HOPEWORKS TENANT IMPROVEMENT Bill of Material FIRE ALARM GENERAL NOTES
<br /> Qty. Description Manufacturer Model Part No. 1. INSTALL NEW NOTIFICATION, INITIATION AND MONITORING DEVICES FOR KITCHEN SPACE
<br /> 3 HORN STROBE,CEILING,WHITE SYSTEM SENSOR PC2WL PC2WL TENANT IMPROVEMENT PER NFPA 72 2016 and 2018 IBC. TWO NOTIFICATION DEVICES ARE
<br /> Le 7 STROBE,WALL,WHITE SYSTEM SENSOR SWL SWL BEING RELOCATED, ALL OTHER DEVICES ARE NEW. NEW DEVICES TO BE INSTALLED ON
<br /> n 4 0 4 4 2 DUAL MONITOR MODULE SILENT KNIGHT SK-MONITOR-2 SK-MONITOR-2 ISTING CIRC S IF OWER PAC ALLOWS.
<br /> a NE NO IC ION EVIC A D . 4 A S IS NG OW SU L AND IR IT.
<br /> ® Funka Everett Snohomish Count PUD n ro �� 7 HORN STROBE,WALL,WHITE SYSTEM SENSOR P2WL P2WL
<br /> 9 y 1 cdifor sr FIELD VERIFY POWER SUPPLY HAS THE CAPACITY TO SUPPORT NEW DEVICES. CONTRACTOR
<br /> p 1 SMOKE DETECTOR SILENT KNIGHT SK-PHOTO-W SK-PHOTO-W TO PERFORM 24HR DRAW DOWN TEST IN FIELD TO VERIFY EXISTING BATTERY SIZE AND
<br /> Hewitt Reptile Emporium END OF LINE VOLTAGE. SHOULD THE DRAW DOWN TEST FAIL, THE BATTERY SIZE WILL BE
<br /> o HewlttAve Narrative Coffee Everett HewttAve v r INCREASED AND TESTED AGAIN. SHOULD THE END OF LINE VOLTAGE BE BELOW 16V, THE
<br /> Schack Art Center 9 CIRCUIT WILL BE SPLIT AND A NEW POWER SUPPLY WILL BE ADDED, IF REQUIRED.
<br /> MATRIXFIRE OF3. NEW INITIATION AND MONITORING DEVICES ADD .155 AMPS (ALARM), .0002 AMPS (STANDBY)
<br /> US Foods CHEFISTORE -
<br /> Imagine Chuseu s® © 1 E APPLIES TO TI AREA DEVICES ONLY J '`
<br /> f ( ) T TO EXISTING FIRE ALARM CONTROL UNIT (FACU). CONTRACTOR TO PERFORM 24HR DRAW
<br /> Museum ,� Lowe's Home c, P °
<br /> Improvement cl c ��° °�� o DOWN TEST IN FIELD TO VERIFY EXISTING BATTERY SIZE AND END OF LINE VOLTAGE.
<br /> SHOULD THE DRAW DOWN TEST FAIL, THE BATTERY SIZE WILL BE INCREASED AND TESTED
<br /> Pacific Ave Pac ific Ave J �. (� �O ti
<br /> PaeiOc Ave n x _ 1f 1/I 0(0 ��? °2 �, Q�2 �� °� e m AGAIN. SHOULD THE END OF LINE VOLTAGE BE BELOW 16V, AN SLC EXPANDER WILL BE
<br /> o s Jade Garden Chinese �� o KT o P �� �P o ADDED.
