Laserfiche WebLink
(E) POTTER VS R <br /> The Symbol of Protection Vane Type Waterflow Alarm Switch W/Retard <br /> Installation (see Fig. 1) <br /> These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they shall be installed on the top side of the pipe where they will <br /> be accessible. The device should not be installed within 6" (15 cm)of a fitting which changes the direction of the waterflow or within 24" (60 cm) <br /> of a valve or drain. <br /> NOTE:Do not leave cover off for an extended period of time. <br /> Drain the system and drill a hole in the pipe using a hole saw in a slow speed drill(see Fig. 1).Clean the inside pipe of all growth or other material <br /> for a distance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend or crease it. <br /> Insert the vane so that the arrow on the saddle points in the direction of the waterflow. Take care not to damage the non-corrosive bushing in the <br /> saddle.The bushing should fit inside the hole in the pipe.Install the saddle strap and tighten nuts alternately to required torque(see the chart in Fig. <br /> 1).The vane must not rub the inside of the pipe or bind in any way. <br /> A CAUTION <br /> Do not trim the paddle.Failure to follow these instructions may prevent the device from operating and will void the warranty.Do not obstruct or otherwise prevent the trip <br /> stem of the flow switch from moving when water flows as this could damage the flow switch and prevent an alarm.If an alarm is not desired,a qualified technician should <br /> disable the alarms stem. <br /> Fig.1 Retard Adjustment <br /> DO NOT LEAVE COVER OFF FOR <br /> AN EXTENDED PERrOD OF TIME The delay can be adjusted by rotating the retard adjustment knob <br /> from 0 to the max setting(60-90 seconds).The time delay should be <br /> set at the minimum required to prevent false alarms <br /> TIGHTEN NUTS <br /> A1,TERNATELY CAUTION <br /> �/ Hole must be drilled perpendicular to the pipe and vertically centered <br /> o Refer to the Compatible Pipe/Installation Requirements chart for size <br /> MOUNT ON PIPE SO CO1T0Ct IriCO1TeCt <br /> ARROW ON SADDLE O <br /> POINTS IN DIRECTION <br /> OF WATERFLOW <br /> SOmm <br /> ROLL PADDLE IN <br /> OPPOSITE DIRECTION ADAPTER ADAPTER <br /> DIRECTION OF OF WATERFLOW <br /> WATERFLOW <br /> (Flowing water activates 20mm 2-MAX. <br /> device in one direction only.) DN50 ONLY <br /> DWG IfA6-II USE(2)5180162 ADAPTERS AS SHOWN ABOVE <br /> Compatible Pipe/Installation Requirements <br /> Model Nominal Pipe Nominal Pipe Pipe Wall Thickness Hole Size U-Bolt Nuts <br /> Size O.D. Lightwall Schedule 10(UL) Schedule 40(UL) BS-1387(LPC) DN(VDS) Torque <br /> inch mm inch mm inch mm inch mm inch mm inch mm inch mm inch mm ft-lb n-m <br /> VSR-2 2 DN50 2.375 60.3 .065 1.651 0.109 2.77 0.154 3.91 0.142 3.6 0.091 2.3 <br /> VSR-21/2 2.5 - 2.875 73.0 .084 2.134 0.120 3.05 0.203 5.16 - - - - 1.25+.125/-.062 33.0±2.0 <br /> VSR-21/2 - DN65 3.000 76.1 - - 0.142 3.6 0.102 2.6 <br /> VSR-3 3 DN80 3.500 88.9 .083 2.108 0.120 3.05 0.216 5.49 0.157 4.0 0.114 2.9 <br /> VSR-31/2 3.5 - 4.000 101.6 - - 0.120 3.05 0.226 5.74 - - - - 20 27 <br /> VSR-4 4 DN100 4.500 114.3 .084 2.134 0.120 3.05 0.237 6.02 0.177 4.5 0.126 3.2 <br /> 2.00±.125 50.8t2.0 <br /> VSR-5 5 - 5.563 141.3 - - 0.134 3.40 0.258 6.55 - - - - <br /> VSR-6 6 DN150 6.625 168.3 2.921 1 0.134 3.40 1 0.280 7.11 0.197 5.0 0.157 4.0 <br /> VSR-8 8 1 DN200 8.625 219.1 0.148 3.76 1 0.322 1 8.18 1 0.248 6.3 0.177 4.5 <br /> Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com <br /> 5401146-REV N 10/21 PAGE 2 OF 5 <br />