Laserfiche WebLink
i Permit Inspections <br /> V E R E T T City of Everett <br /> WASHINGTON <br /> 2/21/2023 2/21/2023 ELEC 05-SERVICE STEVE BANKS CORRECTION eTRAKiT Inspection Request <br /> REQUIRED <br /> Notes: <br /> 2/17/2023 1:09 PM HOME RUN ELECTRIC LLC <br /> use contact above for access <br /> Contact Name:Brian Smith-HOME RUN ELECTRIC LLC <br /> Site Address:2701 WETMORE AVE <br /> Phone:2062514068 <br /> e-Mail:admin@homerunelectricllc.com <br /> Grounded,conductors and equipment grounding conductors must travel with each set of parallel conductors through out feeder conduits.AIC is over <br /> 10 K so rejecter clips must be installed in disconnect.Verify that the 10K breakers are sufficient behind the fuses installed. Properly phase all <br /> contractors. <br /> 3/14/2023 3/14/2023 ELEC 05-SERVICE STEVE BANKS TAPPROVAL 400 amp feeder to 4 units <br /> Notes: <br /> 3/13/2023 1:30 PM HOME RUN ELECTRIC LLC <br /> please call above number for access-Brian Smith <br /> Contact Name:Brian Smith-HOME RUN ELECTRIC LLC <br /> Site Address:2701 WETMORE AVE <br /> Phone:2062514068 <br /> e-Mail:admin@homerunelectricllc.com <br /> 400 amp feeder to units 1,2,3&4. <br /> 3/14/2023 3/14/2023 ELEC 10-FINAL STEVE BANKS APPRVD-PERMIT 4 residential units <br /> FINAL <br /> Notes: <br /> 4 residential units. <br /> I <br /> Printed:Wednesday,06 August, 2025 5 of 5 rk <br /> SUPERION <br />