Laserfiche WebLink
SYSTEM: SPF-2 <br />AREA SERVED: STAIR #2 <br />Fan Information <br />1. Rated voltage: 208 <br />2. Actual Operating Voltage: 214 <br />3. Rated Amperage: 5.6 <br />4. Actual Operating Amperage: 1.0 <br />5. Fan RPM: 26.0 HZ <br />6. Number Fan Belts: DIRECT DRIVE <br />7. Fan Belts Condition: DIRECT DRIVE <br />Measurements Taken <br />Floor <br />Inches H2O <br />Floor <br />Inches <br />H2O <br />Floor <br />Door Force <br />(LBS) <br />Floor <br />Door Force <br />(LBS.) <br />G-OUTSIDE <br />0.15 <br />4T" <br />0.17 <br />G- <br />OUTSIDE <br />13 <br />4T" <br />25 <br />G-PARKING <br />0.16 <br />5T" <br />0.18 <br />G- <br />PARKING <br />14 <br />5T" <br />26 <br />1ST <br />0.17 <br />1ST <br />24 <br />2NID <br />0.17 <br />2ND <br />24 <br />3RID <br />0.17 <br />3RD <br />26 <br />General <br />16. Do stair shafts have flush? CFM <br />17. Were measurements taken from atmospheric pressure? <br />18. Were measurements taken from shaft and the main occupied area? <br />19. What was static pressure? 0.15 to 0.18 in. H2O <br />20. Were readings taken at every 5th floor? <br />21. Do fans operate when fire alarm is activated? <br />22. Do fans operate on emergency power? <br />23. If no sprinklers, is elevator shaft pressure 0.15 in H2O or greater? <br />24. Do elevator shaft pressures measure 0.10 in H2O, in 100% automatic <br />sprinklered building? <br />25.AII doors (stairway and elevator) operate correctly? <br />26. System can be operated manually? <br />27. Does life safety core type building have 0.05 in H2O between pressurized <br />core and tenant area? <br />28.Are gaskets in good condition on stair and elevator doors? <br />29. Do all dampers, controls work properly on shaft pressurization system? <br />30. Do stair shaft pressures measure 0.10 in H2O? <br />Additional Measurements. Calculations and Comments: <br />EMERGENCY POWER TEST PERFORMED BY OTHERS. <br />YES <br />NO <br />N/A <br />❑ <br />❑ <br />® <br />❑ <br />❑ <br />® <br />❑ <br />❑ <br />❑ <br />❑ <br />® <br />❑ <br />❑ <br />® <br />❑ <br />❑ <br />❑ <br />❑ <br />® <br />❑ <br />❑ <br />® <br />❑ <br />❑ <br />® <br />❑ <br />❑ <br />Shaft Pressurization Page 4 of 4 <br />