SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 <br /> DATE: 6/26/2024 NEW DRY SYS-SUBMITTAL. sdf <br /> JOB TITLE: Boeing 40-87 High Density Storage - New Dry Riser <br /> WATER SUPPLY ANALYSIS <br /> Static: 67 . 00 psi Resid: 57 . 00 psi Flow: 3090 . 0 gpm <br /> 180 . 0 <br /> LEGEND <br /> 1 �Pressure available <br /> C <br /> 150 . 0 at source <br /> 63.31 psi @ 1803.0 gpm <br /> 2 Pressure required <br /> 5 at source <br /> G 53.24 psi @ 1803.0 gpm <br /> A 120 . 0 3 g 6 Pressure available <br /> -- _ <br /> U from pump <br /> G 74.37 psi @ 1303.0 gpm <br /> E 4 �Pressure required <br /> from pump <br /> P 90 . 0 74.37 psi @ 1303.0 gpm <br /> R 5 Total Pressure avail- <br /> E able at pump dschg. <br /> S 4 137.67 psi @ 1303.0 gpm <br /> S E 6 Total Pressure re- <br /> F_ � quired at pump dschg. <br /> U 60 . 0 0-1 — <br /> R _ 127.60 psi @ 1303.0 gpm <br /> �17 2 ill - - - - \_ ------ Avail. OnSite Demand Press. <br /> E 7�A 7�i1 - <br /> 63.31 psi @ 1303.0 gpm <br /> ( Req. OnSite Demand Press. <br /> p 30 . 0 53.24 psi @ 1303.0 gpm <br /> s A. Source Supply Curve <br /> i B. Net Pump Supply Curve <br /> D C. Pump Discharge Curve <br /> 0 . 0 D. System Demand Curve <br /> E. Available at Source (On Site) <br /> -14 . 7 F. Available at Pump Suction <br /> 80i12001600 2000 2400 2800 3200 3600 4000 <br /> FLOW (GPM) <br /> Note: (1) Dashed Lines indicate extrapolated values from Test Results <br /> (2) On Site pressures are based on hose stream deduction at the source <br />