Laserfiche WebLink
Flow Summary - NFPA 2007 <br /> A-PEX Design Services Inc. Page 3 <br /> CHELSEA HEIGHTS LOT 47 PLAN LENNON GL-One Head Calculation (H.13) Date 7/22/2024 <br /> SUPPLY ANALYSIS <br /> Node at Static Residual Available <br /> Source Pressure Pressure Flow Pressure Total Demand Required Pressure <br /> STIR 87.0 20 500.0 86.871 17.0 37.434 <br /> NODE ANALYSIS <br /> Pressure Discharge <br /> Node Tag Elevation Node Type at Node at Node Notes <br /> H.13 116.0 4.9 12.03 17.0 0.05 324 <br /> H.11 116.0 12.88 <br /> H.7 116.0 13.36 <br /> T.22 116.0 13.57 <br /> T.24 108.0 19.37 <br /> S.1 104.0 21.56 <br /> PRV 100.0 30.53 <br /> MTR 100.0 35.02 <br /> STIR 100.0 37.43 <br /> H.14 116.0 12.31 <br /> H.17 116.0 12.86 <br /> H.16 116.0 13.33 <br /> T.28 116.0 13.45 <br /> T.27 116.0 13.57 <br /> T.26 108.0 18.52 <br /> H.18 108.0 18.63 <br /> T.25 108.0 19.37 <br /> H.12 116.0 13.57 <br /> H.3 116.0 13.57 <br /> HA 116.0 13.57 <br /> T.19 116.0 13.57 <br /> H.1 116.0 13.57 <br /> H.6 116.0 13.57 <br /> H.15 108.0 18.55 <br /> T.23 108.0 18.68 <br /> H.10 108.0 18.74 <br /> T.20 108.0 18.83 <br /> T.21 108.0 18.84 <br /> H.5 108.0 18.98 <br /> H.2 108.0 19.12 <br /> H.8 108.0 19.21 <br /> H.9 108.0 18.84 <br /> Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 <br />