i Permit Inspections <br /> V E R E T T City of Everett <br /> WASHINGTON <br /> 1/3/2023 1/3/2023 ELEC 05-SERVICE MICHAEL CORRECTION as noted <br /> WICKLANDER REQUIRED <br /> Notes: <br /> georgeb@callbrinc.com <br /> in unit 202 panel,close any unused openings per NEC 110.12(A)no more than 1/4"nm sheathing is allowed in a junction box or panel Per 314.17 <br /> 1/11/2023 1/11/2023 ELEC 05-SERVICE MIKE BEARDA NO ACCESS <br /> Notes: <br /> 425-588-6142 <br /> GEORGEB@CALLBRINC.COM <br /> 2:27pm <br /> 1/13/2023 1/13/2023 ELEC 05-SERVICE MICHAEL APPROVAL <br /> WICKLANDER <br /> Notes: <br /> 425-367-7882 <br /> JOSHD@CALLBRINC.COM <br /> Corrections made approve service. <br /> 1/26/2023 1/26/2023 ELEC 10-FINAL MICHAEL CORRECTION <br /> WICKLANDER REQUIRED <br /> Notes: <br /> 425-367-7882 <br /> JOSHD@CALLBRINC.COM <br /> Provide accurate directory(schedule)per NEC 408.4AAFCI breakers are required to the modified circuits per 210.12. <br /> 2/1/2023 2/1/2023 ELEC 10-FINAL MICHAEL PARTIAL <br /> WICKLANDER APPROVAL <br /> Notes: <br /> 425-367-7882 <br /> JOSHD@CALLBRINC.COM <br /> Partial final in units 202;302.Unit 102 doesn't have power yet. <br /> 8/4/2023 8/4/2023 ELEC 10-FINAL MICHAEL APPRVD-PERMIT <br /> WICKLANDER FINAL <br /> Notes: <br /> 425-367-7882 <br /> joshd@callbrinc.com <br /> I <br /> Printed:Thursday, 17 August,2023 2 of 2 rk <br /> SUPERION <br />