Laserfiche WebLink
victaulic.com <br /> 7.0 REFERENCE MATERIALS — CHARACTERISTICS <br /> VicFlex Maximum Load Values <br /> Series AH2 Hose with 24" Bracket <br /> Actual Length Total Load Max. Uniform Load <br /> ft <br /> Model Size m Ib N Ib/linearft N/linearm <br /> 31/790 6 5. 23 2.6 38 <br /> 0.8 <br /> 36/915 �9 5.5 25 2.8 40 <br /> 48/1220 1 2 6.3 28 3.1 46 <br /> 60/1525 1 5 7.0 31 3.5 51 <br /> 72/1830 1 8 7.7 34 3.9 57 <br /> Series AH2 Hose with 48" Bracket <br /> Actual Length Total Load Max. Uniform Load <br /> ft <br /> Model Size m lb N Ib/linearft N/linearm <br /> 31/790 2.6 6.1 27 1.5 22 <br /> 36/915 0 9 6.4 29 1.6 23 <br /> 48/1220 1 2 7.2 32 1.8 26 <br /> 60/1525 15 7.9 35 2.0 29 <br /> 72/1830 1 8 8.7 39 2.2 32 <br /> Total Load is defined as the sum of the weights of the following: <br /> • water-filled flexible sprinkler hose with threaded end fittings, including a typical fire sprinkler <br /> • bracket assembly (any applicable Victaulic bracket model of the relevant associated size) <br /> ASTM C 635: Suspension System Load-Carrying Capabilities (excerpted) <br /> Actual Length Min.Allowable Uniform Load <br /> Suspension System ft/m Ib/linearft N/linearm <br /> Light 5.0 75.7 <br /> Direct Hung Intermediate 12.0 181.0 <br /> Heavy 16.0 241.7 <br /> SUMMARY: All direct-hung suspension system duty classifications per ASTM C 635 are able to withstand the <br /> maximum water-filled weight of the VicFlex sprinkler hose and bracket. <br /> 10.85 5839 Rev AL Updated 02/2022 ©2022 Victaulic Company.All rights reserved. <br /> victaulic.com 29 ✓ctaulic° <br />