Laserfiche WebLink
B-B-HORTON" <br /> Pacific Ridge Series <br /> R.F.I. - ENGINEERING <br /> THELON B CHELSEA HEIGHTS LOT 32 CITY OF EVERETT <br /> Pacific Ridge Homes Issued By: Jason Atkin <br /> 17921 Bothell-Everett Hwy Suite 100 Bothell WA 98012 Date Requested: 8/26/2024 <br /> Phone: (425)438-8444 <br /> SUBJECT: Missing (2) 2x6 at Electrical Panel <br /> DESCRIPTION: <br /> The electricians installed their electrical panel drop where the(2)2x6 point load post is supposed to go so the(2)2x6 is not installed.We are <br /> asking for a 4x header so the electricians still have a path to the top of the Panel. <br /> SOLUTION: <br /> Install a 4x8 header centered above the electrical panel to support the(2)2x6 point load from above. Install two 2x6 trimmers and one 2x6 king <br /> stud each end. <br /> II <br /> CO 4 <br /> - + � <br /> R S08 <br /> CS16x3'-0"- <br /> PLATE TO PLATE <br /> A <br /> kg <br /> r'` I O <br /> J <br /> m <br /> iL <br /> APPROVED <br /> By Ryan Hartman at 11:56 am,Aug 27, 2024 <br /> Thank you, <br /> Brian Lampe,P.E.,S.E. <br /> BTL Engineering <br /> ENG <br /> BTT 19011 Wood-Sno Road NE,Suite 100 <br /> 1 1J Woodinville,WA 98072-4436 <br /> Phone:(425)814-8448 <br /> Fax:(425)821-2120 <br /> RFI Thelon B 2018 2024 8-26 Missing(2)2x6 at Electrical Panel 1 of 1 8/27/2024 <br />