Laserfiche WebLink
Fault Current Calculations <br />Project: Jackson Elementary School - 2024 Portables <br />Job # 23-219 <br />Fault on Load Side of Transformer with Infinite Short Circuit Current on Primary Available. <br />Node # kVA L-L Volt 0 %Z <br />Utility Transformer <br />6 <br />Date: 2/21 /2024 <br />By: Jeffrey P. Hoover, PE <br />Short Circuit Current <br />37,207.00 <br />Fault Current at the End of a Run of Cable. <br />Short Circuit Current Length Conductors Conductor Raceway Short Circuit Current at <br />Node # at Beoinnino of Run of Run L-L Volt Per Phase 0 TVoe TVoe Wire Size End of Cable Run <br />Panel'DP-PORT' <br />37,207.00 <br />100 <br />240 <br />2 <br />1 <br />Aluminum <br />Non -Metallic <br />350 kcmil <br />25,465.64 <br />(E) Panel'Port1' <br />25,465.64 <br />240 <br />240 <br />1 <br />1 <br />Aluminum <br />Non -Metallic <br />1/0 AWG <br />4,749.24 <br />(E) Panel'Port2' <br />25,465.64 <br />210 <br />240 <br />1 <br />1 <br />Aluminum <br />Non -Metallic <br />1 AWG <br />4,418.63 <br />(E) Panel'Port3' <br />25,465.64 <br />120 <br />240 <br />1 <br />1 <br />Aluminum <br />Non -Metallic <br />1/0 AWG <br />8,005.48 <br />(E) Panel'Port4' <br />25,465.64 <br />240 <br />240 <br />1 <br />1 <br />Aluminum <br />Non -Metallic <br />1/0 AWG <br />4,749.24 <br />(E) Panel'Port5' <br />25,465.64 <br />170 <br />240 <br />1 <br />1 <br />Aluminum <br />Non -Metallic <br />1/0 AWG <br />6,226.65 <br />(E) Panel'Port6' <br />25,465.64 <br />120 <br />240 <br />1 <br />1 <br />Aluminum <br />Non -Metallic <br />1/0 AWG <br />8,005.48 <br />(E) Panel'Port7' <br />25,465.64 <br />90 <br />240 <br />1 <br />1 <br />Aluminum <br />Non -Metallic <br />1/0 AWG <br />9,661.56 <br />