Laserfiche WebLink
Four Corners- Building D Page 11 of 15 <br />Allen <br />Engineering <br />Smoke Control Sequence Test <br />Test Conditions <br />Item <br />Protocol <br />Yes <br />No <br />Building/Floor: 3 <br />1 <br />All systems NORMAL. <br />X <br />Initiating Device: SD <br />2 <br />Activate an alarm initiating device. <br />X <br />IL <br />3 <br />Alarm system activates fire alarm visual & <br />audible appliances per matrix. <br />X <br />4 <br />Verify posture of floor dampers MD-1 and <br />MD-2 OPEN per matrix. <br />X <br />5 <br />Verify smoke control fans SPF-1 and SPF-2 ON <br />per matrix. <br />X <br />6 <br />Verify elevator lobby smoke door and <br />corridor fire doors CLOSED per matrix. <br />X <br />7 <br />Verify posture of floor HVAC and dampers <br />per matrix. <br />X <br />8 <br />Alarm, fan, and damper status correctly <br />annunciated on FSCP. <br />X <br />9 <br />Return all systems to NORMAL. <br />X <br />Verified by: Company: <br />Travis Allen Allen Engineering, PLLC <br />Comments: <br />Date: <br />2/15/2024 <br />www.AllenFPE.com 4412 Shelby Road. Lynnwood WA 98087 (425) 954-2050 <br />