Laserfiche WebLink
Four Corners Building E Page 14 of 14 <br />Allen <br />engineering <br />Smoke Control Weekly Self Test Verification <br />rest Conditions <br />Item <br />Protocol <br />Yes <br />I No <br />1 <br />All systems set to NORMAL. <br />X <br />2 <br />Activate the weekly self test. <br />X <br />Initiating <br />Device: MP <br />3 <br />Activate an alarm initiating device. <br />X <br />4 <br />Verify self test aborts and smoke control <br />system initiates proper response. <br />X <br />Building/ <br />Floor: G <br />5 <br />Alarm system activates fire alarm visual & <br />laudible appliances throughout building. <br />X <br />6 <br />Alarm, fan, damper status correctly <br />annunciated on FSCP. <br />X <br />7 <br />Verify smoke control fans and dampers <br />ON/OPEN per matrix. <br />X <br />8 <br />Return all systems to NORMAL. <br />X <br />9 <br />Set weekly self test to activate. <br />X <br />10 <br />Activate an alarm initiating device. <br />X <br />11 <br />Wait for weekly test to initiate and verify that <br />that weekly self test does not interrupt alarm <br />event. <br />X <br />12 <br />lReturn all systems to NORMAL. <br />X <br />Verified by: Company: Date: <br />Travis Allen Allen Engineering, PLLC 6/13/24 <br />Comments: <br />