSICAL PATHWAYS INSTALLED IN METAL
<br /> BASED ON APPROXIMATE WATTAGE OF THE SPEAKER CIRCUIT.CIRCUIT LENGTHS RACEWAYS.
<br /> ARE FURTHER BASED ON ORIGINATION OF A CIRCUIT FROM EITHER THE PATHWAY SURVIVABILITY LEVEL 2.PATHWAY SURVIVABILITY LEVEL 2 SHALL
<br /> AMPLIFIER OR FROM THE CCi MODULE. CONSIST OF ONE OR MORE OF THE FOLLOWING:
<br /> ALLOWABLE LENGTH AT 25 Vrms,WITH 0.5 dB LOSS (1) 2-HOUR FIRE-RATED CIRCUIT INTEGRITY(CI)CABLE
<br /> 16AWG-20 WATTS-231' (2) 2-HOUR FIRE-RATED CABLE SYSTEM[ELECTRICAL CIRCUIT PROTECTIVE
<br /> 1
<br /> 6AWG-30 WATTS-154' SYSTEM(S)]
<br /> 16AWG- 0 WATTS-154' (3) 2-HOUR FIRE RATED ENCLOSURE OR PROTECTED AREA
<br /> (4) 2-HOUR PERFORMANCE ALTERNATIVES APPROVED BY THE AUTHORITY
<br /> ALLOWABLE LENGTH AT 70 Vrms,WITH 0.5 dB LOSS HAVING JURISDICTION
<br /> 16AWG-20 WATTS-
<br /> 1815' PATHWAY SURVIVABILITY LEVEL 3.SAME AS LEVEL 2 WITH ADDITION OF BEING IN A
<br /> 1
<br /> 6AWG-30 WATTS- FULLY
<br /> i6AWG-40 WATTS-BOT SPRINKLED BUILDING MEETING THE REQUIREMENTS OF NFPA 13.
<br /> 907'
<br /> NAC CIRCUIT(HORN,STROBE)WIRING LIMITATIONS: CIRCUITS REQUIRING SURVIVABILITY BY NFPA 72
<br /> FOR 24VDC SYSTEMS,MINIMUM DEVICE OPERATING VOLTAGE IS 16VDC. THE FOLLOWING CIRCUIT TYPES,WHEN USED ARE REQUIRED TO BE SURVIVABLE
<br /> VOLTAGE DROP CALCULATIONS ARE BASED ON 16VDC AND POWER SUPPLY AS DESCRIBED BELOW.REFER TO NFPA 72,CHAPTER 24 FOR ADDITIONAL
<br /> DE-RATED AND ON DEPLETED BATTERY BACKUP PER THE PRESCRIBED PERIOD INFORMATION REGARDING CIRCUIT TYPES.THIS IS NOT A COMPLETE LIST AND IS
<br /> OF STANDBY AND ALARM RING TIME.THE VOLTAGE DROP WILL LIMIT THE MEANT TO SUPPLEMENT ANY NOTES PROVIDED ELSEWHERE IN OUR DRAWING
<br /> CIRCUITS CAPACITY IN ALMOST ALL CASES AND CURRENT CANNOT BE USED AS PACKAGE.PLEASE CONTACT CONVERGINT ENGINEERING DEPARTMENT WITH ANY
<br /> THE ONLY CIRCUIT WIRING LIMITATION.ALTERATIONS TO CIRCUIT LENGTH QUESTIONS ON THE APPLICATION OF SURVIVABILITY.
<br /> FROM THOSE CALCULATED MAY CAUSE CIRCUITS TO BE OUT OF THE
<br /> TOLERANCES GRANTED BY THE FIRE ALARM CODE.CHANGES TO DEVICE IN-BUILDING FIRE EMERGENCY VOICE/ALARM COMMUNICATIONS SHALL BE
<br /> LOCATION OR CIRCUIT LENGTH SHALL BE COMMUNICATED TO THE CONVERGINT SURVIVABLE BASED ON ONE OF TWO CATEGORIES(24.3.6.4)
<br /> TEAM. •• FOR SYSTEMS EMPLOYING RELOCATION OR PARTIAL EVACUATION,A LEVEL
<br /> 2 OR 3 PATHWAY SURVIVABILITY SHALL BE REQUIRED(24.3.6.4.1).
<br /> NAC CIRCUIT WIRING AND ROUTING MUST NOT EXCEED WHAT IS SHOWN ON THE •• FOR SYSTEMS THAT DO NOT EMPLOY RELOCATION OR PARTIAL
<br /> DESIGN DRAWINGS AND CALCULATIONS.A VOLTAGE DROP TEST IS PART OF EVACUATION,A LEVEL 0,LEVEL 1,LEVEL 2 OR LEVEL 3 PATHWAY
<br /> MOST FIRE FINALS AND IS REQUIRED BY NFPA.A FAILED FIRE FINAL MAY SURVIVABILITY SHALL BE REQUIRED(24.3.6.4.2).
<br /> REQUIRE REWIRING OF THE FAILED CIRCUITS.
<br /> TWO-WAY IN-BUILDING WIRED EMERGENCY COMMUNICATIONS SYSTEMS SHALL
<br /> WIRE RESISTANCE RATINGS USED FOR CALCULATIONS: HAVE A PATHWAY SURVIVABILITY OF LEVEL 2 OR LEVEL 3(24.3.6.7).THIS
<br /> 18AWG-13 OHMS PER 1000' APPLIES TO FIREMAN PHONE SYSTEMS,STAIRWELL RE-ENTRY INTERCOM
<br /> i6AWG-8 OHMS PER 1000' AND ELEVATOR LOBBY TWO-WAY AS REQUIRED BY INTERNATIONAL BUILDING
<br /> 14AWG-:OHMS
<br /> PER 1000' CODE(IBC),SECTIONS,403 AND 1009.8.
