1 <br /> ' Proposed Jaynes Monroe Elementary School Replacement Subsurface Exploration, Geologic Hazards, andRevised Geotechnical Engineering Report <br /> Everett, Washington Design Recommendations <br /> backfilled walls, which are free to yield laterally at least 0.1 percent of their height, may be <br /> designed using an equivalent fluid equal to 35 pounds per cubic foot (pcf). Fully restrained, <br /> ' horizontally backfilled, rigid walls that cannot yield should be designed for an equivalent fluid <br /> of 50 pcf. Walls with sloping backfill up to a maximum gradient of 2H:1V should be designed <br /> using an equivalent fluid of 55 pcf for yielding conditions or 75 pcf for fully restrained <br /> ' conditions. If parking areas are adjacent to walls, a surcharge equivalent to 2 feet of soil <br /> should be added to the wall height in determining lateral design forces. <br /> As required by the 2006 IBC, retaining wall design should include a seismic surcharge <br /> pressure in addition to the equivalent fluid pressures presented above. Considering the site <br /> soils and the recommended wall backfill materials, we recommend a seismic surcharge <br /> pressure of 51I and 10H psf, where H is the wall height in feet for the active and at-rest <br /> loading conditions, respectively. The seismic surcharge should be modeled as a rectangular <br /> distribution with the resultant applied at the midpoint of the walls. <br /> The lateral pressures presented above are based on the conditions of a uniform backfill <br /> consisting of excavated on-site soils, or imported structural fill compacted to 90 percent of <br /> ' ASTM:D 1557. A higher degree of compaction is not recommended, as this will increase the <br /> pressure acting on the walls. A lower compaction may result in settlement of the slab-on-grade <br /> or other structures supported above the walls. Thus, the compaction level is critical and must <br /> be tested by our firm during placement. Surcharges from adjacent footings or heavy <br /> construction equipment must be added to the above values. Perimeter footing drains should be <br /> provided for all retaining walls, as discussed under the "Drainage Considerations" section of <br /> Ithis report. <br /> It is imperative that proper drainage be provided so that hydrostatic pressures do not develop <br /> ' against the walls. This would involve installation of a minimum 1-foot-wide blanket drain to <br /> within 1 foot of finish grade for the full wall height using imported, washed gravel against <br /> the walls. The blanket drain should be continuous with and freely communicate with the <br /> footing drain. <br /> 13.1 Passive Resistance and Friction Factors <br /> Lateral loads can be resisted by friction between the foundation and the natural glacial soils or <br /> supporting structural fill soils, and by passive earth pressure acting on the buried portions of <br /> ' the foundations. The foundations must be backfilled with structural fill and compacted to at <br /> least 95 percent of the maximum dry density to achieve the passive resistance provided below. <br /> We recommend the following allowable design parameters: <br /> ' • Passive equivalent fluid = 250 cf <br /> q P <br /> • Coefficient of friction = 0.30 <br /> 1 <br /> ' October.5, 2009 ASSOCIATED EARTH SCIENCES, INC. <br /> BWG/!d-KE090312A3-Projecis120090312IKEIWP Page 18 <br /> 1 <br />