Laserfiche WebLink
Four Corners Building E Page 5 of 14 <br />Allen <br />Engineering <br />Stairway Pressurization and Door Opening Force Test <br />Test Date: 6/13/2024 Outside Temp: 57°F <br />Level <br />Stair <br />Level <br />APressure <br />Acceptable Range <br />inches w.c. <br />APressure <br />Measured <br />inches w.c. <br />Force to Set <br />Door in <br />Motion <br />(max. 301b) <br />Properly <br />rated fire <br />door with <br />gasketing? <br />Door closer <br />provided <br />and door <br />latches? <br />Pass/ Fail <br />5 <br />Stair <br />Sta i r to corridor <br />0.10 < Test < 0.35 <br />0.23 <br />29 <br />Pass <br />Pass <br />Pass <br />4 <br />Sta irl <br />Sta i r to corridor <br />0.10 < Test < 0.35 <br />0.22 <br />28 <br />Pass <br />Pass <br />Pass <br />3 <br />Sta irl <br />Sta i r to corridor <br />0.10 < Test < 0.35 <br />0.22 <br />25 <br />Pass <br />Pass <br />Pass <br />2 <br />Sta irl <br />Sta i r to corridor <br />0.10 < Test < 0.35 <br />0.21 <br />25 <br />Pass <br />Pass <br />Pass <br />1 <br />Sta irl <br />Sta i r to corridor <br />0.10 < Test < 0.35 <br />0.21 <br />28 <br />Pass <br />Pass <br />Pass <br />G <br />Stair <br />Sta it to garage <br />0.10 < Test < 0.35 <br />0.2 <br />*DNA <br />Pass <br />Pass <br />Pass <br />G <br />Stair <br />Sta i r to exterior <br />0.10 < Test < 0.35 <br />0.2 <br />*DNA <br />Pass <br />Pass <br />Pass <br />5 <br />Stair <br />Sta i r to corridor <br />0.10 < Test < 0.35 <br />0.18 <br />27 <br />Pass <br />Pass <br />Pass <br />4 <br />Stair <br />Sta i r to corridor <br />0.10 < Test < 0.35 <br />0.19 <br />26 <br />Pass <br />Pass <br />Pass <br />3 <br />Stair <br />Sta i r to corridor <br />0.10 < Test < 0.35 <br />0.18 <br />28 <br />Pass <br />Pass <br />Pass <br />2 <br />Stair <br />Sta i r to corridor <br />0.10 < Test < 0.35 <br />0.18 <br />28 <br />Pass <br />Pass <br />Pass <br />1 <br />Stair <br />Sta i r to corridor <br />0.10 < Test < 0.35 <br />0.17 <br />28 <br />Pass <br />Pass <br />Pass <br />G <br />Stair <br />Sta it to garage <br />0.10 < Test < 0.35 <br />0.17 <br />*DNA <br />Pass <br />Pass <br />Pass <br />G <br />Stair <br />Sta i r to exterior <br />0.10 < Test < 0.35 <br />0.17 <br />*DNA <br />Pass <br />Pass <br />Pass <br />Verified by: <br />Travis Allen <br />Company: Date: <br />Allen Engineering, PI -LC 6/13/24 <br />Comments: <br />*Door Swings Outward and latch releases upon alarm. <br />www.AllenFPE.com 4412 Shelby Road. Lynnwood WA 98087 (425) 954-2050 <br />