<br /> > s a 3Z Restaurant&Lounge .. Delta Hotels by p= ? = O
<br /> Drder Delivery© 4 1 Q O J
<br /> EvzrettQ Vs2^d St Mar io{t Seattle Ever' c Oo Q y- 4, Q o
<br /> wanuberEats c �� o o 0 0 �o J0 CONDITIONS. o
<br /> �` � �� =P �� `g zo Q 5. CONDUIT IS TO BE PROVIDED AND INSTALLED BY OTHERS. k N
<br /> �`Willamette Dental p '° o } ° � o J �, Q= �, Q ��
<br /> Group•Everett _ �o �° Ps= �� °o� �_ �P 6. SSNW TO PERFORM A 24—HOUR DRAW DOWN TEST OF THE FACU AND END LINE VOLTAGE o
<br /> ScuttlebuttBrewing© ' e �P �P �� Jm e ��' o �P �P moo° °� TEST TO VERIFY NEW DEVICES ADDED ARE SUPPORTED BY THE CURRENT STANDBY POWER r
<br /> as"s` , Taproom = °� o� 3� JQ �° oo ° P °� c� zJ �' AVAILABLE. SHOULD THE ADDITION OF THESE DEVICES CAUSE THE CIRCUIT TO BE o
<br /> GENERAL FIRE ALARM OVERLOADED (EOL VOLTAGE BELOW 16V) OR THE BACKUP POWER TO BE EXCEEDED, AN
<br /> m Q 340sr Sams MANUAL PULL STATIONS • • • • • • APPROPRIATE POWER SUPPLY AND/OR BATTERY BACKUP SHALL BE EMPLOYED TO o o < o
<br /> n a�^sr M GENERAL AREA SMOKE • • • • • • • ACCOMPLISH CODE COMPLIANCE. Z
<br /> DEVICE TROUBLE • • ¢ ^
<br /> Doyle Park n sa`nal FACU TROUBLE • • 7. CORE DRILLING REQUIRED TO FACILITATE ALL CONDUIT WORK. CORE DRILLED HOLES SHALL o o
<br /> FACU AC LOSS • • NOT PENETRATE THROUGH ANY STRUCTURAL BEAMS, REBAR AND/OR CONDUIT CONTAINED o z z o
<br /> PORT GARDNER Brown Bear Car Wash 9Dick'sTowing,lnc FACU SILENCE • �
<br /> Q • WITHIN THE CONCRETE SLABS AND/OR WALLS THAT MAY COMPROMISE THE STRUCTURAL
<br /> FACU RESET Y
<br /> JiiLube INTEGRITY OF THE BUILDING. CORE DRILL LOCATION MAY NEED TO BE ADJUSTED TO
<br /> 5zh st
<br /> OS15DfrStandard LEVEL 1 ACCOMMODATE OBSTRUCTIONS. PRIOR TO DRILLING COORDINATE EXACT LOCATIONS OF
<br /> 3 o Oil Change GENERAL AREA SMOKE • • • HOLES WITH GENERAL CONTRACTOR.
<br /> Diamond q FLow swlrcH • • • • • • • 8. THIS DRAWING SHOWS THE LAYOUT OF THE FIRE ALARM SYSTEM AND INDICATES THE F�
<br /> VeterinaryHospitaly 3nhSt 3Tmsl a ELEVATOR LOBBY SMOKE • • • • • • • • APPROXIMATE LOCATION OF EQUIPMENT, WIRING, AND CONDUIT. WIRING AND CONDUIT ARE
<br /> 37th St (1) POINTS SHOWN ARE TYPICAL. ORDER OF OPERATIONS WILL BE DICTATED BY EXISTING PROGRAMMING ON FACU. L
<br /> SHOWN POINT TO POINT ONLY. THE CONDUIT IS TO BE INSTALLED IN APPROXIMATELY THE r z
<br /> AREA AS INDICATED ON THE DRAWINGS; HOWEVER, THE CONTRACTOR SHALL BE
<br /> VICINITY MAP RESPONSIBLE FOR ANY MODIFICATIONS AS MAY BE REQUIRED TO SUIT STRUCTURAL OR JOB CD
<br /> CONDITIONS. THE CONTRACTOR SHALL FURNISH ALL OFFSETS, ADDITIONAL MATERIAL, ^I
<br /> NTs: CONDUIT ADJUSTMENTS, ETC. AS MAY BE REQUIRED TO MEET INSTALLATION CONDITIONS. w rn v CD
<br /> ACTUAL WIRE RUNS SHALL BE KEPT IN AN ORGANIZED MANOR BY THE INSTALLING Q
<br /> CONTRACTOR TO FACILITATE AS—BUILT DRAWINGS. v
<br /> 9. PRIOR TO ROUGH—IN COORDINATE THE EXACT LOCATIONS OF FIRE ALARM EQUIPMENT, l ' _ Ln Q rn
<br /> DEVICES, AND CONDUIT WITH THE ELECTRICAL, MECHANICAL, AND FIRE PROTECTION v J Z x o 0
<br /> Fire Alarm Symbol Legend Cable/Circuit Report CONTRACTORS. 1
<br /> C Length 1 1 7 z M M
<br /> SYMBOL DESCRIPTION PART NUMBER able Lth Overage:l0% 10. THE CONTRACTOR IS TO REVIEW AND VERIFY ALL FIELD CONDITIONS, MEASUREMENTS, W O J
<br /> PLANS, AND STOCK LISTS, PRIOR TO ORDERING, FABRICATION, AND INSTALLING. SECURITY m
<br /> MODULES Source Circuit Circuit Type Circuit Abbr Wiring Style Symbol Description Gauge Length Color SOLUTIONS NW WILL NOT ASSUME THE RESPONSIBILITY OF THE ALARM COMPONENTS OR tin
<br /> EXISTING FACU I SIG ISignaling line U Class IS 1812 SOL JKT FPLR IM RL RED #18 100'-0 Red CONDUIT FITTING PER PLAN.
<br /> DM DUAL MONITOR MODULE,ADDRESSABLE SK-MONITOR-2 EXISTING POWER SUPPLY I NAC INotification I V I Class IS I 1412SOLJKTFPLRIMRLRED #14 350'-0 1 Red 11. THE FIRE ALARM SYSTEM CONTRACTOR AND GENERAL CONTRACTOR SHALL COORDINATE ALL
<br /> INITIATION CUTTING, PATCHING, AND FINISH WORK.
