Laserfiche WebLink
Four Corners- Building D Page 5 of 15 <br />All <br />Engineering <br />Stairway Pressurization and Door Opening Force Test <br />Test Date: 2/15/2024 Outside Temp: 39°F <br />Level <br />Stair <br />Level <br />APressure <br />Acceptable Range <br />inches w.c. <br />APressure <br />Measured <br />inches w.c. <br />Force to Set <br />Door in <br />Motion <br />(max. 30 lb) <br />Properly <br />rated fire <br />door with <br />gasketing? <br />Door closer <br />provided <br />and door <br />latches? <br />Pass/ Fail <br />5 <br />Stair 1 <br />Stair to corridor <br />0.10 < Test < 0.35 <br />0.18 <br />26 <br />Pass <br />Pass <br />PASS <br />4 <br />Stair 1 <br />Stair to corridor <br />0.10 < Test < 0.35 <br />0.18 <br />23 <br />Pass <br />Pass <br />PASS <br />3 <br />Stair 1 <br />Stair to corridor <br />0.10 < Test < 0.35 <br />0.17 <br />25 <br />Pass <br />Pass <br />PASS <br />2 <br />Stair 1 <br />Stair to corridor <br />0.10 < Test < 0.35 <br />0.16 <br />25 <br />Pass <br />Pass <br />PASS <br />1 <br />Stair 1 <br />Stair to corridor <br />0.10 < Test < 0.35 <br />0.14 <br />24 <br />Pass <br />Pass <br />PASS <br />G <br />Stair 1 <br />Stair to garage <br />0.10 < Test < 0.35 <br />0.15 <br />*DNA <br />Pass <br />Pass <br />PASS <br />G <br />Stair 1 <br />Stair to exterior <br />0.10 < Test < 0.35 <br />0.16 <br />*DNA <br />Pass <br />Pass <br />PASS <br />5 <br />Stair 2 <br />Stair to corridor <br />0.10 < Test < 0.35 <br />0.18 <br />26 <br />Pass <br />Pass <br />PASS <br />4 <br />Stair 2 <br />Stair to corridor <br />0.10 < Test < 0.35 <br />0.17 <br />25 <br />Pass <br />Pass <br />PASS <br />3 <br />Stair 2 <br />Stair to corridor <br />0.10 < Test < 0.35 <br />0.17 <br />26 <br />Pass <br />Pass <br />PASS <br />2 <br />Stair 2 <br />Stair to corridor <br />0.10 < Test < 0.35 <br />0.17 <br />24 <br />Pass <br />Pass <br />PASS <br />1 <br />Stair 2 <br />Stair to corridor <br />0.10 < Test < 0.35 <br />0.17 <br />24 <br />Pass <br />Pass <br />PASS <br />G <br />Stair 2 <br />Stair to garage <br />0.10 < Test < 0.35 <br />0.16 <br />*DNA <br />Pass <br />Pass <br />PASS <br />G <br />IStair 2 <br />Stair to exterior <br />0.10 < Test < 0.35 <br />0.15 <br />*DNA <br />I Pass <br />Pass <br />PASS <br />Verified by: <br />Travis Allen <br />Company: Date: <br />Allen Engineering, PLLC 2/15/2024 <br />Comments: <br />*Door Swings Outward and latch releases upon alarm. <br />www.AllenFPE.com 4412 Shelby Road. Lynnwood WA 98087 (425) 954-2050 <br />