Laserfiche WebLink
Application <br />Model F1 Res ILL sprinklers are cULus Listed in accor- <br />dance with UL 1626 for installation in accordance with <br />NFRA 13, NFRA 13R. and NFRA 13D. Sprinkler systems <br />using Model F1 Res LLaprinNem must be hydraulically <br />designed to provide a1least the flow identified in the Tech- <br />nical Data tables in this bulletin. For NFPA 13 inaiuUaLiuna' <br />the flow per sprinkler must be the greater of: (1) the f|mm <br />listed in the applicable Technical Data table and (2) the <br />flow required to achieve a minimum design density of 0.1 <br />Upnl/sq Uover the design area cdthe sprinkler. For cover- <br />age area dimensions less than those listed in the Technical <br />Data tables, use the minimum required Umm for the next <br />larger max. coverage area listed. <br />Pendent, CCP&SVVCsprinklers use only the Model (3FR2 <br />sprinkler wrench; for installing Model F1 LLRes Recessed <br />HSVVsprinklers use only the Model (JFR2 Sprinkler Wrench. <br />Use ofwrenches other than those specified may damage <br />these sprinklers. Install F1 Ren44 LLwith noei|inQ to de- <br />flector distance of4" 12" Flow arrow on deflector must <br />point away from near wall and "Top" marking must face <br />Adjustment <br />"A" <br />Face of fitting <br />Type <br />Inch (mm) <br />Inch (mm) <br />to ceiling <br />Inch (mm) <br />°Note: Escutcheons F1o,F2may bnused with <br />Model F1 Res 49 LL & 58 LL Recessed Pendent Sprinkler <br />