?owers
<br /> PERFORMANCE DATA FASTENING INNOVATIONS
<br /> Converted Allowable Loads for Power-Stud+ SD2 in Cracked Concrete','
<br /> Minimum Concrete Compressive Strength
<br /> Nominal Nominal fc=2,500 si fc=3,000 si fc=4,000 si f'c=6,000 si f'c=8,000 si
<br /> Anchor Embed. P P P P P
<br /> Size ham
<br /> (in.) (In.) Tai_ble,ASD VA. ble,ASD Tall-ble,ASD Vall-ble,ASD Tallowable,ASD V,11-1,1e,ASD Tallowable,ASD Vall-ble,ASD Tallowable,ASD VJ..abl,,ASD
<br /> / Tension Shear Tension Shear Tension Shear Tension Shear Tension Shear
<br /> [lbs.) (lbs.) [lbs.) (lbs.) (lbs.) [lbs.) (lbs.) [lbs.) (lbs.) (lbs.)
<br /> 3/8 2-3/8 1,005 1,205 1,070 1,320 1,175 1,445 1,345 1,445 1,480 1,445
<br /> 2-1/2 1,120 1,205 1,220 1,320 1,410 1,520 1,730 1,860 1,995 2,150
<br /> 112
<br /> 3-3/4 2,030 2,235 2,225 2,235 2,570 2,235 3,145 2,235 3,630 2,235
<br /> 3-7/8 2,310 3,015 2,530 3,300 2,925 3,810 3,580 4,670 4,135 4,720
<br /> 5/8
<br /> 4-7/8 3,455 4,720 3,790 4,720 4,375 4,720 5,355 4,720 6,185 4,720
<br /> • 4-1/2 2,865 5,420 3,140 5,855 3,625 5,855 4,440 5,855 5,125 5,855
<br /> 3/4
<br /> 5-3/4 3,620 5,855 3,965 5,855 4,580 1 5,855 5,605 5,855 6,475 5,855
<br /> 1. Allowable load values are calculated using a conversion factor,o(,from Factored Design Strengths and conditions shown on the previous page.
<br /> 2. Tabulated allowable load values assume 50%dead load and 50%live load,with controlling load combination 1.2D+1.6L.Calculated weighted average for the conversion factor,
<br /> Z o(:1.2(0.5)+1.6(0.5)=1.4.
<br /> 0
<br /> a � Converted Allowable Loads for Power-Stud+ SD2 in Uncracked Concrete",
<br /> Minimum Concrete Compressive Strength
<br /> O Nominal Nominal fc=2,500 si fc=3,000 si fc=4,000 si fc=6,000 si fc=8,000 si
<br /> Anchor Embed. P P P P P
<br /> Size hna
<br /> (in.) (in-) Tallowable,ASD V Ilowablc.ASD TdllOwdblc.A$D V Ilowablc.ASD T Ilowable.ASD V Ilowable,ASD T Ilowablc.ASD V Ilowablc.ASD T Ilowable,ASD V Ilowable,ASD
<br /> �C Tension Shear Tension Shear Tension Shear Tension Shear Tension Shear
<br /> � v [lbs.) (lbs.) [lbs.) (lbs.) (lbs.) [lbs.) (lbs.) [lbs.) (lbs.) [lbs.)
<br /> p 3/8 2-3/8 1,290 1,445 1,410 1,445 1,630 1,445 1,995 1,445 2,305 1,445
<br /> 2-1/2 1,575 1,695 1,725 1,860 1,995 2,145 2,445 2,235 2,820 2,235
<br /> 1/2
<br /> v 3-3/4 3,070 2,235 3,365 2,235 3,885 2,235 4,755 2,235 5,495 2,235
<br /> N 3-7/8 3,265 4,220 3,575 4,620 4,130 4,72 55,055 4,720 5,840 4,720
<br /> 5/8
<br /> 4-7/8 4,880 4,720 5,345 4,720 6,175 4,720 7,005 4,720 7,005 4,720
<br /> 4-1/2 4,045 5,855 4,430 5,855 5,120 5,855 6,270 5,855 7,235 5,855
<br /> 3/4
<br /> 1 5-3/4 6,230 5,855 6,825 5,855 7,880 5,855 9,650 5,855 11,145 5,855
<br /> 1. Allowable load values are calculated using a conversion factor,o(,from Factored Design Strengths and conditions shown on the previous page.
<br /> 2. Tabulated allowable load values assume 50%dead load and 50%live load,with controlling load combination 1.21)+1.6L.Calculated weighted average for the conversion factor,
<br /> o(:1.2(0.5)+1.6(0.5)=1.4.
<br /> Ultimate and Allowable Load Capacities for Power-Stud+ SD2 in dpB F,
<br /> Grouted Filled Concrete Masonry'Z,3
<br /> Minimum Masonry Compressive Strength,
<br /> Nominal f'm=1,500 psi(10.4 MPa)
<br /> = In Minimum M^m- a
<br /> v Size Embedment Installation Ulimate Allowable Ulimate Allowable Di...Rip) �
<br /> z Depth Location' Load Load Load Load
<br /> n Min. (mm) Tension Tension Shear Shear
<br /> lbs. lbs. lbs. lbs. MTum
<br /> (kN) (kN) (kN) (kN) ���'DisWnw
<br /> ('1
<br /> Z 3/8 2 1/2 Wall Face/End 11670 335 2,075 415
<br /> D (9.5) (50.8) Min.2-1/2' Edge and (74) (1.5) (9.2) (1.8) Gaut tilled
<br /> n
<br /> End Distances �MDaP)
<br /> z
<br /> Wall Face/End
<br /> Min.3"
<br /> A 2-1/2 Edge and 2 295 460 1,310 260
<br /> (50.8) Face Shell
<br /> 112 End Distances (10.2) (2.0) (5.8) (1.2) Permissible Anchor Locations
<br /> (12.7) TO of Wall (Un-hatched Area/Through Face Shell)
<br /> 0 3 3/4 Min.1-3/4" Ede and 3 320 665 1,140 230
<br /> (953) 4" Edge Distances (14.8) (3.0) (5.1) (1.0)
<br /> 0 1. Tabulated load values are for anchors installed in minimum 6-inch wide,minimum Grade N,Type II,lightweight,medium-weight or normal-weight concrete masonry units conforming to
<br /> ASTM C 90.Mortar must be minimum Type N.Masonry compressive strength must be at the specified minimum at the time of installation.
<br /> 2. Allowable load capacities listed are calculated using and applied safety factor of 5.0.Consideration of safety factors of 10 or higher may be necessary depending upon the application
<br /> such as life safety.
<br /> 3. Anchor installations into grouted masonry walls are limited to one per masonry cell.
<br /> 9 www.powers.com