<br /> 12. ALL ALARM WIRING IS TO BE IN ACCORDANCE WITH NFPA 72
<br /> 13. WIRING PATHWAY CLASS DESIGNATIONS:
<br /> OS PHOTO SMOKE DETECTOR SK-PHOTO-W — SLC PATHWAY CLASS DESIGNATIONS: CLASS B
<br /> 14. PENETRATIONS THROUGH FIRE RATED PARTITIONS TO BE SEALED BY OTHERS TO MAINTAIN
<br /> NOTIFICATION THE INTEGRITY OF THE PARTITION.
<br /> 0
<br /> ',p�' HORN/STROBE,WALL P2WL
<br /> Q: ❑ 15. LOCATE SMOKE DETECTORS NOT CLOSER THAN 36" FROM AIR—SUPPLY DIFFUSER OR
<br /> ❑ T ING A ® DISH WALK-IN RETURN—AIR OPENINGS.
<br /> SHING
<br /> EXISTING HORN/STROBE,WALL 75 coo 16. LOCATE DETECTORS NOT CLOSER THAN 12" FROM ANY PART OF A LIGHTING FIXTURE AND
<br /> NOT DIRECTLY ABOVE PENDANT MOUNTED OR INDIRECT LIGHTING.
<br /> HORN/STROBE,CEILING PC2WL 17. INSTALL A COVER ON EACH SMOKE DETECTOR THAT IS NOT PLACED IN SERVICE DURING
<br /> s 30CD T RA
<br /> ALK-I CONSTRUCTION. COVER SHALL REMAIN IN PLACE EXCEPT DURING SYSTEM TESTING.
<br /> ® STROBE,WALL SWL
<br /> TO EXISTING Lc ® p CHILL F EEZE 18. AUDIBLE/VISUAL ALARM INDICATION DEVICES SHALL BE INSTALLED NOT LESS THAN 6"
<br /> ® BELOW THE CEILING BETWEEN 80" AND 96" ABOVE FLOOR LEVEL. INSTALL HORN/STROBES
<br /> q RF H 75c E ON FLUSH MOUNTED BACK BOXES. ALL DEVICES SHALL BE MOUNTED AT THE SAME HEIGHT.
<br /> REVIEWED BY: CHRIS RUSSELL
<br /> ANS�LAL R L 19. AUDIBLE ALARM INDICATION DEVICES SHALL BE INSTALLED NOT LESS THAN 90' ABOVE THE NICET CERTIFICATION NO.120520
<br /> DM DM m FLOOR AND NOT LESS THAN 6" BELOW THE CEILING. ALL DEVICES SHALL BE MOUNTED AT
<br /> 1,9 E FROM EXISTING SLC THE SAME HEIGHT. FIRE ALARM SYSTEMS
<br /> EXPIRES:AUGVEL III
<br /> m m 20. CONTRACTOR SHALL PERFORM AND MEET ALL CODE REQUIRED TESTS, AND FILE A CERTIFICATION EXPIRES:AUGUST 1,2025
<br /> 9RELOCATE DEVICE
<br /> arr MATERIALS TEST CERTIFICATE PER NFPA 72.
<br /> t m IR
<br /> Permit#: FA2402-015
<br /> ® Site Address: 3315 Broadway
<br /> RELOCATE DEVICE , Applicant: Madison Stewart W
<br /> 75C ®® ® Application Date:02/22/2024 C
<br /> Description: Hopeworks Fire Alarm TI for Kitchen G
<br /> Review Date: 02/28/2024 WW
<br /> _ O�LL/
<br /> EVERETT
<br /> tl Everett Fire Dept.Permit Review
<br /> Status:Approved
<br /> € 000e.rvIAIR
<br /> .i.c.
<br /> Reviewed By:KBrown
<br /> g 02/28/2024 2:13:28
<br /> PM 5
<br /> OUTSIDE SCOPE L z
<br /> LU Q
<br /> z
<br /> LU
<br /> Ce z 0 zCie
<br /> O
<br /> m F—
<br /> U
<br /> �
<br /> L.U0 W N W
<br /> Z r/� � W
<br /> r F
<br /> Ce V W V
<br /> W Lf w M w O
<br /> LL a M W a =
<br /> DRAWING SIZE:E SIZE 30".42"
<br /> DRAWN BY:JOEL DUGGAN
<br /> DATE DRAWN:08/28/23
<br /> REV DATE: 10/12/23
<br /> FLOOR PLAN - LEVEL 1 SHEET INDEX BUSINESSECURSN790#
<br /> SECURSN790NE
<br /> SHEET DESCRIPTION ELECTRICAL LICENSE#
<br /> SCALE:1/8"=V-0" SECURSN954JG
<br /> o r e
<br /> FA.0.01 SHEET INDEX,SYMBOL LIST,GENERAL NOTES,WIRE DESIGNATIONS,LAYOUT,ETC...
<br /> FA.1.01 DEVICE DETAILS&SYSTEM POINT-TO-POINT(TYPICAL) FA.0.01