• • <br /> MyBui tdirn Perm t.corn <br /> a erviceof'` CfGavrret Construction Tip Sheet 04 <br /> Alarms and Detectors Near Cooking Appliances per NFPA 72 <br /> Refer to Figure 2: <br /> A. Photoelectric smoke alarms shall not be installed less than 6 feet horizontally from a <br /> permanently installed cooking appliance. (NFPA 72 29.8.3.4 (4)) <br /> B. Ionization smoke alarms with an alarm-silencing switch must not be less than 10 feet from a <br /> permanent cooking appliance. (NFPA 72 29.8.3.4(4)) <br /> C. Ionization smoke alarms without an alarm-silencing switch must not be less than 20 feet from a <br /> permanent cooking appliance. (NFPA 72 29.8.3.4 (4)) <br /> Kitchen <br /> 20'----t' < 10"-/ <br /> Figure 2: Smoke Alarms and Smoke Detectors Near Cooking Appliances <br /> Carbon Monoxide Alarm Location Limitations <br /> ❑ Do not place alarms directly above or beside fuel-burning appliances. <br /> ❑ Do not place alarms in direct sunlight. <br /> ❑ Do not place alarms in low areas where children can reach. Do not place alarms behind <br /> curtains or any structure that might prevent carbon monoxide from reaching the sensor. <br /> April 12,2021 MyBuildingPermit.com I Smoke,Heat&Carbon Monoxide Alarms 4 <br /> ct Gev tef= <br />