Laserfiche WebLink
Service Ticket No. :ST00371802 <br /> Date : 12/17/2024 <br /> PYE* Frequency: Annual <br /> � BARKER Service Ticket No. : ST00371802 <br /> Inspection Contract No. <br /> FIRE 6 SAFETY•EST. 1946 PO No. : <br /> Equipment Location : Water Manifold to the left of <br /> Backflow Inspection Report <br /> Property McDonald's#23463 Owner McDonald's#23463 <br /> Address 7920 Evergreen Way Address 7920 Evergreen Way <br /> City Everett City Everett <br /> State WA State WA <br /> Zip 98203 Zip 98203 <br /> Phone 4253536267 Phone 4253536267 <br /> BACKFLOW INSPECTION SUMMARY <br /> Domestic: 1 Fireline: 0 <br /> Irrigation: 0 <br /> DEFICIENCIES <br /> None found at time of inspection. <br /> BACKFLOW INSPECTION - Location: Water Manifold To The Left Of Dishpit 1- Protecting Incoming <br /> Assembly Located Inside Building <br /> Type of backflow Domestic <br /> Assembly Type RP <br /> Time of Test 01:14pm <br /> Manufacturer Wilkins <br /> Model 375XLRP <br /> Size .50 <br /> Serial Number AJBI0654 <br /> Inspection Type Initial Inspection <br /> Reason Tested New Assembly <br /> Service Meter Number NA <br /> Supply Line Size .50 <br /> Line PSI 75 <br /> Isolation or Containment N/A <br /> **Check Valve#1 Closed Tight or Leaked Closed Tight <br /> PSI Differential Across Check Valve#1 8.8 <br /> **Check Valve#2 Closed Tight or Leaked Closed Tight <br /> PSI Differential Across Check Valve#2 8.8 <br /> •735 E Fairhaven Ave•Burlington WA•98233-1914 <br /> Backflow Inspection Page 2 of 3 <br />