Laserfiche WebLink
Job:SOCIETY OF ST.VINCENT DE PAUL <br /> Hydraulic Analysis for : 1 <br /> Calculation Info <br /> Calculation Mode Demand <br /> Hydraulic Model Hazen-Williams <br /> Fluid Name Water @ 60F (15.6C) <br /> Fluid Weight, (lb/ft3) N/A for Hazen-Williams calculation. <br /> Fluid Dynamic Viscosity, (lb•s/ftz) N/A for Hazen-Williams calculation. <br /> Water Supply Parameters <br /> Supply 1 : W 1 Flow(gpm) Pressure(psi) <br /> 0 73 <br /> 2094 41 <br /> Supply Analysis <br /> Residual Available <br /> Node at Source Static Pressure pressure Flow pressure Total Demand Required Pressure <br /> (Psi) (psi) (gpm) (psi) (gpm) {Psi) <br /> wi 73 41 2094 71.3 680.7 55.7 <br /> Hoses <br /> Inside Hose Flow!Standpipe Demand(gpm) <br /> Outside Hose Flow(gpm) <br /> Additional Outside Hose Flow(gpm) 250 <br /> Other(custom defined) Hose Flow(gpm) <br /> Total Hose Flow(gpm) 250 <br /> I <br /> Sprinklers <br /> Ovehead Sprinkler Flow(gpm) 430.7 <br /> InRack Sprinkler Flow(gpm) 0 <br /> Other(custom defined)Sprinkler Flow(gpm) 0 <br /> i <br /> t <br /> Total Sprinkler Flow(gpm) 430.7 <br />. Other <br /> Required Margin of Safety(psi) 0 <br /> W1 -Pressure(psi) 56.7 <br /> W 1 -Flow(gpm) 430.7 <br /> i <br /> Demand w/o System Pump(s) N/A <br /> r <br /> t <br /> is <br /> l <br /> r <br /> a <br /> e <br />[k <br /> E <br /> 4 <br /> k: <br /> l <br /> is <br /> File:E:1F22043-SOCIETY OF VINCENT DE PAUL1F22043-ST.VINCENT CALCS.dwg <br /> Date 11/23/2022 Copyright @ 2002-2012 Tyco Fire Protection Products Page 4 <br /> i <br />