Laserfiche WebLink
2. The accessible access isles serving the accessible parking stalls do not appear to have <br />curb cut ramps on Sheet L1.09. ANSI Section 502.4 <br />a. Though not strictly required per ANSI Section 502.4 they are arguably required by <br />the generic route of travel language in IBC Section 1104.1 <br />3. A minimum of 9 Type A units should be provided. The 9al unit should be a'0' bedroom <br />unit due to proportional distribution. Section 1107.6.2.2.1 <br />4. The doors in a series at Vestibule 128 should have a minimum of 4 feet clearance beyond <br />the swing of the interior doors to the exterior exit doors. ANSI Section 404.2.5 <br />5. The post -mounted signage for the accessible parking spaces should be shown on the <br />plans. Sections 1111.1 & ANSI 502.7 <br />Energy <br />1. No comments <br />STRUCTURAL <br />1. Comments to be forwarded under separate letter when structural review is completed. <br />In order for the processing of your application to continue, it will be necessary to provide the <br />Building Division with two new sets of revised construction documents reflecting the corrections <br />requested. Please include a response letter which indicates how the corrections were resolved. <br />All codes cited refer to the 2015 International Building Code (IBC), 2015 International Existing <br />Building Code (IEBC), the 2015 International Fire Code (IFC), the 2015 International Mechanical <br />Code (IMC), and/or the 2015 Washington State Energy Code (WSEC), as amended by the State <br />of Washington and adopted by the City of Everett. The current IBC referenced standard for <br />accessible design is the 2009 "Accessible and Usable Buildings and Facilities" (ICC/ANSI <br />A117.1). Federal ADA regulations and standards may be more restrictive. <br />These comments address building issues only. Additional revisions or additions may be required <br />by other departments (such as Utilities, Traffic, Planning or Fire). All required submittals must <br />be of sufficient detail and information to ensure that the proposed structure will be constructed <br />in compliance with all adopted codes. <br />Sincerely, <br />Tony <br />Building Official <br />3200 Cedar Street p 425.257.8810 ® tice@everettwa.gov <br />everettwa.gov <br />O Everett, WA 98201 O 425.257.8857 fax everettwa.gov <br />