Laserfiche WebLink
Flow Summary - NFPA 2007 <br />A-PEX Design Services Inc. <br />BENTON SQUARE BLDG B PLAN B GR - One Head Calculation (H.8) <br />Page 4 <br />Date 3/14/2024 <br />SUPPLY ANALYSIS <br />Node at Static Residual Available <br />Source Pressure Pressure Flow Pressure Total Demand Required Pressure <br />STIR 43.0 20 500.0 42.973 13.0 <br />NODE ANALYSIS <br />Pressure <br />Discharge <br />Node Tag <br />Elevation <br />Node Type at Node <br />at Node <br />H.8 <br />124.0 <br />4.9 7.04 <br />13.0 <br />T.26 <br />124.0 <br />7.39 <br />T.27 <br />124.0 <br />7.52 <br />T.30 <br />116.0 <br />11.66 <br />T.33 <br />116.0 <br />11.78 <br />T.32 <br />108.0 <br />15.93 <br />T.25 <br />108.0 <br />16.56 <br />S.1 <br />104.0 <br />18.72 <br />MTR <br />100.0 <br />24.19 <br />STIR <br />100.0 <br />26.21 <br />H.5 <br />124.0 <br />7.2 <br />H.1 <br />124.0 <br />7.37 <br />H.2 <br />124.0 <br />7.54 <br />H.6 <br />124.0 <br />7.72 <br />T.23 <br />124.0 <br />7.8 <br />T.24 <br />116.0 <br />11.63 <br />H.9 <br />116.0 <br />11.66 <br />T.28 <br />116.0 <br />11.72 <br />T.31 <br />116.0 <br />11.74 <br />H.17 <br />116.0 <br />11.8 <br />T.36 <br />116.0 <br />11.83 <br />T.34 <br />108.0 <br />15.82 <br />H.16 <br />108.0 <br />15.92 <br />T.29 <br />124.0 <br />7.54 <br />H.13 <br />124.0 <br />7.58 <br />H.18 <br />124.0 <br />7.67 <br />H.21 <br />124.0 <br />7.75 <br />H.22 <br />124.0 <br />7.82 <br />T.37 <br />124.0 <br />7.84 <br />T.38 <br />116.0 <br />11.82 <br />T.39 <br />116.0 <br />11.84 <br />T.40 <br />116.0 <br />11.84 <br />T.35 <br />108.0 <br />15.82 <br />H.7 <br />124.0 <br />7.8 <br />H.11 <br />124.0 <br />7.81 <br />H.14 <br />124.0 <br />7.82 <br />H.19 <br />124.0 <br />7.84 <br />H.3 <br />116.0 <br />11.64 <br />HA <br />116.0 <br />11.64 <br />H.10 <br />116.0 <br />11.65 <br />H.12 <br />116.0 <br />11.73 <br />H.15 <br />116.0 <br />11.79 <br />26.214 <br />Notes <br />Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 <br />