Seismic Bracing
<br /> TOLCOT" Fig. 980 - Universal Swivel Sway Brace Attachment - 3/8" to 3/4" (UL Listed)
<br /> Size Range: One size fits bracing pipe 1"(25mm)thru 2'150mm1, B-Line series
<br /> OPM C U us
<br /> 12 gauge(2.6mm)channel,and all structural steel up to 1/4"(31.7mm)thick. LISTED
<br /> Material: Steel
<br /> Function: Multi-functional attachment to structure or braced pipe fitting.
<br /> Features: This product's design incorporates a concentric attachment k
<br /> opening which is critical to the performance of structural seismic connections.NFPA 13 (2016)9.3.5.8.4 indicates clearly that fastener table load values areU
<br /> based only on concentric loading. Mounts to any surface angle. Break off bolt
<br /> head assures verification of proper installation.Installation: Fig.980 is the structural or transitional attachment component ?
<br /> of a longitudinal or lateral sway brace assembly. It is intended to be combined
<br /> with the"bracing pipe"and TOLCO'braced pipe"attachment, Fig. 1000, 1001,
<br /> 2002,3000,4L,4LA,4A or approved attachment to pipe to form a complete Set soli
<br /> bracing assembly. NFPA 13 guidelines should be followed. Included
<br />' ware
<br /> To Install: Place the Fig,980 onto the"bracing g Mounting Not I ncl d Included
<br /> g pipe'.Tighten the set bolt until Is Not Included
<br /> the head breaks off.Attachment can pivot for adjustment to proper brace angle.
<br /> Approvals:—Underwriters Laboratories Listed in the USA(UL)and
<br /> { )
<br /> Canada(cUL). Included in our Seismic Engineering Guidelines approved by the
<br /> State of California Office of Statewide Health Planning and Development
<br /> IOSWPD). For additional load, spacing and placement information relating to
<br /> OSHPD projects, please refer to our Seismic Engineering Guidelines,
<br /> OPM-0052-13. "
<br /> For FM Approval information refer to FM Approved page 61.
<br /> Note: Fig.980 Swivel Attachment and Fig. 1001, 1000,2002,4A,4L,4LA,or
<br /> approved attachment to pipe that make up a sway brace system of UL Listed
<br /> attachments and bracing materials which satisfies the requirements of
<br /> Underwriters Laboratories and the National Fire Protection Association (NFPA)
<br /> Finish: Plain, Electro-Galvanized or Stainless Steel. 1-
<br /> Contact customer service for alternative finishes.
<br /> Fig.Order By: Figure number and finish. Fig.gao
<br /> / Fig.980
<br /> Pat.#6,273,372, Pat.#6,517,030,Pat.#1i,953,174,
<br /> Pat. #6,708,930, Pat.#7,191,987,Pat.#7,441,730,
<br /> Pat. #7,669,806 +- Brace o
<br /> Fig.980
<br /> I
<br /> Lateral Brace .. _ . Longitudinal Brace
<br /> Fig.4B
<br /> shown
<br /> Part M(g.Hdw. Mounting Hole Max.Design Approx.
<br /> Number Size A 8 D Load IcULus) W000
<br /> in. (mm) in. (mm) in, Win) in. (niml in. (mm) Ihs. (kg)
<br /> t3/8'.'i`I9.5) ;'i'' .51/4"1133.3}i:'.:i`:`s1`:17/8 :{47.6) :1`.i:;.13/32":'110.3► 2015 I8.96f'::`;:::::.;149.'(67.6)
<br /> 980-1/2 1/2" (12.7) 51/4" (133.3) 17/8"147.6) 17/32" (13.5) 2015 (8.96) 148 (67.1)
<br /> 5/8" 115.9) 51/4 :`I133.3) : 17le(47.6) 1 t/I6".(17.5) :. ` 2015 f 8.96) .: 147 (66.71:
<br /> 980-3/4 3/4" (19.0) 51/4" (133.3) 17/8"147.6) 13/16" (26.5) 2015 (8.96) 146 (66.2)
<br /> Standard size.
<br /> Ilmportantl; For.:;lead.information wheq;using Fig:9$O,wlth:Pre�hfstall.ed.Or;past-installed.:concrete::anchors.;in,
<br /> cmnpllance with NFPA.13{2018)or ASCE 7=70,1noluding prying factors,see load taUles on.pages AL 1 thru AL 21`
<br /> Eaton's B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
<br /> resulting in a listed seismic bracing assembly.Eaton B-Line Division warranty for seismic bracing components will be the warranty
<br /> provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton,except that, in addition to the other
<br /> exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to 13-Line series seismic bracing components that are
<br /> combined with products not provided by Eaton.
<br /> All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified.
<br /> _._... ... ..0_._... _._............._._................ ..... .................._.................. .. ......._.._.._.................
<br /> Eaton B-Line series Fire Protection Solutions