Laserfiche WebLink
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 15 <br /> DATE: 7/25/2024DOCUMENTS\HYDRAULIC CALCS\MCKESSON TI\MCKESSON TI-SYSS.SDF <br /> JOB TITLE: McKesson TI <br /> WATER SUPPLY CURVE <br /> 72+ <br /> I <br /> I <br /> I <br /> 66+ <br /> I <br /> I <br /> * <br /> 60\ <br /> I\ <br /> I \ <br /> \0 <br /> 54+ \ <br /> I \ <br /> I \ <br /> I \ <br /> P 48+ \ <br /> R I \ <br /> E I \ <br /> S I \ <br /> S 42+ \ <br /> U I \ <br /> R I \ <br /> E I \ <br /> 36+ \ <br /> ( I \ <br /> P I \ <br /> S I \ <br /> I 30+ \ <br /> I \ <br /> I \ <br /> I \ <br /> 24+ \ <br /> I \ <br /> I \ <br /> X * <-20.0 psi @ 2052 gpm <br /> 18+ Flow Test Point <br /> I <br /> I <br /> 1=====_________________________ <br /> 12+ LEGEND " <br /> I <br /> X = Required Water Supply " <br /> 20.00 psi @ 730.6 gpm " <br /> 6+ <br /> 0 = Available Water Supply " <br /> 54.93 psi @ 730.6 gpm " <br /> I <br /> 0++-+---+----+-----+------+--------+--------+---------+-----------+ <br /> 8001200 1600 2000 2400 2800 3200 3600 4000 <br /> FLOW (GPM) <br />