<br /> EXAMPLE: 1.0 AMP CIRCUIT LOAD USING#14 WIRE=409 FEET MAXIMUM. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS(DAS)SHALL
<br /> COMPLY WITH 24.3.6.8.1 THROUGH 24.3.6.8.4.DAB IS NOT A COMPONENT OF
<br /> THE FIRE ALARM DESIGN AND IS PROVIDED FOR INFORMATIONAL PURPOSES
<br /> ONLY.
<br /> CLASS A OR B NOTIFICATION WIRING • AREA OF REFUGE EMERGENCY COMMUNICATIONS SYSTEMS SHALL HAVE
<br /> PATHWAY SURVIVABILITY OF LEVEL 2 OR LEVEL 3(24.3.6.9.1).
<br /> CIRCUITS INTENDED TO TRANSMIT OFF-PREMISES SHALL HAVE A PATHWAY
<br /> SURVIVABILITY OF LEVEL 0,LEVEL 1,LEVEL 2 OR LEVEL 3(24.3.6.9.2).
<br /> EOL
<br /> FOR SMOKE CONTROL SPECIFIC SURVIVABILITY REQUIREMENTS,REFER TO THE
<br /> FACP SMOKE CONTROL SECTION OF OUR NOTES.UPON REQUEST,CONVERGINT WILL
<br /> OR EOL RESISTOR ON PROVIDE EQUIVALENT SUBSTITUTIONS FOR ANY SPECIFIED CABLE.ANY CABLE
<br /> NAC NON ADDRESSABLE SUBSTITUTED MUST HAVE EQUAL TO OR BETTER PROPERTIES TO THE CABLE
<br /> CIRCUITS SPECIFIED IN OUR WIRE LEGEND.
<br /> DEVICE DEVICE POWER REQUIREMENTS
<br /> CLASS B,STYLE 4 WIRING EACH MAIN FIRE ALARM PANEL REQUIRES(1)120VAC,20AMP DEDICATED
<br /> CIRCUIT.
<br /> EACH NAC BOOSTER PANEL REQUIRES(1)120VAC,15AMP DEDICATED CIRCUIT.
<br /> IN BUILDINGS EMPLOYING EMERGENCY STANDBY POWER SYSTEMS,THE FIRE REIJON-DESCRIPTION -
<br /> ALARM SHALL BE SUPPLIED WITH EMERGENCY POWER.THIS IS REQUIRED IN ISSUEDFOR PERMIT 12-1-24 TH
<br /> FACP HIGH-RISE AND SMOKE CONTROL APPLICATIONS.ALL OTHER APPLICATIONS I ENGINEERING REVISIONS 02-5 TIN
<br /> OR ARE SUBJECT TO LOCAL BUILDING AND ELECTRICAL CODES.
<br /> NAC
<br /> WHERE THE FIRE ALARM SYSTEM IS CONNECTED TO EMERGENCY
<br /> POWER,THE FIRE ALARM SYSTEM MONITORS THE GENERATOR FOR T2
<br /> RUNNING,FUEL LOW AND TROUBLE STATES.
<br /> DEVICE DEVICE FOR ADDITIONAL DETAILS,REFER TO NFPA 72,CHAPTER 10.
<br /> }
<br /> a
<br /> O 1116
<br /> TAYLOR H.
<br /> 0 PROJECT DESIGNER: gnORH
<br /> W
<br /> Q CLASS A.STYLE 6 WIRING
<br /> U
<br /> to
<br /> Q SEPARATION OF CLASS A CIRCUITS-INSTALLATION EXCEPTIONS:
<br /> PROVIDENCE PACIFIC
<br /> H CLASS A OUTGOING AND RETURN CONDUCTORS,EXITING AND RETURNING LEVEL 2 BEHAVIORAL HEALTH
<br /> TO THE CONTROL PANEL,ARE TO BE ROUTED SEPARATELY.THE MINIMUM 916 PACIFIC AVE
<br /> N 7 RECOMMENDED SEPARATION IS 1 FT.VERTICALLY AND 4 FT.
<br /> x HORIZONTALLY.THE FOLLOWING EXCEPTIONS STILL DO NOT ELIMINATE A 98201
<br /> o THE 2ND PAIR OF WIRES.THEY ALLOW YOU TO USE A SINGLE RACEWAY
<br /> M AND ELIMINATE THE SEPARATION FOR THESE CONDITIONS.
<br /> H
<br /> z 1. WHEN MAXIMUM CABLE,ENCLOSURE,OR RACEWAY IS LESS THAN 10 NOTES
<br /> FEET.NO LIMIT TO NUMBER OF DEVICES.
<br /> 2. UNLIMITED CONDUIT OR RACEWAY DROP TO AN INDIVIDUAL DEVICE.
<br /> ()
<br /> 3. UNLIMITED CONDUIT OR RACEWAY DROP TO A ROOM NOT FIRE ALARM SYSTEM
<br /> Z EXCEEDING 1000 SO,FT.NO LIMIT TO THE NUMBER OF DEVICES.
<br /> Q wlNc.