Laserfiche WebLink
Flow Summary - NFPA 2007 <br /> A-PEX Design Services Inc. Page 3 <br /> CHELSEA HEIGHTS LOT 10- One Head Calculation (H.16) Date 8/26/2024 <br /> SUPPLY ANALYSIS <br /> Node at Static Residual Available <br /> Source Pressure Pressure Flow Pressure Total Demand Required Pressure <br /> STIR 87.0 20 500.0 86.922 13.0 29.67 <br /> NODE ANALYSIS <br /> Pressure Discharge <br /> Node Tag Elevation Node Type at Node at Node Notes <br /> H.16 116.0 4.9 7.04 13.0 0.05 256 <br /> H.11 116.0 7.9 <br /> H.10 116.0 8.24 <br /> T.21 116.0 8.67 <br /> T.20 108.0 13.06 <br /> T.23 108.0 13.12 <br /> T.28 108.0 13.18 <br /> T.27 108.0 13.19 <br /> H.12 108.0 13.23 <br /> H.8 108.0 13.39 <br /> T.22 108.0 13.48 <br /> T.25 108.0 13.52 <br /> S.1 104.0 15.42 <br /> PRV 100.0 24.29 <br /> MTR 100.0 28.2 <br /> STIR 100.0 29.67 <br /> H.18 116.0 7.45 <br /> H.15 116.0 7.73 <br /> H.17 116.0 8.21 <br /> H.14 116.0 8.49 <br /> T.26 116.0 8.72 <br /> HA 116.0 8.67 <br /> H.5 116.0 8.68 <br /> H.1 116.0 8.69 <br /> H.3 116.0 8.69 <br /> H.6 116.0 8.7 <br /> T.19 116.0 8.7 <br /> H.9 116.0 8.71 <br /> T.24 116.0 8.72 <br /> H.7 108.0 13.12 <br /> H.2 108.0 13.35 <br /> H.13 108.0 13.18 <br /> Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 <br />