(E) POTTER RTS-O/RTS-C <br /> The Symbol of Protection Room Temperature Switch <br /> Inspection, Testing, & Maintenance <br /> The frequency of inspection and testing of the RTS and its associated monitoring system shall be in accordance with applicable local and NFPA codes <br /> and standards.Manufacturer recommends quarterly or more frequently. <br /> Functional test can be accomplished by spraying the RTS with circuit cooler or equivalent. <br /> More accurate test requires exposing the RTS to 40°F f 5°F. <br /> The RTS requires no maintenance other than ensuring the vent holes are not obstructed. <br /> Fig 1 <br /> RTS-O RTS-O <br /> Control Unit <br /> Supervisory Device EOLR <br /> Circuit <br /> RTS-C RTS-C <br /> Control Unit <br /> Supervisory Device EOLR <br /> Circuit <br /> DWG#1019-1 <br /> NOTE.This RTS does not have duplicate terminals.Do not use looped wire under terminals.Break wire run to provide supervision of connections. <br /> RTS Mounting Template Ordering Information <br /> Fig 2 Model Description Stock No. <br /> RTS-O Normally Open Room Temperature 1010108 <br /> O O Switch <br /> + RTS-C Normally Closed Room Temperature 1010109 <br /> 0 O O Switch <br /> 0 0 , <br /> Supervisory switches have a normal service life of 10-15 years. <br /> O 0 O O However, the service life may be significantly reduced by local <br /> enviromnental conditions. <br /> 0 <br /> Potter Electric Signal Company, LLC St. Louis, MO Phone: 866-956-0988 / Canada 888-882-1833 www.pottersignal.com <br /> 5401019-REV H • 09/15 PAGE 2 OF 2 <br />